Part Number Hot Search : 
0120A 56083 D1212 BP60220 SKBB500 C3120 CSCD3 UPD780
Product Description
Full Text Search
 

To Download S5-155U Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
  contents notes on using this manual and on the ce symbol 1 centralized and distributed configuration of a programmable controller 2 installation guidelines 3 central controllers and expansion units power supply units 4 cpus, memory cards, memory submodules, interface submodules 5 multiprocessor operation/ coordinators 6 interface modules 7 digital input/output modules 8 analog input/output modules 9 monitoring module 10 connector assignments 11 appendices appendix a guidelines for handling electrostatically-sensitive devices (esd) b index 11/99 s5-135u/155u system manual this manual has the order number: 6es5998-0sh21 simatic edition 07
ii this manual contains notices which you should observe to ensure your own personal safety, as well as to protect the product and connected equipment. these notices are highlighted in the manual by a warning triangle and are marked as follows according to the level of danger: ! warning indicates that death, severe personal injury or substantial property damage can result if proper precautions are not taken. note draws your attention to particularly important information on the product, handling the product, or to a particular part of the documentation. the device/system may only be set up and operated in conjunction with this manual. only qualified personnel should be allowed to install and work on this equipment. qualified persons are defined as persons who are authorized to commission, to ground, and to tag circuits, equipment, and sys tems in accordance with established safety practices and standards. note the following: ! warning this device and its components may only be used for the applications described in the catalog or the technical description, and only in connection with devices or components from other manufacturers which have been approved or recommended by siemens. this product can only function correctly and safely if it is transported, stored, set up, and installed correctly, and operated and maintained as recommended. ! caution ul + csa: lithium battery replacement danger of explosion if battery is incorrectly replaced. replace only with same or equivalent type recommended by the manufacturer. dispose of used batteries according to the manufacturer's instructions. ! warning fm warning - do not disconnect while circuit is live unless location is known to be nonhazardous simatic ? and simatic net ? , and simatic hmi ? are registered trademarks of siemens ag. third parties using for their own purposes any other names in this document which refer to trademarks might infringe upon the rights of the trademark owners. we have checked the contents of this manual for agreement with the hardware and software described. since deviations cannot be precluded entirely, we cannot guarantee full agreement. however, the data in this manual are reviewed regularly and any necessary corrections included in subsequent editions. suggestions for improvement are welcomed. ? siemens ag 1993 subject to change without prior notice. disclaimer of liability copyright ? siemens ag 1993 all rights reserved the reproduction, transmission or use of this document or its contents is not permitted without express written authority. offenders will be liable for damages. all rights, including rights created by patent grant or registration of a utility model or design, are reserved. siemens ag bereich automatisierungs- und antriebstechnik geschaeftsgebiet industrie-automatisierungssysteme postfach 4848, d-90327 nuernberg siemens aktiengesellschaft 6es5998-0sh21 safety guidelines qualified personnel correct usage trademarks
iii system manual c79000-g8576-c199-07 contents 1 notes on using this manual and on the ce symbol 1-1 . . . . . . . . . . . . . . . . . . . . . . . notes on using this manual 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . notes on the ce symbol 1-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . notes for machine manufacturers 1-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . safety notes 1-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 centralized and distributed configuration of a programmable controller 2-1 . . . 2.1 application 2-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2 centralized and distributed configuration 2-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2.1 installing a plc with centralized configuration 2-4 . . . . . . . . . . . . . . . . . . . . . . 2.2.2 installing a plc with distributed configuration 2-5 . . . . . . . . . . . . . . . . . . . . . . . 2.3 examples 2-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 installation guidelines 3-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.1 principles of installation of systems for emc 3-2 . . . . . . . . . . . . . . . . . . . . . . . . 3.1.1 overview of possible types of interference 3-2 . . . . . . . . . . . . . . . . . . . . . . . . . 3.1.2 the most important basic rules for ensuring emc 3-6 . . . . . . . . . . . . . . . . . . 3.2 installation of programmable controllers for emc 3-8 . . . . . . . . . . . . . . . . . . . . 3.2.1 basic rules for assembling and grounding the inactive metal parts 3-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.2 example of cabinet assembly for emc 3-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.3 example of rack and wall mounting for emc 3-11 . . . . . . . . . . . . . . . . . . . . . . . 3.3 wiring of programmable controllers for emc 3-12 . . . . . . . . . . . . . . . . . . . . . . . 3.3.1 routing of cables 3-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.3.2 equipotential bonding 3-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.3.3 shielding of cables and lines 3-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.3.4 special measures for interference-free operation 3-17 . . . . . . . . . . . . . . . . . . . 3.3.5 checklist for the electromagnetically compatible installation of control systems 3-19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.4 power supplies for programmable controllers and i/os 3-20 . . . . . . . . . . . . . . 3.4.1 power supplies for control systems with simatic s5 3-20 . . . . . . . . . . . . . . . 3.4.2 connecting the programmable controller and load power 3-21 . . . . . . . . . . . . 3.4.3 connecting non-floating or floating modules 3-26 . . . . . . . . . . . . . . . . . . . . . . . 3.5 interference-free installation of centralized and distributed interface circuits 3-28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5.1 interference-free installation of centralized interface circuits 3-28 . . . . . . . . . 3.5.2 interference-free installation of distributed interface circuits 3-28 . . . . . . . . . . 3.6 interference-free connection of monitors 3-30 . . . . . . . . . . . . . . . . . . . . . . . . . . .
iv system manual c79000-g8576-c199-07 3.6.1 interference-free connection of a monitor to the cp of the s5 controller 3-30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.6.2 shielding and grounding 3-31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.7 selection and installation of cabinets with simatic s5 3-33 . . . . . . . . . . . . . . . 3.7.1 types of cabinet 3-34 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.7.2 clearances in cabinets 3-34 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.7.3 removal of power dissipation from cabinets 3-37 . . . . . . . . . . . . . . . . . . . . . . . . 3.7.4 examples for determining the type of cabinet 3-38 . . . . . . . . . . . . . . . . . . . . . . 3.7.5 determining the power dissipation of modules 3-39 . . . . . . . . . . . . . . . . . . . . . . 4 central controllers and expansion units power supply units 4-1 . . . . . . . . . . . . . 4.1 s5-135u/155u central controller 4-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1.1 technical description 4-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1.2 installation 4-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1.3 startup 4-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1.4 repair guidelines 4-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1.5 technical specifications 4-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2 expansion units 4-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2.1 technical description of the expansion units 4-16 . . . . . . . . . . . . . . . . . . . . . . . . 4.2.2 installing the expansion units 4-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2.3 technical specifications of the expansion units 4-18 . . . . . . . . . . . . . . . . . . . . . 4.3 power supply units 4-19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3.1 product overview 4-19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3.2 setting and connecting the power supply unit 4-23 . . . . . . . . . . . . . . . . . . . . . . 4.3.3 fault indications/fault diagnostics 4-36 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3.4 maintenance and repairs 4-40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3.5 description of internal sequences in the power supply unit 4-49 . . . . . . . . . . . 4.3.6 technical specifications of the power supply units 4-51 . . . . . . . . . . . . . . . . . . 4.4 6es5 955-3na12 power supply unit 4-57 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4.1 technical description 4-57 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4.2 setting the power supply unit 4-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4.3 installation 4-63 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4.4 operation 4-64 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4.5 maintenance 4-66 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4.6 technical specifications 4-68 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.5 fan submodules 4-70 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.5.1 technical description 4-70 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.5.2 setting and connecting the fan submodule 4-72 . . . . . . . . . . . . . . . . . . . . . . . . 4.5.3 technical specifications 4-74 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . contents
v system manual c79000-g8576-c199-07 5 cpus, memory cards, memory submodules, interface submodules 5-1 . . . . . . . . 5.1 cpu 948b -3ua13 or cpu 948b -3ua23 5-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1.1 technical description 5-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1.2 installation and startup 5-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1.3 interfaces of the cpu 948 5-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1.4 technical specifications 5-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2 cpu 948 5-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2.1 technical description 5-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2.2 installation and startup 5-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2.3 interfaces of the cpu 948 5-27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2.4 technical specifications 5-28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3 cpu 928b -3ub21 5-30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3.1 technical description 5-30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3.2 installation and startup 5-33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3.3 technical specifications 5-40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.4 cpu 928b 5-42 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.4.1 technical description 5-42 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.4.2 installation and startup 5-45 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.4.3 technical specifications 5-52 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.5 cpu 928 -3ua21 5-54 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.5.1 technical description 5-54 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.5.2 installation and startup 5-56 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.5.3 technical specifications 5-61 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.6 cpu 928 5-62 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.6.1 technical description 5-62 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.6.2 installation and startup 5-64 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.6.3 technical specifications 5-70 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.7 cpu 922 5-71 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.7.1 technical description 5-71 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.7.2 installation and startup 5-73 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.7.3 technical specifications 5-79 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.8 374 flash eprom cards 5-80 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.8.1 technical description 5-80 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.8.2 notes on operation 5-80 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.8.3 technical specifications 5-81 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.9 376 memory submodules 5-82 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.9.1 technical description 5-82 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.9.2 notes on operation 5-82 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.9.3 technical specifications 5-83 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.10 377 memory submodules 5-84 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.10.1 technical description 5-84 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.10.2 notes on operation 5-84 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.10.3 ram submodules with battery backup 5-85 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.10.4 technical specifications 5-90 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.11 interface submodules 5-92 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.11.1 installing and removing the interface submodules 5-93 . . . . . . . . . . . . . . . . . . . 5.11.2 pg submodule 5-95 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . contents
vi system manual c79000-g8576-c199-07 5.11.3 v.24 submodule 5-99 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.11.4 tty submodule 5-106 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.11.5 rs422 a/485 submodule 5-112 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.11.6 sinec l1 submodule 5-118 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.11.7 technical specifications of the interface submodules 5-122 . . . . . . . . . . . . . . . . 6 multiprocessor operation/coordinators 6-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.1 introduction 6-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2 starting the multiprocessor operation 6-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.3 coordinator modes 6-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.4 923a coordinator module (is no longer supplied) 6-15 . . . . . . . . . . . . . . . . . . . . 6.4.1 technical description 6-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.4.2 settings on the coordinator 6-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.5 923c coordinator module 6-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.5.1 technical description 6-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.5.2 settings on the coordinator 6-23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.6 technical specifications of the coordinators 6-28 . . . . . . . . . . . . . . . . . . . . . . . . 7 interface modules 7-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1 the 300 and 312 interface modules 7-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1.1 indicators and controls 7-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1.2 modes/jumper assignments of the im 300 7-5 . . . . . . . . . . . . . . . . . . . . . . . . . . 7.2 the 301 and 310 interface modules 7-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.2.1 indicators and controls 7-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.2.2 modes/jumper assignments of the im 301 7-12 . . . . . . . . . . . . . . . . . . . . . . . . . . 7.3 the 304 and 314 interface modules 7-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.3.1 indicators and controls 7-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.3.2 modes/jumper assignments of the im 304 7-16 . . . . . . . . . . . . . . . . . . . . . . . . . . 7.3.3 modes/jumper assignments of the im 314 7-18 . . . . . . . . . . . . . . . . . . . . . . . . . . 7.4 technical specifications 7-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.4.1 6es5 721 connecting cable 7-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.4.2 6es5 7602 terminator 7-23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 digital input/output modules 8-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1 technical description 8-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1.1 design 8-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1.2 function of the enable inputs 8-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1.3 special features of the 432 digital input module 8-8 . . . . . . . . . . . . . . . . . . . . . 8.1.4 special features of the di/dq 482 8-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.2 installation and startup 8-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.2.1 setting the module address 8-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.2.2 removing and inserting modules 8-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.2.3 marking of modules 8-20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.2.4 connecting the signal lines 8-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.2.5 connection of outputs in parallel and switching on the load via a contact 8-22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.2.6 short-circuit protection and fusing 8-24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.2.7 quenching for inductive loads 8-25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . contents
vii system manual c79000-g8576-c199-07 8.3 common technical specifications 8-28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.4 specification sheets for the modules 8-30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.4.1 6es5 420-4ua13/4ua14 digital input module 8-30 . . . . . . . . . . . . . . . . . . . . . . . 8.4.2 6es5 430-4ua13/4ua14 digital input module 8-32 . . . . . . . . . . . . . . . . . . . . . . . 8.4.3 6es5 431-4ua12 digital input module 8-34 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.4.4 6es5 432-4ua12 digital input module 8-36 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.4.5 6es5 434-4ua12 digital input module 8-39 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.4.6 6es5 435-4ua12 digital input module 8-42 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.4.7 6es5 436-4ua12 digital input module 8-44 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.4.8 6es5 436-4ub12 digital input module 8-46 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.4.9 6es5 441-4ua13/4ua14 digital output module 8-48 . . . . . . . . . . . . . . . . . . . . . 8.4.10 6es5 451-4ua13/4ua14 digital output module 8-50 . . . . . . . . . . . . . . . . . . . . . 8.4.11 6es5 453-4ua12 digital output module 8-52 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.4.12 6es5 454-4ua13/4ua14 digital output module 8-54 . . . . . . . . . . . . . . . . . . . . . 8.4.13 6es5 455-4ua12 digital output module 8-56 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.4.14 6es5 456-4ua12 digital output module 8-58 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.4.15 6es5 456-4ub12 digital output module 8-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.4.16 6es5 457-4ua12 digital output module 8-62 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.4.17 6es5 458-4ua12 digital output module 8-64 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.4.18 6es5 458-4uc11 digital output module 8-67 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.4.19 6es5 482-4ua11 digital input/output module 8-69 . . . . . . . . . . . . . . . . . . . . . . . 9 analog input/output modules 9-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.1 technical description 9-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.2 common technical specifications 9-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.3 the 460 analog input module 9-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.3.1 design 9-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.3.2 function of the enable input 9-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.3.3 special features of the 460 analog input module 9-8 . . . . . . . . . . . . . . . . . . . . 9.3.4 setting the module address 9-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.3.5 removing and inserting modules 9-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.3.6 marking of modules and front connectors 9-15 . . . . . . . . . . . . . . . . . . . . . . . . . . 9.3.7 connecting the signal lines 9-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.3.8 connection of sensors 9-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.3.9 connecting a compensating box for thermal e.m.f. measurement 9-19 . . . . 9.3.10 connecting resistance thermometers in the standard pt 100 range 9-20 . . 9.3.11 connecting resistance thermometers in the extended pt 100 range 9-21 . . 9.3.12 broken wire signal 9-22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.3.13 connecting transducers 9-23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.3.14 measured-value representation 9-24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.3.15 technical specifications 9-29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.4 the 463 analog input module 9-35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.4.1 design 9-35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.4.2 function of the enable input 9-35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.4.3 special features of the 463 analog input module 9-39 . . . . . . . . . . . . . . . . . . . . 9.4.4 setting the module address 9-39 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.4.5 removing and inserting modules 9-42 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.4.6 marking of modules and front connectors 9-44 . . . . . . . . . . . . . . . . . . . . . . . . . . 9.4.7 connecting the signal lines 9-45 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.4.8 measured-value representation 9-46 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.4.9 technical specifications 9-47 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . contents
viii system manual c79000-g8576-c199-07 9.5 the 465 analog input module 9-50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.5.1 design 9-50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.5.2 function of the enable input 9-50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.5.3 special features of the 465 analog input module 9-54 . . . . . . . . . . . . . . . . . . . . 9.5.4 setting the module address 9-56 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.5.5 removing and inserting modules 9-59 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.5.6 marking of modules and front connectors 9-61 . . . . . . . . . . . . . . . . . . . . . . . . . . 9.5.7 connecting the signal lines 9-62 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.5.8 connecting a compensating box for thermal e.m.f. measurement 9-63 . . . . 9.5.9 connecting resistance thermometers to the 465 analog input module 9-64 . 9.5.10 broken wire signal for resistance thermometers 9-66 . . . . . . . . . . . . . . . . . . . 9.5.11 connecting transducers 9-67 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.5.12 measured-value representation 9-68 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.5.13 technical specifications 9-72 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.6 the 466 analog input module 9-77 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.6.1 design 9-77 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.6.2 special features of the 466 analog input module 9-77 . . . . . . . . . . . . . . . . . . . . 9.6.3 startup for analog input 466-3la11 9-77 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.6.4 startup for analog input 466-4ua11 9-84 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.6.5 removing and inserting modules 9-91 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.6.6 marking of modules and front connectors 9-93 . . . . . . . . . . . . . . . . . . . . . . . . . . 9.6.7 connecting the signal lines 9-94 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.6.8 connecting sensors to the 466 analog input module 9-95 . . . . . . . . . . . . . . . . . 9.6.9 measured-value representation 9-98 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.6.10 technical specifications 9-102 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.7 the 470 analog output module 9-106 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.7.1 design 9-106 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.7.2 function of the enable input 9-106 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.7.3 special features of the 470 analog output module 9-110 . . . . . . . . . . . . . . . . . . 9.7.4 setting the module address 9-110 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.7.5 removing and inserting modules 9-113 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.7.6 marking of modules and front connectors 9-115 . . . . . . . . . . . . . . . . . . . . . . . . . . 9.7.7 connecting the signal lines 9-116 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.7.8 connecting loads to the 470 analog output module 9-117 . . . . . . . . . . . . . . . . . 9.7.9 measured-value representation 9-119 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.7.10 technical specifications 9-120 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 monitoring module 10-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1 application 10-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1.1 design 10-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1.2 mode of operation 10-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1.3 block diagram 10-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1.4 fault detection 10-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1.5 resetting 10-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2 installation 10-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2.1 possible configurations 10-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2.2 removing and inserting 10-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2.3 connecting the reset input 10-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2.4 switch positions of the relay contact 10-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2.5 installation guidelines 10-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.3 operation 10-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . contents
ix system manual c79000-g8576-c199-07 10.3.1 addressing 10-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.3.2 setting the address switches s1, s2, s3, s4 10-12 . . . . . . . . . . . . . . . . . . . . . . . 10.3.3 setting the switch s5 10-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.4 technical specifications 10-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.5 address table 10-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 connector assignments 11-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . a appendix a-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . b guidelines for handling electrostatically-sensitive devices (esd) b-1 . . . . . . . . . b.1 what is esd? b-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . b.2 electrostatic charging of persons b-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . b.3 general protective measures against electrostatic discharge damage b-4 . index index-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . contents
x system manual c79000-g8576-c199-07 contents
1-1 system manual c79000-g8576-c199-07 notes on using this manual and on the ce symbol notes on using this manual the s5-135u/155u plc is a member of the family of simatic s5 programmable (logic) controllers. the controller can be used in single and in multiprocessor operation with up to four cpus. in multiprocessor operation, each cpu processes its individual user program independently of the other cpus (multicomputing). the following are available as cpus: cpu 948 for fast word and binary signal processing especially fast double-word and floating point processing and for large programs with a high storage requirement. programming in step 5. when you use a cpu 948 you have an S5-155U plc. cpu 928b for fast word and binary signal processing and for communication. programming in step 5. cpu 928 for fast binary signal processing and for word processing. programming in step 5. cpu 922 (r processor) for word processing (computing controlling monitoring signaling). programming in step 5. you can combine the cpus arbitrarily at the cpu slots in the central controller: cpu slot requirement cpu 948/cpu 928b/cpu 928 2 slots cpu 922/cpu 928-3ua21/ cpu 928b-3ub21 cpu 948b-3ua13/ -3ua23 1 slot cpus available slots 1
1-2 system manual c79000-g8576-c199-07 pointers on how this manual is organized are given as a guide below. they will assist you when using your s5-135u/155u programmable controller.  at the start of this manual you will find the a safety-related guidelines o and the a esd guidelines .o you must observe these to the letter and follow them during the entire time you are working with the s5-135u/155u plc. if your plc requires repair, you must observe the repair guidelines in section 4.1.4.  chapter 3 contains the installation guidelines with information on interference-free installation of the s5-135u/155u plc. which of the remaining chapters of this manual you may require when working with your plc will depend on the extent of your automation task and on the configuration of your plc. for a basic configuration in single-processor operation without expansion units, you will need the following chapters:  chapter 4 describes the central controller (cc) in section 4.1. the technical features, installation, startup and maintenance of the cc are described here. section 4.3 describes the power supply units. you will find a separate description of the 6es5 955-3na12 power supply unit in section 4.5. both sections describe the installation and startup as well as the necessary maintenance on the power supply units. the 24 v/4 a load power supply is described in section 4.4.  chapter 5 contains the instructions for the individual cpus. the technical features, installation and startup of the individual cpus are described here. the various methods of operating the cpus are also described, as are the cpu statuses where they can be directly indicated by the leds on the module. if you use memory submodules or memory cards (cpu 948), you can look up the necessary information in sections 5.7 to 5.9.  chapter 8 and chapter 9 describe the digital and analog i/o modules. the installation, wiring and operation of these modules are described here. individual i/o modules exhibit specific features which are discussed in separate chapters. to configure your plc with expansion units (eus) you will need the following chapters:  chapter 2 shows how you can configure a plc with expansion units in a centralized or distributed arrangement.  chapter 4 , section 4.2, describes the eu 183u, eu 184u, eu 185u and eu 187u. those eus which operate with their own power supply unit are described in section 4.3.  chapter 7 describes the interface modules (ims) which serve for data communication between central controllers and expansion units. to operate two or more cpus in multiprocessor mode in your plc, you will need chapter 6.  chapter 6 describes multiprocessor operation. this chapter contains all the measures you must take for startup of the plc in multiprocessor operation. sections 6.5 and 6.6 describe the 923c and 923a coordinators. how the manual is organized notes on usin g this manual and on the ce s y mbol
1-3 system manual c79000-g8576-c199-07 chapter 11 lists the connector assignments of the individual modules and subracks. the appendix contains the ordering data for the products described in this manual, references to further reading material and the index of keywords in this manual. notes on usin g this manual and on the ce s y mbol
1-4 system manual c79000-g8576-c199-07 notes on the ce symbol the following applies to the simatic products described in this manual: products which carry the ce symbol fulfil the requirements for the ec directive 89/336/eec on aelectromagnetic compatibility.o the ec declarations of conformity and the documentation relating to this are available to the authorities concerned, according to the above ec directive, article 10 (2), from: siemens aktiengesellschaft automation group a&d as e48 postfach 1963 d-92209 amberg germany products which do not carry the ce symbol meet the requirements and standards given in this manual under the respective atechnical specificationso sections. for simatic s5, the following fields of application apply according to this ce symbol: field of application requirement for emitted interference noise immunity industry en 50081-2: 1993 en 50082-2: 1995 the installation guidelines and safety-related guidelines given in this manual must be observed during startup and when operating simatic s5 devices. moreover, the following rules must be observed when using certain modules. programmable controllers of the type simatic s5-135u/S5-155U must be installed in metal cabinets according to these installation guidelines. to protect the modules from static discharge, the user must discharge his body's electrostatic charge before opening a cabinet. ec directive on emc 89/336/eec fields of application observing the installation guidelines installing the devices working on cabinets notes on usin g this manual and on the ce s y mbol
1-5 system manual c79000-g8576-c199-07 additional measures are required when using the following modules. a shielded signal cable is required for the following modules: order number module 6es5 453-4ua12 digital output module 453-4 6es5 457-4ua12 digital output module 457-4 a filter (sifi c b841213-c-b30 or equivalent) is required in the 230 v ac load voltage supply for the following modules: order number module 6es5 436-4ua12 digital input module 436-4 6es5 436-4ub12 digital input module 436-4 6es5 456-4ua12 digital output module 456-4 6es5 456-4ub12 digital output module 456-4 a filter (sifi c, b841213-c-b30 or equivalent) is required in the 24 v dc load voltage supply for the following modules: order number module 6es5 261-4ua11 proportioning module ip 261 6es5 453-4ua12 digital output module 453-4 6es5 457-4ua12 digital output module 457-4 notes on individual modules notes on usin g this manual and on the ce s y mbol
1-6 system manual c79000-g8576-c199-07 notes for machine manufacturers the simatic programmable controller is not a machine in the sense of the ec directive on machines. therefore, there is no declaration of conformity for simatic as regards the ec directive 89/392/eec on machines. the ec directive 89/392/eec on machines controls machine requirements. here, a machine is understood to be the entire sum of devices or parts involved (see also en 292-1, paragraph 3.1). simatic is part of the electrical equipment for a machine and must therefore be included in the procedure for checking conformity by the machine manufacturer. the en 60204-1 standard (machine safety, general requirements for the electrical equipment for machines) applies to the electrical equipment for machines. the following table should help you with the declaration of conformity and shows which criteria apply to en 60204-1 (as at june 1993) for simatic. en 60204-1 subject/criterion remarks para. 4 general requirements requirements are fulfilled if the machines are assembled/installed according to the installation guidelines. see also the explanations on the previous pages. para. 11.2 digital i/o interfaces requirements are fulfilled. para. 12.3 programmable equipment requirements are fulfilled if the machines are installed in lockable cabinets to protect them from memory modifications by unauthorized persons. para. 20.4 voltage tests requirements are fulfilled. introduction ec directive 89/392/eec on machines electrical equipment for machines to en 60204 notes on usin g this manual and on the ce s y mbol
1-7 system manual c79000-g8576-c199-07 safety notes risks involved in the use of so-called simatic-compatible modules of non-siemens manufacture athe manufacturer of a product (simatic in this case) is under the general obligation to give warning of possible risks attached to his product. this obligation has been extended in recent court rulings to include parts supplied by other vendors. accordingly, the manufacturer is obliged to observe and recognize such hazards as may arise when a product is combined with products of other manufacture. for this reason, we feel obliged to warn our customers who use simatic products not to install so-called simatic-compatible modules of other manufacture in the form of replacement or add-on modules in simatic systems. our products undergo a strict quality assurance procedure. we have no knowledge as to whether outside manufacturers of so-called simatic-compatible modules have any quality assurance at all or one that is nearly equivalent to ours. these so-called simatic-compatible modules are not marketed in agreement with siemens; we have never recommended the use of so-called simatic-compatible modules of other manufacture. the advertising of these other manufacturers for so-called simatic-compatible modules wrongly creates the impression that the subject advertised in periodicals, catalogs, or at exhibitions had been agreed with us. where so-called simatic-compatible modules of non-siemens manufacture are combined with our simatic automation systems, we have a case of our product being used contrary to recommendations. because of the variety of applications of our simatic automation systems and the large number of these products marketed worldwide, we cannot give a concrete description specifically analyzing the hazards created by these so-called simatic-compatible modules. it is beyond the manufacturer's capabilities to have all these so-called simatic-compatible modules checked for their effect on our simatic products. if the use of so-called simatic-compatible modules leads to defects in a simatic automation system, no warranty for such systems will be given by siemens. in the event of product liability damage due to the use of so-called simatic-compatible modules, siemens are not liable since we took timely action in warning users of the potential hazards involved in so-called simatic-compatible modules.o notes on usin g this manual and on the ce s y mbol
1-8 system manual c79000-g8576-c199-07 notes on usin g this manual and on the ce s y mbol
2-1 system manual c79000-g8576-c199-07 centralized and distributed configuration of a programmable controller this chapter contains an overview of the methods of configuring an s5-135u/155u plc. you will find a description of the types of communication between a central controller and the expansion units, and an overview of the interface modules required for the different types of communication. section contents page 2.1 application 2-2 2.2 centralized and distributed configuration 2-3 2.3 examples 2-6 chapter overview 2
2-2 system manual c79000-g8576-c199-07 2.1 application the s5-135u/155u programmable controllers comprise a central controller (cc) and, if required, one or more expansion units (eus). you need eus when there are insufficient slots in the cc for the modules to be used. various interface modules (ims) are available for communication between the cc and the eus and between the eus. it is therefore possible to install an eu or eus in the immediate vicinity of the cc (centralized configuration) or at some distance (distributed configuration). a combination of both types of configuration is also possible by connecting additional eus in a centralized configuration with a distributed eu (see figure 2-5). this is clarified on the following pages. centralized and distributed confi g uration of a pro g rammable controller
2-3 system manual c79000-g8576-c199-07 2.2 centralized and distributed configuration you can install a plc in centralized or distributed configuration according to your application. if ... then ... you wish to position the modules as closely as possible to the cc and can accept longer cable runs to the process, choose the centralized configuration you wish to position the i/o modules as closely as possible to the process and can accept longer cable runs to the cc, choose the distributed configuration with the centralized configuration, you can install the cc and eus in the same cabinet or in adjacent cabinets. data transmission is parallel. shown in the following figure is a centralized configuration. eu eu cc load power supply figure 2-1 centralized configuration centralized and distributed confi g uration of a pro g rammable controller
2-4 system manual c79000-g8576-c199-07 with the distributed configuration, a distinction is made between parallel and serial communication. the main features of these types of communication are as follows:  parallel fast data transmission line length of up to 600 m  serial slower data transmission line length of up to 3000 m 2.2.1 installing a plc with centralized configuration the following table shows which interface modules and connecting cables can be used for connecting the various expansion units to the cc in a centralized configuration. interface module in the cc expansion unit interface module in the eu connecting cable max. distance im 300-3 6es5 300-3ab11 im 301-3 1) 6es5 301-3ab13 eu 183u eu 185u (i/o mod. only) eu 183u eu 185u (i/o mod. only) im 312-3 2) 6es5 312-3ab11 im 312-3 2) 6es5 312-3ab31 fixed to the im 312 module 0.5 m; 0.95 m fixed to the im 312 module 0.5 m; 0.95 m im 300-5 6es5 300-5ca11 im 301-5 1) 6es5 301-5ca12 eu 184u eu 187u eu 184u eu 187u im 312-5 6es5 312-5ca11 im 312-5 6es5 312-5ca21 fixed to the im 312 module 0.5 m; 1.5 m fixed to the im 312 module 0.5 m; 1.5 m im 300-5 6es5 300-5lb11 er 701-1 im 306 6es5 306-7la11 6es5 705-0xxxx 0.5 m to 2,5 m 1) this im has a second interface for distributed communication. 2) the last im 312-3 always requires a 6es5 760-0ab11 terminator. to install a plc in a centralized configuration, you must observe the following conditions:  a centralized configuration is generally only suitable for connecting i/o modules (di, do, ai, ao) and some intelligent i/o modules (ips) in the eu (see the configuring aids in the catalog and chapter 4).  the line length between the im in the cc and the last im in the eu must not exceed 2 m. centralized and distributed confi g uration of a pro g rammable controller
2-5 system manual c79000-g8576-c199-07 2.2.2 installing a plc with distributed configuration to install a plc in a distributed configuration, you have a choice of parallel/symmetrical and serial communication. the following table shows which interfaces and connecting cables can be used to connect the various expansion units (eus/ers) to the cc in a distributed configuration. interface module in the cc expansion unit interface module in the eu connecting cable max. permiss. line length im 301-3 6es5 301-3ab13 (not for s5-155h) im 301-5 6es5 301-5ca12 eu 183u er 701-2 er 701-3 eu 183u eu 185u im 310 1) 6es5 310-3ab11 im 310 1) 6es5 310-3ab11 6es5 721-0xxxx 1 m to 200 m im 304 6es5 304-3ub11 er 701-2 er 701-3 eu 183u eu 185u im 314 1) 6es5 314-3ua11 6es5 721-0xxxx 1 m to 600 m im 308 6es5 308-3ua12 er 701-2 er 701-3 eu 183u eu 185u im 318-3 6es5 318-3ua11 6es5 707-5aa00 v45551-f21-b5 up to 3000 m et 100u (catalog st 52.1) im 318-8 6es5 318-8ma12 icm 560 im 308-b 6es5 308-3ub11 et 200 im 318-b 6es5 318-8mb11 cable connection im 307 6es5 307-3ua11 er 701-2 er 701-3 im 317 6es5 317-3ua11 6es5 722-2xxxx fiber optic cable up to 1500 m eu 183u eu 185u im 317 6es5 317-3ua11 pp 1) the last im 310 or im 314 always requires a 6es5 760-1aa11 terminator. the er 701-2 and er 701-3 always additionally require an im 306 for communication via an im 304, im 307 or im 308. to install a plc in a distributed configuration, you must observe the following conditions:  with the im 301/im 310 pair of interface modules, you can only use i/o modules (di, do, ai, ao) and ips without page addressing in the eus.  with the im 304/314 pair of interface modules, you can use all ips, cps and i/o modules in the eu 185u. note the im 307/317, im 308/318 and im 308-b/318-b each have their own manual (see catalog). centralized and distributed confi g uration of a pro g rammable controller
2-6 system manual c79000-g8576-c199-07 2.3 examples given in the following are some examples of centralized and distributed configuration of various simatic s5 components. eu 184u eu 184u eu 184u eu183u eu183u cc s5-135u/155u im 312-5 im 312-5 im 300-5 im 312-5 6es5 760-0ab11 im 312-3 im 312-3 im 300-3 3 eus max. 4 eus max. cc s5-135u/155u figure 2-2 centralized configuration of an s5-135u/155u with the im 300 and im 312 im 306 im 300-5lb im 306 im 306 3 ers max. er 701-1 cc s5-135u/155u er 701-1 er 701-1 figure 2-3 centralized configuration of an s5-135u/155u with er 701s centralized and distributed confi g uration of a pro g rammable controller
2-7 system manual c79000-g8576-c199-07 im 304 im 314 im 314 im 314 im314 eu185u 600m max. 6es5 760-1aa11 6es5 760-1aa11 cc s5-135u/155u 6es5 721-0xxx0 eu 185u eu185u eu 185u 4 eus max. 4 eus max. 6es5 721-0xxx0 figure 2-4 distributed configuration of an s5-135u/155u with the im 304 and im 314 im 312-3 im 312-3 im312-3 eu 183u eu 183u eu 183u eu 183u eu 183u eu 183u eu 183u eu 183u eu 183u eu 183u eu 183u im 310-3 im 310-3 im 300-3 cc s5-135u/155u im 300-3 im 301-3 6es5 760-0ab11 6es5 760-0ab11 6es5760-0ab11 6es5 760-0aa11 6es5 721-0xxx0 figure 2-5 distributed configuration of an s5-135u/155u with expansion units in centralized configuration centralized and distributed confi g uration of a pro g rammable controller
2-8 system manual c79000-g8576-c199-07 centralized and distributed confi g uration of a pro g rammable controller
3-1 system manual c79000-g8576-c199-07 installation guidelines the installation guidelines provide you with information for the interference-free installation of the simatic s5-135u/155u programmable controllers. this chapter describes the following:  paths which serve for interference pickup in programmable controllers, and five rules for ensuring electromagnetic compatibility (emc)  interference-free installation of the programmable controllers  cable routing, the connecting of cable shields and equipotential bonding between equipment  the power supplies for control and load circuits, and the different grounding concepts  shielding and grounding for the connection of centralized and distributed expansions and monitors to programmable controllers  the selection and design of cabinets section description page 3.1 principles of installation of systems for emc 3-2 3.2 installation of programmable controllers for emc 3-8 3.3 wiring of programmable controllers for emc 3-12 3.4 power supplies for programmable controllers and i/os 3-20 3.5 interference-free installation of centralized and distributed interface circuits 3-28 3.6 interference-free connection of monitors 3-30 3.7 selection and installation of cabinets with simatic s5 3-33 chapter overview 3
3-2 system manual c79000-g8576-c199-07 3.1 principles of installation of systems for emc electromagnetic compatibility (emc) is understood to mean the capability of electrical equipment to operate correctly in a defined electromagnetic environment, without being affected by the environment and without affecting the environment to an unacceptable degree. all simatic s5 products have been developed for applications in harsh industrial environments and meet high requirements for emc. before installing the control system, however, you should still carry out emc planning and involve possible interference sources in the assessment. the following chapter describes  the various paths over which interference can be picked up in the plc,  typical interference sources and their coupling mechanisms,  basic rules for ensuring emc. 3.1.1 overview of possible types of interference electromagnetic interference can be picked up over different paths by the programmable controller: sinec bus system power supply protective conductor i/o signal lines fields programmable controller figure 3-1 electromagnetic interference with programmable controllers what does emc mean? installation guidelines
3-3 system manual c79000-g8576-c199-07 depending on the propagation medium (conducted or non-conducted interference) and distance from the source, interference can be picked up by the programmable controller via different coupling mechanisms. a distinction is made between the following:  direct coupling  capacitive coupling  inductive coupling  radiated interference installation guidelines
3-4 system manual c79000-g8576-c199-07 the following table shows the four different coupling mechanisms, their causes, and possible interference sources. coupling mechanism cause typical interference sources  direct coupling direct or metallic coupling lhii  switched devices (supply ff d b i d simatic s5 interference direct coupling path always occurs when two circuits have a common conductor affected by inverters and external power supply units)  motors being started  different potentials of component cases with a common power supply  static discharges  capacitive coupling capacitive or electrical coupling bd  interference pickup via ll l i l bl simatic s5 interference capacitive coupling path occurs between conductors which are at different potentials. the degree of coupling is proportional to the voltage variation as a function of time. parallel signal cables  static discharge of the operator  contactors  inductive coupling inductive or magnetic coupling bd  transformers, motors, li ld simatic s5 interference inductive coupling path signal occurs between two conductor loops through which current is flowing. interference voltages are induced by the magnetic fluxes associated with the currents. the degree of coupling is proportional to the current variation as a function of time. electric welders  parallel ac supply cables  cables whose currents are switched  signal cables with a high frequency  unconnected coils coupling mechanisms and typical interference sources at a glance installation guidelines
3-5 system manual c79000-g8576-c199-07 coupling mechanism typical interference sources cause  radiated interference there is a radiation path when a d i bj d  local transmitters (di) simatic s5 interference radiation path conductor is subjected to an electromagnetic wave. impinging of the wave results in induced currents and voltages. (e.g. two-way radios)  spark gaps (spark plugs, collectors in electric motors, welders) installation guidelines
3-6 system manual c79000-g8576-c199-07 3.1.2 the most important basic rules for ensuring emc it is often sufficient to comply with a few elementary rules for ensuring emc. when installing the control system, therefore, observe the following five basic rules. when installing the programmable controllers, provide large-area good quality grounding of the inactive metal parts (see section 3.2).  make a large-area low-impedance interconnection of all inactive metal parts.  for screw connections on painted and anodized metal parts, either use special contact washers or remove the insulating protective layers.  if possible, do not use aluminum parts. aluminum oxidizes easily and is therefore less suitable for grounding.  make a central connection between the chassis ground and the ground/protective ground conductor system. ensure proper routing of lines when wiring (see sections 3.3.1 and 3.3.2).  arrange the cabling in line groups. (ac power cable, power supply lines, signal lines, data lines)  always install ac power cables and signal or data lines in separate ducts or bunches.  route the signal and data lines as closely as possible to grounded surfaces such as cabinet elements, metal bars and cabinet panels. ensure that cable shields are properly secured (see section 3.3.3).  data lines must be shielded. the shield should be connected at both ends.  analog lines must be shielded. for the transfer of signals with low amplitudes, it may be advisable to connect the shield at only one end.  provide the line shields with a large-area connection to a shield/protective conductor bar immediately after the cabinet inlet, and secure the shields with cable clamps. route the grounded shield as far as the module without interruption, but do not connect the shield there again.  ensure that the shield/protective ground bar has a low-impedance connection to the cabinet.  use metal or metallized connector cases for shielded data lines. installation guidelines
3-7 system manual c79000-g8576-c199-07 employ special emc measures for particular applications (see section 3.3.4).  fit quenching elements to all inductances which are not controlled by simatic s5 modules.  use incandescent bulbs for illuminating cabinets, and avoid fluorescent lamps. create a standard reference potential; ground all electrical apparatus if possible (see sections 3.4 and 3.5).  use specific grounding measures. grounding of the control system is a protective and functional measure.  system parts and cabinets with central controllers and expansion units should be connected to the ground/protective conductor system in star configuration. this serves to avoid the creation of ground loops.  in the case of potential differences between system parts and cabinets, install equipotential bonding conductors of sufficient rating. installation guidelines
3-8 system manual c79000-g8576-c199-07 3.2 installation of programmable controllers for emc measures for suppressing interference voltages are often applied only when the control system is already operational and proper reception of a useful signal is impaired. the reason for such interference is usually inadequate reference potentials caused by mistakes in equipment assembly. the following sections describe:  basic rules for grounding the inactive metal parts  examples of cabinet assembly for emc  example of rack and wall mounting for emc 3.2.1 basic rules for assembling and grounding the inactive metal parts ensure wide-area chassis grounding of the inactive metal parts when mounting the equipment. properly implemented grounding creates a uniform reference potential for the control system, and reduces the effects of picked-up interference. chassis grounding is understood to mean the electrical connection of all inactive parts. the entirety of all interconnected inactive parts is the chassis ground. inactive parts are conductive parts which are electrically isolated from active parts by basic insulation, and can only develop a voltage in the event of a fault. the chassis ground must not develop a dangerous touch voltage , even in the event of a fault. the ground must therefore be connected to the protective ground conductor. to prevent ground loops, locally separated ground elements such as cabinets, structural and machine parts, must always be connected to the protective ground system in star configuration. ensure the following when chassis grounding:  connect the inactive metal parts with the same degree of care as the active parts.  ensure low-impedance metal-to-metal connections, e.g. with large-area good quality contact.  when you are incorporating painted or anodized metal parts in the grounding, these insulating protective layers must be penetrated. use special contact washers or remove the insulating layer.  protect the connection points from corrosion, e.g. with grease.  movable grounded parts such as cabinet doors must be connected via flexible grounding strips. the grounding strips should be short and have a large surface because the surface is decisive in providing a path to ground for high-frequency interference. installation guidelines
3-9 system manual c79000-g8576-c199-07 3.2.2 example of cabinet assembly for emc the example of cabinet assembly in the figure shows the various measures, the grounding of inactive metal parts and the connection of shielded cables. this example applies only to grounded operation. follow the points numbered in the figure during assembly. 2 1 7 6 5 4 8 3 figure 3-2 example of cabinet assembly for emc installation guidelines
3-10 system manual c79000-g8576-c199-07  grounding strips if there are no large-area metal-to-metal connections, you must connect inactive metal parts such as cabinet doors and supports with grounding strips. these should be short and have a large surface.  cabinet members the cabinet members should have a large-area connection to the cabinet housing (metal-to-metal connection).  mounting bracket for subrack there must be a large-area metal-to-metal connection between cabinet member and mounting bracket.  signal lines in the case of shielded signal lines and data lines, the shield must be secured to the protective conductor bar or an additionally fitted shield bar using large-area cable clamps. cable clamp the cable clamp must enclose and make contact with the shield braid over a large area.
shield bar this bar must have a large-area connection to the cabinet members (metal-to-metal connection). it serves for grounding the cable shields. protective conductor bar the protective conductor bar must have a large-area connection to the cabinet members (metal-to-metal connection). the protective conductor bar must be connected to the protective conductor system via an external conductor (at least 10 mm 2 ). this is essential for providing a reliable path to ground for fault currents and interference currents. conductor to the protective conductor system (ground point) the conductor must have a large-area connection to the protective conductor system (ground point). installation guidelines
3-11 system manual c79000-g8576-c199-07 3.2.3 example of rack and wall mounting for emc to operate your control system in a low-interference environment whilst observing the permissible ambient conditions (see atechnical specificationso), you can mount the programmable controllers on racks or directly on walls. picked-up interference should be given a path to large metal surfaces. you should therefore secure standard sectional rails, shield and protective conductor bars to metal structural elements. for wall mounting in particular, installation on reference potential surfaces made of sheet steel has proved advantageous. when installing shielded cables, provide a shield bar for connecting the cable shields. the shield bar can also be the protective conductor bar. ensure the following for rack and wall mounting:  suitable contacting aids should be used on painted and anodized metal parts. use special contact washers or remove the insulating protective layers.  provide large-area, low-impedance metal-to-metal connections when securing the shield/protective conductor bar.  ac conductors must be covered. shield/protective conductor bar cable clamp for shield contact shielded signal line reference potential surface connection to p. ground: 10 mm  figure 3-3 wall mounting of an s5-135/155u plc installation guidelines
3-12 system manual c79000-g8576-c199-07 3.3 wiring of programmable controllers for emc the following section describes:  routing of cables within and outside cabinets  equipotential bonding between devices  single and double-ended connection of cable shields  checklist for electromagnetically compatible installation 3.3.1 routing of cables this section covers the routing of bus, signal and supply lines. the purpose of cable routing is to suppress crosstalk between cables laid in parallel. for electromagnetically compatible routing of cables and lines, it is expedient to subdivide the lines into the following line groups and lay the groups separately.  shielded bus and data lines (for programmer, op, sinec l1, sinec l2, profibus, profibus dp, printer, etc.)  shielded analog lines  unshielded lines for dc voltage  60 v  unshielded lines for ac voltage  25 v  coaxial cables for monitors  unshielded lines for dc voltage > 60 v and  400 v  unshielded lines for ac voltage > 25 v and  400 v  unshielded lines for dc and ac voltage > 400 v  lines for sinec h1 from the combination of individual groups in the following table, you can read off the conditions for laying the line groups. group a group b group c group d group a     group b     group c     group d     routing of cables within and outside cabinets group a group b group c group d installation guidelines
3-13 system manual c79000-g8576-c199-07 legend for the table  lines can be laid in common bundles or cable ducts.  lines must be laid in separate bundles or cable ducts (without minimum clearance).  lines within cabinets must be laid in separate bundles or cable ducts; outside the cabinets but within buildings, they must be laid over separate cable routes with a clearance of at least 10 cm.  lines must be laid in separate bundles or cable ducts with a clearance of at least 50 cm. outside buildings, lay the lines on metal cable trays if possible. provide the joints between cable trays with an electrical connection and ground the cable trays. when laying lines outside buildings, you must observe the valid lightning protection and grounding measures. the following applies in general: ! caution where cables and lines for simatic s5 controllers are to be laid outside buildings, you must apply measures for internal and external lightning protection. outside the buildings, lay your lines either  in metal conduit grounded at both ends, or  in concreted cable ducts with continuously connected reinforcement. protect the signal lines from overvoltages by means of  varistors or  inert gas-filled surge diverters. fit these protective devices at the cable entry into the building. note lightning protection measures always require an individual assessment of the entire installation. for clarification, please consult your siemens regional office or a company specializing in lightning protection. ensure adequate equipotential bonding between the connected equipment (see section 3.3.2). routing of cables outside buildings lightning protection equipotential bonding installation guidelines
3-14 system manual c79000-g8576-c199-07 3.3.2 equipotential bonding between separate sections of an installation, potential differences can develop if  programmable controllers and i/o devices are connected via a non-floating link, or  cable shields are connected at both ends and are grounded at different parts of the system. different ac supplies, for example, can cause potential differences. these differences must be reduced by installing equipotential bonding conductors to ensure functioning of the electronic components. the following points must be observed for equipotential bonding:  the lower the impedance of the equipotential bonding conductor, the greater is the effectiveness of equipotential bonding.  where shielded signal lines are laid between the relevant sections of the system and connected at both ends to the ground/protective conductor, the impedance of the additional equipotential bonding conductor must not exceed 10 % of the shield impedance.  the cross-section of the equipotential bonding conductor must be rated for the maximum circulating current. the following cross-sections of copper have proved to be satisfactory in practice: -16 mm  of copper for equipotential bonding conductors of up to 200 m in length -25 mm  of copper for equipotential bonding conductors of more than 200 m in length.  use copper or zinc-plated steel for equipotential bonding conductors. they must be given a large-area connection to the ground/protective conductor and protect it from corrosion.  the equipotential bonding conductor should be laid so that the smallest possible areas are enclosed between the equipotential bonding conductor and signal lines. equipotential bonding conductor signal line figure 3-4 routing of equipotential bonding conductor and signal line installation guidelines
3-15 system manual c79000-g8576-c199-07 3.3.3 shielding of cables and lines shielding is a method of attenuating magnetic, electrical or electro-magnetic interference fields. interference currents on cable shields are given a path to ground via the shield bar which is electrically connected to the housing. a low-impedance connection to the protective conductor is particularly important so that these interference currents themselves do not become an interference source. where possible, only use lines with a braided shield. the coverage density of the shield should be more than 80 %. avoid lines with a foil shield because the foil can be very easily damaged by tensile strain and compression during fitting; this results in reduced effectiveness of the shield. as a rule, line shields should always be connected at both ends. this is the only way to achieve a good degree of interference suppression in the higher frequency region. only in exceptional cases should the shield be connected at one end only, as this only achieves attenuation of the low frequencies. single-ended shield connection may be more advantageous when:  an equipotential bonding conductor cannot be laid;  analog signals (of a few mv or  a) are to be transmitted;  foil (static) shields are used. as a rule, line shields should always be connected at both ends. this is the only way to achieve a good degree of interference suppression in the higher frequency region. with data lines for serial communication, always use metal or metallized connectors. secure the shield of the data line to the connector case. do not connect the shield to pin 1 of the connector. for stationary operation, it is advisable to fully strip the insulation from the shielded cable and connect it to the shield/protective conductor bar. note in the event of potential differences between ground points, a circulating current may flow through the shield connected at both ends. in this case, install an additional equipotential bonding conductor (see section 3.3.2). shields at both ends data lines installation guidelines
3-16 system manual c79000-g8576-c199-07 please observe the following points when connecting the shield:  use metal cable clamps for securing the braided shield. the clamps must enclose the shield over a large area and provide a good contact. 1)  connect the shield to a shield bar immediately after the cable entry into the cabinet. route the shield as far as the module but do not connect it there again. ? ? ? ? ? ? ? ?? ?? ?? ? ? ? ?? ? ? ? ?? ? ? ? ? figure 3-5 example of securing shielded lines with cable clamps 1) it is advisable to check the contacts of the screening at regular intervals. installation guidelines
3-17 system manual c79000-g8576-c199-07 3.3.4 special measures for interference-free operation as a rule, inductances such as contactor or relay coils controlled by simatic s5 do not require external quenching elements in the circuit, because the quenching elements are already integrated in the modules. inductances should only be fitted with quenching elements  when simatic s5 output currents can be switched off by additionally fitted contacts, such as relay contacts. in this case the integrated quenching elements in the modules are no longer effective;  if they are not controlled by simatic s5 modules. you can place freewheel diodes, varistors or rc networks in circuits with inductances. circuitry for dc-operated inductances with diode with zener diode with varistor with rc network circuitry for ac-operated inductances figure 3-6 quenching circuits for inductances fitting quenching elements to inductances installation guidelines
3-18 system manual c79000-g8576-c199-07 a power socket should be fitted in each cabinet for the ac supply to programmers. the sockets should be powered from the distribution system to which the protective conductor for the cabinet is also connected. use incandescent bulbs, such as linestra lamps, for cabinet lighting. avoid using fluorescent lamps because they generate interference fields. if the use of fluorescent lamps cannot be avoided, apply the measures shown in the following figure. shielded cable screen over the lamp metal-enclosed switch ac filter or shielded power cable figure 3-7 measures for interference suppression of fluorescent lamps in a cabinet ac power connection for programmers cabinet lighting installation guidelines
3-19 system manual c79000-g8576-c199-07 3.3.5 checklist for the electromagnetically compatible installation of control systems emc measures notes connection of inactive parts (section 3.2) check, in particular, the connections on:  subracks  cabinet members  shield and protective conductor bars do all inactive metal parts have a large-area, low-impedance interconnection and ground? is there a satisfactory connection to the ground/protective conductor system? have insulating layers on painted and anodized surfaces been removed, or have special contact washers been used for the connections? are connections protected from corrosion, e.g. by grease? are cabinet doors connected to the cabinet element with grounding strips? routing of cables (section 3.3.1) cabling subdivided into line groups? supply cables (230 to 400 v) and signal lines laid in separate ducts or bundles? equipotential bonding (section 3.3.2) with a separate arrangement, check that the equipotential bonding conductor has been correctly laid. shielding of cables (section 3.3.3) have metal connectors been used throughout? are all analog and data lines shielded? are line shields connected to the shield or protective conductor bar at the cabinet entry? are line shields secured with cable clamps over a large area and at low impedance? are line shields connected at both ends where possible? inductances (section 3.3.4) are contactor coils which are switched via contacts, fitted with quenching elements? installation guidelines
3-20 system manual c79000-g8576-c199-07 3.4 power supplies for programmable controllers and i/os this section describes:  which circuits you must distinguish in the control system and which demands are made on the power supply.  connection and grounding concept with higher-level infeed from grounded, centrally grounded and ungrounded supplies.  connecting the power supply to non-isolated and isolated modules. 3.4.1 power supplies for control systems with simatic s5 for control systems with simatic s5, you will need:  a power supply for the internal plc circuits (control power supply)  and a load power supply for the input and output circuits. the power supply for the internal plc circuits powers the cpu and the modules used. note ensure that the control power supply is not overloaded. make a current addition and estimate the current drawn by all modules. the load power supply feeds the input and output circuits (load circuits) as well as sensors and actuators. only a power supply which offers safe electrical isolation from the ac system may be used for the 24 v dc supply. ! caution only safety-separated low voltage dc  60 v may be used for the 24 v dc supply. the safety separation can be implemented according to the requirements of, amongst other sources, vde 0100, part 410/hd 384-4-41/iec 60364-4-41 (functional extra-low voltage with safety separation) or vde 0805/en 60950/iec 60950 (safety extra-low voltage selv) or vde 0106, part 101. power supply for the plc circuits load power supply for the i/os installation guidelines
3-21 system manual c79000-g8576-c199-07 the electronic short-circuit protection of digital output modules only responds when 3-times the rated current is exceeded. you should therefore so design the load power supply units that the unit can supply the current required for shutting down in the event of a short-circuit at one output. in the event of short-circuits at digital outputs, if the load power supply is not adequately rated, a current which is higher than the rated current can flow for a longer period without responding of the electronic short-circuit protection of the dq module. operation in the overload region can destroy the module. if you use non-floating modules, you must create a common reference potential for the internal control circuits of the plc and for the load circuits. the reference potential of the load power supply should therefore be connected to the ground terminal of the plc (pe or protective conductor terminal). the ground terminal is permanently connected to the internal reference potential of the controller. note if you use switched-mode power supply units for floating analog modules and beros, you must fit an ac system filter to the input of the power supply. 3.4.2 connecting the programmable controller and load power each of the following figures shows a circuit example for connecting the control and load power supplies as well as the grounding concept for operation from:  grounded supplies  centrally grounded supplies  ungrounded supplies when assembling the control system, observe the following explanations. the text contains identification numbers relating to figures 3-8 to 3-10.  for the programmable controller, sensors and actuators, you must fit a main switch  to din vde 0113, part 1, or an isolating device to din vde 0100, part 460. if an ac plug is used as the isolating device, the socket must be in the vicinity of the central controller and must be easily accessible (vde 0805, 1.7.2). these devices are not required in the case of a subsystem where the appropriate devices are fitted at a higher level.  the circuits for sensors and actuators can be given group protection for short-circuit and/or overload  . according to vde 0100, part 725, single-phase protection is required; and all-phase protection to din vde 0113, part 1. ratings of load power supplies load power supply for non-floating modules load power supply for floating modules main switch and protection installation guidelines
3-22 system manual c79000-g8576-c199-07  for 24 v dc load circuits, you require a load power supply unit with safety separation. if an ac plug is used as the isolating device, the socket must be in the vicinity of the central controller and easily accessible (vde 0805, 1.7.2).  unregulated load power supply units require a reservoir capacitor  (rated at 200 mf per 1 a load current). connect the capacitor in parallel with the output terminals of the load power supply.  according to din vde 0113, part 1, control systems with more than five items of electromagnetic apparatus require isolation by a transformer; according to din vde 0100, part 725, it is recommended .  load power supplies should be grounded if possible
. provide a detachable connection to the protective conductor at the load power supply unit (terminal l- or m) or on the secondary side of the isolating transformer. ! caution for ungrounded power supplies, you must provide insulation monitoring if:  hazardous system states can be caused by double faults;  there is no safety separation;  circuits are operated with voltages of more than 120 v dc;  circuits are operated with voltages of more than 50 v ac. load power supply grounding installation guidelines
3-23 system manual c79000-g8576-c199-07 operation from grounded power supplies offers the best rejection of interference. cabinet control power supply l+ l l1 n l+/l1 l/n pe pe ac dc ac ac ac dc ac dc non floating output non- floating input floating output floating input l1 l2 l3 n pe programmable controller low-voltage distribution e.g. tn-s system protective conductor bar in cabinet 24 to 230 v ac load supply for ac modules 5 to 60 v dc load supply for non-floating dc modules 5 to 60 v dc load supply for floating dc modules process i/os ps cpu u 0 v int        
figure 3-8 operating a programmable controller with process i/os from a grounded supply operating a programmable controller with process i/os from a grounded supply installation guidelines
3-24 system manual c79000-g8576-c199-07 in systems with their own transformers or generators, the plc is connected to the central ground. a detachable connection should be provided so that ground faults can be measured. the plc should be insulated from cabinet/protective conductor potential. to maintain this isolated arrangement, all connected devices must be operated with capacitive grounding or ungrounded . for this reason, programmers should only be powered via an isolating transformer. cabinet control power supply l+ l- l1 l1 l2 l3 n n l+/l1 l/n pe pe ac dc ac ac ac dc ac dc non- floating input l1 l2 l3 programmable controller, insulated arrangement higher-level supply protective conductor bar in cabinet, insulated arrangement 24 to 230 v ac load supply for ac modules 5 to 60 v dc load supply for non-floating dc modules 5 to 60 v dc load supply for floating dc modules process i/os central ground, e.g. foundation ground detachable con- nection for measurement purposes ps cpu u 0 v int        
non- floating output floating input floating output figure 3-9 operating a programmable controller with process i/os from a centrally grounded supply operating a programmable controller with process i/os from a centrally grounded supply installation guidelines
3-25 system manual c79000-g8576-c199-07 in cases in which the higher-level power supply is not grounded, you must connect the programmable controller to a separate protective conductor/ground (e.g. foundation ground). operation of the plc with non-floating power supplies is not allowed. when connecting the power supplies, please note: in 3 x 230 v systems, you may connect the power supply directly to two phases. schrank control power supply l+ l l1 l2 pe l+/l1 l/l2 pe ac dc ac ac ac dc ac dc non-float- ing input l1 l2 l3 pe e.g. it system (3 x 230v) programmable controller protective conductor bar in cabinet low-voltage distribution, 24 to 230 v ac load supply for ac modules 5 to 60 v dc load supply for non-floating dc modules process i/os protective conductor grounding ps cpu u 0 v int        
non-float- ing output floating input floating output 5 to 60 v dc load supply for floating dc modules figure 3-10 operating a programmable controller with process i/os from an ungrounded supply in 3 x 400 v systems, a connection between phase and neutral conductor is not allowed (excessively high voltage in the event of a ground fault). intermediate transformers should be used in these systems. operating a programmable controller with process i/os from an ungrounded supply installation guidelines
3-26 system manual c79000-g8576-c199-07 3.4.3 connecting non-floating or floating modules shown in the following sections are the specical features when installing non-floating and floating modules. in an installation with non-floating modules, the reference potentials of the control circuit (0 v int ) and load circuits (0 v ext ) are electrically connected. the reference potential of the control circuit (0 v int ) is given by the pe or protective conductor terminal and must be connected to the reference potential of the load circuit via an externally laid conductor. shown in the following figure is a simplified installation with non-floating modules. the arrangement is independent of the grounding concept. the connections for grounding are therefore not drawn. 1l+ 1l pe control power supply 2l+ 2l dc 24 v load power supply external connection for a standard reference potential ps cpu di dq data 0 v u int  figure 3-11 simplified representation of an installation with non-floating modules the voltage drop on line  must not exceed 1 v. otherwise there will be a shift in reference potentials resulting in module malfunctions. installation with non-floating modules installation guidelines
3-27 system manual c79000-g8576-c199-07 note for 24 v dc digital output modules with electronic short-circuit protection, you must ensure that the reference potential of the load power supply is connected to terminal l- of the module. if this connection is missing (e.g. open-circuit), a typical current of 15 ma can flow at the outputs. this output circuit is sufficient  to prevent energized contactors or relays from being released  and to energize high-resistance loads (e.g. miniature relays). with floating modules the control circuit and load circuit are metallically isolated. an arrangement with floating modules is required  for all ac load circuits and  for dc load circuits which cannot be coupled. the reasons are, for example, different reference potentials of the sensors or grounding of the positive terminal of a battery. shown in the following figure is a simplified installation with floating modules. the arrangement is independent of the grounding concept. the connections for grounding are therefore not drawn. 1l+ 1l pe 24 v dc control power supply 2l+ 2l 24 v dc load power supply ps cpu di dq data 0 v u int l1 n 230 v ac load power supply figure 3-12 simplified representation of an arrangement with floating modules installation with floating modules installation guidelines
3-28 system manual c79000-g8576-c199-07 3.5 interference-free installation of centralized and distributed interface circuits subjects described in the following sections are the shielding and grounding concept with centralized and distributed interface circuits. information on component selection, the mechanical arrangement and wiring can be found in the appropriate reference manuals for the interface modules. note if you use components which are not approved for the installation of a centralized or distributed interface circuit, interference rejection may be impaired. 3.5.1 interference-free installation of centralized interface circuits when you connect the central controller and expansion unit centrally via suitable interface modules, no particular shielding and grounding measures are required. ensure, however, that  all subracks are interconnected at a low resistance;  the subracks in a grounded arrangement have star-configuration grounding;  the contact springs of the modules are clean and not bent, which could affect the path to ground for interference currents. 3.5.2 interference-free installation of distributed interface circuits if you interconnect the central controller and expansion unit in a distributed arrangement using suitable interface modules, no particular shielding and grounding measures are usually required. only in industrial environments with an extremely high level of interference is there a need for special shielding and grounding. in these cases, please observe the following points:  cable shields should be connected to the shield bar in the cabinet, immediately after the cable inlet; - insulation is fully stripped from the cable for the purpose; - braided shields are secured to the shield bar with as large an area as possible (e.g. with metal ties which enclose the shield over a large area).  shield bars should be connected to the frame or cabinet panel over a large area.  cable shields should be connected to the cabinet conductor. installation guidelines
3-29 system manual c79000-g8576-c199-07 with distributed interfacing (im 304/im 314 and im 301/im 310), ensure that the vde specifications for laying the protective ground are complied with; distributed interfacing is non-floating. the measures described above are shown in the following figure. if the permissible potential difference between ground points can be exceeded, you must install an equipotential bonding conductor (cross-section  16 mm 2 of copper). shield/protective conductor bar < 7 v cc eu im 304 im 314 figure 3-13 shielding and grounding the connecting cable with distributed interfacing, you must use the prefabricated connecting cables. you may have excess lengths of up to 100 m when installing the connecting cable. these excess lengths must be bifilar-wound and deposited at a point which is protected from electromagnetic interference. special features installation guidelines
3-30 system manual c79000-g8576-c199-07 3.6 interference-free connection of monitors these sections cover the following topics:  floating connection of cables at video inputs  shielding and grounding concept information on selecting the components can be found in catalog st80. 3.6.1 interference-free connection of a monitor to the cp of the s5 controller operator control and process monitoring systems from the coros product family can be used with monitor connections. the physical arrangement of apparatus and the interference level of the environment are important for the interference-free connection of monitors to simatic s5 control systems. the choice of monitor and video cables is governed by the following:  whether the monitor and plc are to be operated under low-interference conditions or  under industrial conditions. where the monitor and plc are installed under low-interference environmental conditions and operated over short distances, the monitor and plc are at almost the same ground potentials. interference and ground loop disturbances are therefore not expected. in these cases, you can drive the monitor both via ttl signals and via analog signals. digital cables or single-shielded coaxial cables can be used to transmit the video signals. note that the braided shield of the coaxial cable serves as the return conductor and must not be connected to the shield bar. the monitor and communication processor (cp) are interconnected without additional shielding and grounding. where the monitor and plc are installed under harsh industrial conditions and operated over great distances, the devices may be at different ground potentials. these different ground potentials may cause interference and ground loop disturbances. operation of the monitor and plc under low-interference conditions operation of the monitor and plc under industrial conditions installation guidelines
3-31 system manual c79000-g8576-c199-07 in these cases, double-shielded coaxial cables (triaxial cables) must be used to transmit the video signals. the inner braided shield of the coaxial cable serves as the return conductor and must not be connected to the shield bar. the outer braided shield provides a path to ground for interference currents and must be incorporated in the shielding and grounding measures. to avoid ground loops, the electronics ground and housing ground of the monitor must be independent. this requirement is met when:  the electronics and housing grounds of the monitor are metallically isolated,  or the electronics and housing grounds are connected via a voltage-dependent resistor (vdr) fitted by the manufacturer of the monitor. 3.6.2 shielding and grounding if the monitor and plc are used under harsh industrial conditions, you must ensure the following at the plc end:  cable shields should be connected to the shield bar in the cabinet, immediately after the cable inlet; - the video cables should be fully stripped; - the outer braided shield should be secured to the shield bar of the plc over as large an area as possible (e.g. with metal ties which enclose the shield or with cable clamps).  shield bars should be connected to the frame or cabinet panel over a large area.  shield bars should be connected to the ground point of the cabinet. you must ensure the following at the monitor end:  separate the electronics ground and housing ground. - remove the jumper at the monitor to separate the two grounds. - fit touch protection at the video sockets because hazardous touch voltages of more than 40 v may be present at the sockets after separation of the grounds.  connect the ground clamp of the monitor to the protective conductor.  connect the cable shields to the ground clamp of the monitor; - fully strip the video cables; - secure the outer braided shield to the ground clamp of the monitor over a large area. installation guidelines
3-32 system manual c79000-g8576-c199-07 shown in the following figure is a simplified representation of the shielding and grounding measures for installing the monitor and plc. shield/ protective conductor bar external shield connected to ground clamp monitor with separate electronics and housing grounds cp figure 3-14 shielding and grounding for a distributed arrangement of monitor and plc installation guidelines
3-33 system manual c79000-g8576-c199-07 3.7 selection and installation of cabinets with simatic s5 the following criteria must be observed when selecting and dimensioning a cabinet:  ambient conditions at the point of installation of the cabinet  clearances for power supplies and subracks  total power dissipation of components in the cabinet the ambient conditions at the point of installation of the cabinet (temperature, humidity, dust, effects of chemicals) govern the required degree of protection of the cabinet (ip xx) as shown in the following figure. further information on types of protection can be found in iec 529. installation guidelines
3-34 system manual c79000-g8576-c199-07 3.7.1 types of cabinet the following table provides on overview of the most common types of cabinet. it also shows the principle of heat removal, as well as the estimated, maximum achievable power loss removal and the type of protection* . open cabinets closed cabinets through-ventilation by natural convection increased through-ventilation natural convection forced circulation using fan assembly, enhanced natural convection forced circulation using heat exchanger, external ventilation inside and outside heat removal primarily by natural thermal convection, small portion via the cabinet wall increased heat removal through increased air movement heat removal only through the cabinet wall; only low power dissipation permissible. heat accumulation usually occurs in the top of the cabinet. heat removal only via the cabinet wall. forced ventilation of the internal air results in improved heat removal and prevention of heat accumulation. heat removal through exchange between heated internal air and cool outside air. the increased surface of the folded-area sectional wall of the heat exchanger and forced circulation of internal and external air permit good heat output. type of protect. ip 20 type of protect. ip 20 type of protect. ip 54 type of protect. ip 54 type of protect. ip 54 typical removable power dissipation under the following boundary conditions:  cabinet size 2200 x 600 x 600 mm  temperature difference between external and internal temperature of the cabinet: 20 5 c** up to 700 w up to 2700 w (1400 w with very fine filter) up to 260 w up to 360 w up to 1700 w * the location and ambient conditions are decisive for selection of the type of cabinet protection ( see iec 529 and din 40050). ** for other temperature differences, refer to the temperature characteristics of the cabinet manufacturer. 3.7.2 clearances in cabinets you must first define the components to be fitted in the cabinet. then calculate the total power dissipation of the individual components. the following stipulations must be observed:  the expansion units can be accommodated with the respective central controller in one cabinet, or in two or more cabinets (centralized or distributed).  on account of the required clearances and maximum permissible installation height for control elements, a maximum of three simatic s5 devices can be arranged one above the other. installation guidelines
3-35 system manual c79000-g8576-c199-07 maximum installation height for control elements: 2100 mm to din vde 0106, part 100, 2000 mm to din vde 0113. space for air circulation (400 mm deep cabinets are sufficient). 75 mm min., smaller clearances are possible with a closed cabinet roof and an additional, separate ventilation roof. 75 mm min. from obstructions (large apparatus) in the air inlet area. a maximum clearance of 400 mm is possible (50 mm min.) when devices are connected next to one another. 400 mm minimum installation height above access level for control elements, 200 mm for connections. baffles are recommended to improve the air supply. subrack e.g. er 701 subrack e.g. eu 184u subrack e.g. cc s5135u/155u load power supply inlet air exhaust air exhaust air exhaust air inlet air inlet air baffle inlet air access level see table for clearances see table for clearances figure 3-15 clearances in the cabinet installation guidelines
3-36 system manual c79000-g8576-c199-07 where subracks (cc and eu) are arranged one above the other, the installation clearances in the following table must be observed. upper subrack lower subrack min. clearances max. clearances s5-135u/ 155u or s5-115u s5-135u 75 mm 87 mm if baffle is used the maximum clearance is limited by the lengths of connecting cables for hi f dl or s5 - 90u/ 95u/ 100u s5-115u with fan 60 mm g the interface modules. s5 - 90u/ 95u/ 100u s5-115u without fan 100 mm s5-90u/ 95u/ 100u 75 mm the following two points should be observed to improve the air circulation within the cabinet:  the expansion unit with the greatest power dissipation to be removed should be the upper unit.  if subracks of the s5-135u/155u series are installed together with subracks of the s5-90u to 115u series in one cabinet, the rear panels of all subracks must be at the same distance from the rear wall of the cabinet. installation guidelines
3-37 system manual c79000-g8576-c199-07 3.7.3 removal of power dissipation from cabinets the power dissipation that can be removed from a cabinet is governed by the cabinet design, its ambient temperature and the arrangement of equipment in the cabinet. shown in the following figure is a diagram with guide values for the permissible ambient temperature of a cabinet measuring 600 x 600 x 2200 mm, as a function of power dissipation. these values only apply to the arrangement of equipment in the cabinet as given in section 3.6.2. further details can be found in catalogs nv21 and et1. 20 30 40 50 55 200 400 600 800 1000 1200 1400 w power dissipation ambient temperature in o c 1 2 3 1 closed cabinet with heat exchanger of size 11/6 (920 x 460 x 111 mm) 2 cabinet with through-ventilation by natural convection 3 closed cabinet with natural convection and forced circulation using fan figure 3-16 maximum cabinet ambient temperature as a function of power dissipation note when fitting the subracks of the s5-135u/155u series, the maximum power dissipation which can be removed by the fans must not be exceeded. the maximum removable power dissipation per unit with a supply air temperature of 55 5 c is 250 w. this value is increased by 20 w for each reduction in supply air temperature by 1 5 c. installation guidelines
3-38 system manual c79000-g8576-c199-07 ! caution modules with a hard disk drive can only be used at an ambient temperature of up to 50 5 c. 3.7.4 examples for determining the type of cabinet the following example shows the maximum permissible ambient temperature with various cabinet types and the same power dissipation. example the following equipment configuration is given: 1 central controller 200 w 2 expansion units, 250 w power dissipation each 500 w 1 load ps, 24 v/40 a, 6ev1 362-5bk00 (full load) 200 w total power disspation 900 w from figure 3-16, with a total power dissipation of 900 w, the maximum ambient temperatures given by the table are as follows: cabinet design max. permissible ambient temperature closed, with natural convection and forced circulation (curve 3) (operation not possible) open with through-ventilation (curve 2) approx. 33 5 c closed, with heat exchanger (curve 1) approx. 42 5 c installation guidelines
3-39 system manual c79000-g8576-c199-07 3.7.5 determining the power dissipation of modules the power dissipation of the modules can be found in the technical specifications of the catalogs or manuals. if these values are not yet incorporated in the technical specifications, they can be easily calculated from the current consumption. the value of current consumption must be multiplied by the corresponding voltage value. examples cpu 928b current consumption 5a/5v  power dissipation = 25 w cp 143 current consumption 4a/5v 0.5a/15v 0.04a/24v  power dissipation approx. 21 w im 304 current consumption 1.5a/5v  power dissipation = 7.5 w installation guidelines
3-40 system manual c79000-g8576-c199-07 installation guidelines
4-1 system manual c79000-g8576-c199-07 central controllers and expansion units power supply units the s5-135u/155u programmable controller comprises a central controller (cc) and, depending on the configuration, one or more expansion units (eus). expansion units are connected when there are unsufficient central controller slots, or when you wish to position i/o modules as closely to the process as possible (see also chapter 2). with the central controllers and some expansion units, the modules are directly powered and cooled via the integrated power supply plug-in module. with all other expansion units, power is supplied via the ims from the cc (see also chapter 7). section description page 4.1 s5-135u/155u central controller 4-2 4.2 expansion units 4-15 4.3 power supply units 4-19 4.4 6es5 955-3na12 power supply unit 4-57 4.5 fan submodules 4-70 chapter overview 4
4-2 system manual c79000-g8576-c199-07 4.1 s5-135u/155u central controller this description applies to the s5-135u/155u cc with the following power supply units. order no. of the cc with power supply unit input voltage 6es5 188-3ua12 6es5 955-3lc42 120 v/230 v ac, 18 a 6es5 188-3ua22 6es5 955-3lf42 120 v/230 v ac, 40 a 6es5 188-3ua32 6es5 955-3nc42 24 v dc, 18 a 6es5 188-3ua52 6es5 955-3nf42 24 v dc, 40 a 6es5 135-3ua42 6es5 955-3na12 24 v dc, 10 a 4.1.1 technical description the s5-135u/155u cc consists of a housing with backplane bus to accept the individual modules, and a power supply unit with fans to power and cool the modules. shown in the following figure are the most important parts of a central controller. 1) 2) 3) 4) 5) 6) 7) 9) 10) 8) figure 4-1 assembly of a central controller 1. housing with 21 slots for modules 2. power supply unit with fans 3. battery compartment 4. cable duct 5. locking bar 6. mounting bracket 7. sectional rail for individually locking the modules 8. backplane bus 9. filter subdrawer (optional) 10. rechargeable battery assembly of a central controller central controllers and expansion units power suppl y unit s
4-3 system manual c79000-g8576-c199-07 the housing consists of bolted sheet-steel sections with ventilation openings at the top and bottom. the housing contains the bus pcb for electrical and logical interconnection of the modules. all the slots have guiderails which accept the modules. male and female connectors are thus precisely positioned. there is a locking bar at the top of the housing to prevent the modules from becoming accidentally detached. modules with individual locking are secured in the lower sectional rail. there is a cable duct for incoming and outgoing cables at the front of the housing. the power supply unit with the fans is situated in the lower part of the central controller frame. depending on the type of power supply, the input voltage is either 24 v dc or 230/120 v ac. the ac version can be adjusted to the required ac voltage with a selector switch. the following table shows which modules can be inserted at which slots. slot no. 3 11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163 module type 923 coordinator cpu 922/ cpu 928-3ua21/ cpu 928b-3ub21 cpu 928, cpu 928b cpu 948 cp 5xx, cp 143, cp 5430, cp 5431 1) im 300-5 im 301-5 2) im 300-3, im 301-3 im 304, im 308, im 308b/im 308 c im 307 1) 3) di, dq, ai, aq 1) ip 241usw, ip 244, ip 246, ip 247, ip 252 1) ip 240, ip 241, ip 242, ip 242a, ip 242b, ip 243, ip 281 1) 4) 5) ip 245 ip 257 6) ip 260, ip 261 load power supply -951 1) electrical connection mechanical width housing power supply unit modules and slot assignments in the s5-135u/155u cc central controllers and expansion units power suppl y unit s
4-4 system manual c79000-g8576-c199-07 1) allow for particular module widths; additional slots to the right may be occupied (see catalog st 54.1). 2) in the cc with order no. 6es5 135-3ua41, only at slot 163 3) observe jumper setting on the im 307; interrupt transmission is only possible at slots 107 to 131. 4) operation at slots 27, 43, 59, 139, 147 is only possible with severely restricted functions, because no interrupts are wire d. 5) ip 243 without d/a or a/d converter can be used at slots 27, 43, 59, 139 and 147. 6) allow 1 to 4 slots for the di/dq 482 to the right of the ip 257. ! caution do not insert modules at slots which are not intended for them, otherwise these or other modules may be destroyed. the following table shows which slots have particular characteristics. the manuals for the individual modules explain how these characteristics can be utilized. slot no. 3 11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163 characteristic pg mux possible 1) 0 1 2 3 4 5 6 7 interrupt source (process interrupt) battery backup 24 v supply 15 v supply 1) the numbers indicate the station numbers for programmer (pg) communication via pg multiplexers of the cor 923c. central controllers and expansion units power suppl y unit s
4-5 system manual c79000-g8576-c199-07 the modular packaging technique allows variable configuration of a cc with modules and its adaptation to the particular automation task. the various modules carry out the following tasks:  cpu the cpu processes the input signals of the plc according to the user program, and emits the results as output signals. the following cpus can be used in the s5-135u/155u plc cpu 948 cpu 928b cpu 928 cpu 922  coordinators by using a coordinator, you can configure the s5-135u/155u as a multiprocessor controller with up to four task-oriented cpus in different combinations. each cpu processes its program independently of the others.  i/o modules the i/o modules provide the link to the process.  ip module the intelligent i/o modules (signal pre-processing modules) off-load the cpu by independently executing compute-intensive tasks such as controlling, counting and positioning.  interface modules (ims) if your cc has insufficient slots to insert all the modules required for your automation task, you can increase the number of modules with expansion units. the im modules provide the link between central controller and expansion units.  cp module cp modules allow point-to-point communication for data interchange between two plcs, between one plc and an external unit, between one plc and a sinec bus system or between one plc and the coros operator control and process monitoring system. you can use additional cp modules, such as the cp 581, cp 516, for the acquisition, storage, administration and preprocessing of large volumes of data.  vp module vp modules enable the local acquisition and displaying (visualization) of process data of a plc of the simatic s5. central controllers and expansion units power suppl y unit s
4-6 system manual c79000-g8576-c199-07 4.1.2 installation the s5-135u/155u cc is designed for installation in cabinets, on racks and walls. the s5-135/155u cc must only be accessible from the front for connection and maintenance work. consult the installation guidelines in chapter 4 for planning and implementing the installation with respect to emc. shown in the following figures are the important dimensions in mm for installation of a cc. simatics5135u simatics5 siemens 440 265.9 5 221.8 44 260.9 127.5 138.4 0 465 482.6 310 225 266.35 328 432 459 filter subdrawer figure 4-2 mounting dimensions of an s5-135u/155u central controller installing the central controller central controllers and expansion units power suppl y unit s
4-7 system manual c79000-g8576-c199-07 an air supply as shown in the following illustration must be ensured. + + + heat sink exhaust air additional plc or eu baffle rear panel bus connector bus pcb guide rail d 1) supply air locking bar cable duct fan shield filter subdrawer exhaust air + exhaust air figure 4-3 air supply to the central controller 1) d: clearance > 87 mm when a baffle is used d: clearance > 89 mm when a filter subdrawer is fitted d: clearance > 75 mm without filter subdrawer central controllers and expansion units power suppl y unit s
4-8 system manual c79000-g8576-c199-07 you can use the mounting brackets on the subrack for installation in cabinets, on racks and walls. use m6 bolts or, for wall mounting, screws of suitable size. one person can carry out the installation work. the mounting brackets can be fitted to the housing in the following ways: flush 16 5 32 figure 4-4 methods of fitting the mounting brackets the dimensions of the modules for the s5-135u/155u plc comply with the double-height eurocard format (h x d = 233.4 x 160 mm). there are modules with different mounting width. for example: slots occupied sps 1) front plate width in mm example 1 1 1 /3 20.3 cpu 922 2 2 2 /3 40.6 cpu 948 4 5 1 /3 81.3 cp 580 1) sps standard-plug-in station: 1 sps = 15.24 mm fitting the modules central controllers and expansion units power suppl y unit s
4-9 system manual c79000-g8576-c199-07 proceed as follows to fit the modules: step action 1 disconnect the cc from system power. 2 slacken the two screws with which the locking bar is fixed to the subrack. 3 pull the locking bar forward to its end stop. the rail swivels up. 4 if there is a locking pin on the lower part of the module, turn it to the horizontal position. 5 grasp the module at the front plate, insert it into the lower and upper guide rails and push it in. the connectors at the rear will engage in the sockets on the backplane bus, and the release lever on the lower part of the module will be horizontal. 6 if a locking pin is fitted, push it in and rotate it 90 degrees. if you have correctly fitted the module so far, it should no longer be possible to pull it out of the subrack. 7 swivel the locking bar down and push it back into the subrack. 8 retighten the two screws on the locking bar. some i/o modules can also be fitted or removed during operation. consult the reference manuals for the i/o modules, under arelease circuit.o free slots can be covered with dummy front plates. this improves the flow of cooling air in the unit. see the ordering information for order numbers. the connecting cables of cpus, communication processors and eu interface modules are connected with metal front connectors. there are two types of metal front connector: a metal front connector with slide lock is secured after plugging it in, by sliding the lock downward. a metal front connector with milled screws is secured to the unit with the screws. note ensure that the connectors are assigned to the correct modules to avoid damage. the connection of signal lines for the i/o modules is described in chapters 8 and 9. connections of cpus, cps and ims central controllers and expansion units power suppl y unit s
4-10 system manual c79000-g8576-c199-07 4.1.3 startup start up the cc in the sequence of steps given here. this will take you up to the first trial run of the cpu. given in parentheses are references to the chapters of the manual in which the subject is explained in detail. to ensure a straightforward sequence for the startup, commence with one cpu and no eus. proceed according to the following steps to place the cc in operation: step action 1 install the plc so that the supply of air and exhaust air are unimpeded. if you fit two or more units (cc and eu) in one cabinet, observe the clearances and use baffles where necessary (see chapter 3). 2 fit a lithium battery (see sections 4.3 and 4.4) or connect an external backup battery and connect the rechargeable battery. 3 fit the cpu and set the mode switch to stop. 4 connect the power supply and connect the 24 v dc load supply to the monitoring input. check the setting of the voltage selector switch (on 230/ 120 vac power supplies). fit a protective cover over the ac terminals. 5 switch on the power and, if present, the 24 v load supply. position the apowero switch i . reaction : green leds apower supply oko in the adc 5 vo field and in the adc 15/24 vo field light up. 6 hold the cpu switch in the overall reset position and move the switch from stop to run. reaction: the astopo led flashes rapidly. 7 repeat step 6. reaction: the astopo led lights up constantly. 8 keep the pushbutton in the reset position and move the switch from stop to run. reaction: green aruno led lights up, abaspo led (output inhibit) goes off. central controllers and expansion units power suppl y unit s
4 - 1 1 s y s t e m m a n u a l c 7 9 0 0 0 - g 8 5 7 6 - c 1 9 9 - 0 7 t h e f o l l o w i n g f l o w c h a r t p r o v i d e s a n o v e r v i e w o f t h e s e q u e n c e f o r s t a r t u p a n d v a l i d i t y c h e c k o f a c c w i t h c p u i n s e r t e d a n d w i t h n o u s e r p r o g r a m . f o r t h e c p u 9 4 8 , a l l s t e p s r e l a t i n g t o t h e m e m o r y s u b m o d u l e a r e s k i p p e d . n o n o n o n o n o n o n o c o n n e c t p o w e r s u p p l y u n i t s w i t c h o n s u p p l y v o l t a g e c p u : l e d ? b a s p ? o n l e d ? s t o p ? f l a s h i n g f a s t a l l o t h e r s o f f p s : c o r r e c t l y w i r e d ? v o l t a g e p r e s e n t ? l e d ? f a n f a u l t ? o n l e d ? v o l t a g e l o w ? o n c h e c k l o a d v o l t a g e c o n n e c t i o n c h e c k f a n c p u : l e d ? s t o p ? o n l e d ? b a s p ? o n c p u : l e d ? b a s p ? o n l e d ? s t o p ? f l a s h i n g f a s t a l l o t h e r s o f f r e p l a c e p s u n i t o . k . r e p l a c e m e m o r y s u b m o d u l e r e s e t c p u : s e t t o ? r e s e t , ? s w i t c h f r o m ? s t o p ? t o ? r u n ? c p u : l e d ? r u n ? o n , l e d ? b a s p ? o f f m e m o r y s u b m o d u l e : c o r r e c t l y i n s e r t e d ? i n s e r t m e m o r y s u b m o d u l e c o r r e c t l y c p u g e n e r a l r e s e t p s : l e d ? d c 5 v ? a n d ? d c 2 4 v ? o n , a l l o t h e r s o f f i n s e r t m e m o r y s u b m o d u l e i n c p u ( n o t w i t h t h e c p u 9 4 8 ) c p u a t ? s t o p ? r e p l a c e c p u o r r e p e a t s t a r t u p l e d ? m b l o w ? o n l e d ? r b l o w ? o n c h e c k b a c k u p b a t t . a n d r e p l a c e i f n e c e s s a r y r e p l a c e r e c h a r g e a b l e b a t t e r y r e p l a c e b t y c o m p a r t m e n t f a u l t c o r r e c t e d n o n o n o n o y e s y e s y e s y e s y e s y e s y e s y e s y e s y e s y e s p r e s s r e s e t l e d o f f a l l o t h e r s o f f p r e s s r e s e t l e d o f f f a u l t c o r r e c t e d f i g u r e 4 - 5 s t a r t u p s t a r t u p a n d v a l i d i t y c h e c k c e n t r a l c o n t r o l l e r s a n d e x p a n s i o n u n i t s p o w e r s u p p l y u n i t s
4-12 system manual c79000-g8576-c199-07 4.1.4 repair guidelines if measurements or testing become necessary whilst the unit is operational, accident prevention regulations vbg 4.0 must be observed, especially the permissible actions when working on active parts. only use tools that are suitable and approved for working on electrical equipment.  repair of an automation system may only be carried out by the siemens customer service or by qualified personnel (see above).  always disconnect the ac power plug or open the isolating switch before opening the unit. wait at least 8 minutes before pulling out and opening a power supply unit (see section 4.2.3).  parts or components of a central controller may only be replaced by types listed in catalog st 54.1 or in the appendix to this manual.  fuses may only be replaced by the same type.  instructions for maintenance of the individual components can be found in the relevant chapters of this manual. ! warning unauthorized opening and improper repairs can result in death or serious personal injury as well as considerable damage. central controllers and expansion units power suppl y unit s
4-13 system manual c79000-g8576-c199-07 4.1.5 technical specifications important for the usa and canada the following approvals have been granted for the central controllers and expansion units:  ul listing mark underwriters laboratories (ul) to standard ul 508, report e85972  csa certification mark canadian standards association (csa) to standard c 22.2 no. 142, report lr 63533c unit safety the unit complies with: vde 0160, iec 61131-2 protection against overvoltage overvoltage class 2 (not with ps -3na12) vde 0160 class of protection i type of protection (when empty slots are covered by dummy front plates) ip 20 to iec 60529/din 40050 climatic ambient conditions (tested to din iec 60068-2/-1/2/3) ambient temperature in operation (supply air measured at lower air inlet of the unit) 0 to 55 5 c transportation and storage temperature - 40 to 70 5 c temperature variation: in operation during transportation and storage (when delivered at less than 0 o c, at least 3 h acclimatization because of possible condensation) 10 k/h max. 20 k/h max. relative humidity: in operation, during transportation and storage 95% max. at 25 5 c, no condensation altitude: in operation during transportation and storage - 1000 m to + 1500 m above sea level (1080 hpa to 860 hpa) - 1000 m bis + 3500 m above sea level (1080 hpa to 660 hpa) pollutants: so 2 h 2 s 0,5 cm 3 / m 3 , 4 days 0,1 cm 3 / m 3 , 4 days mechanical ambient conditions (tested to din iec 60068-2-6) vibration during operation 10 to58 hz (const. amplitude 0.075 mm) 58 to 500 hz (const. acceleration 1g) central controllers and expansion units power suppl y unit s
4-14 system manual c79000-g8576-c199-07 noise immunity, electromagnetic compatibility (emc) rfi suppression limit value class to en 55011 a 2) conducted interference on ac supply lines (230 v ac) to en 61000-4-4 / iec 61000-4-4 (burst) to iec 61000-4-5 between two lines (  s pulses) between line and ground (  s pulses) 2 kv 1 kv 2 kv dc supply lines (24 v supply) to en 61000-4-4 / iec 61000-4-4 (burst) 2 kv signal lines to en 61000-4-4 / iec 61000-4-4 (burst) 2 kv 1) immunity to discharge of static electricity to en 61000-4-2 / iec 61000-4-2 (esd) 2) immunity of 4 kv contact discharge (8 kv air discharge) is ensured with proper installation (see chapter 3). immunity to electromagnetic rf field 2) amplitude modulated to env 50140 / iec 61004-4-3 80 to 1000 mhz 10 v/m 80% am (1 khz) immunity to electromagnetic rf field 2) pulse-modulated to env 50204 900 mhz 10 v/m 50% ed immunity to high-frequency sinusoidal to env 50141 0.15 to 80 mhz 10 v 80% am mechanical data mechanical requirements installation in stationary equipment, subject to vibration; installation on ships and in vehicles if special installation rules are observed, but not on the engine. weight approx. 14 kg dimensions (w x h x d) 482.6 x 432 x 310 mm 1) signal lines which do not serve to control the process, for example connections to the external i/o etc.: 1 kv 2) when cabinet door is closed. central controllers and expansion units power suppl y unit s
4-15 system manual c79000-g8576-c199-07 4.2 expansion units this chapter contains information on the application, installation and operation of the following expansion units. order no. of expansion unit power supply or fan subassembly 6es5 183-3ua13 6es5 183-3ua22 6es5 955-3lc42 6es5 955-3nc42 6es5 184-3ua11 6es5 184-3ua21 230/120 v ac fan subassembly 24 v dc fan subassembly 6es5 185-3ua13 6es5 185-3ua23 6es5 185-3ua33 6es5 185-3ua43 6es5 955-3lc42 6es5 955-3nc42 6es5 955-3lf42 6es5 955-3nf42 6es5 187-5ua11 various interface modules (ims) are available for communication between the cc and eus and between eus. data transmission between cc and eu, and therefore between cpu and i/o module, is governed by the im. a description of interface modules is given in chapter 7. the following table contains information on available types of expansion unit with their main features. eu type eu 183 eu 184 eu 185 eu 187 version own power supply yes no yes no with fan yes yes yes no with cable duct yes yes yes no number of slots 21 21 21 11 pluggable modules: di/dq ai/aq ip without page ip with page cp yes yes yes no no yes yes yes no no yes yes yes yes yes yes yes no no no with interrupt processing no no no no interface modules central controllers and expansion units power suppl y unit s
4-16 system manual c79000-g8576-c199-07 4.2.1 technical description of the expansion units the design of the eus is comparable to that of the cc: they comprise a compact housing with a type-dependant number of slots for modules and, according to the type of eu, a cable duct, an integral power supply unit or fan subassembly. the mounting dimensions of the eu 183u, eu 184u and eu 185u are the same as those of the 135u/155u cc (see figs. 4-3 and 4-4). the eu 187u has neither power supply unit nor cable duct. its overall height and depth are therefore different from those mounting dimensions of the other eus. simatics5135u 440 225 266 figure 4-6 mounting dimensions of the eu 187u the following tables show which modules can be inserted at which slots. modules and slot assignments of the eu 183u slot no. 3 11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163 module type im 300 im 310, im 314, im 318 im 317 im 312-3 di, dq, ai, aq signal pre-processing modules (ips) see current catalog st 54.1 for slot numbers monitoring module 313 modules and slot assignments of the expansion units central controllers and expansion units power suppl y unit s
4-17 system manual c79000-g8576-c199-07 modules and slot assignments of the eu 184u slot no. 3 11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163 module type im 312-5 di, dq, ai, aq signal pre-processing modules (ips) see current catalog st 54.1 for slot numbers monitoring module 313 modules and slot assignments of the eu 185u slot no. 3 11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163 module type coordinator 923 c communication processors (cps) im 314 r im 300 im 310, im 134 im 318 im 317 im 308 di, dq, ai, aq signal pre-processing modules (ips) see current catalog st 54.1 for slot numbers monitoring module 313 slots 19 to 75 are programmer mux-capable modules and slot assignments of the eu 187u slot no. 3 19 35 51 67 83 99 115 131 147 163 module type im 312-5 di, dq, ai, aq monitoring module 313 central controllers and expansion units power suppl y unit s
4-18 system manual c79000-g8576-c199-07 4.2.2 installing the expansion units like a cc, the eus are designed for installation in cabinets, in racks and on walls. to install an expansion unit, therefore, refer to the description for the cc and chapter 3. 4.2.3 technical specifications of the expansion units  the technical specifications of the expansion units are the same as those of the central controller except for the following (see section 4.1.5).  weight eu 183u: approx. 14 kg eu 184u: approx. 13 kg eu 185u: approx. 14 kg eu 187u: approx. 11 kg  dimensions: eu 187u: 440 x 266 x 225 mm central controllers and expansion units power suppl y unit s
4-19 system manual c79000-g8576-c199-07 4.3 power supply units power supply units are part of the s5-135u/155u central controllers and of the eu 183 and eu 185 expansion units. 4.3.1 product overview the following section provides an overview of power supply types, their functions, leds and controls and their inputs and outputs. your cc/eu contains one of the following power supply units (psus): type of psu (designation) input voltage output voltage application 6es5 955-3lc42 120 v ac 230 v ac (selectable) 5v/18a dc 15v/0.5a dc 24v/1a dc central controller 6es5 188-3ua12 expansion units 6es5 183-3ua13 6es5 185-3ua13 6es5 955-3lf42 120 v ac 230 v ac (selectable) 5v/40a dc 15v/2a dc 24v/2.8a dc central controller 6es5 188-3ua22 expansion units 6es5 185-3ua33 6es5 955-3nc42 24 v dc 5v/18a dc 15v/0.5a dc 24v/1a dc central controller 6es5 188-3ua32 expansion units 6es5 183-3ua22 6es5 185-3ua23 6es5 955-3nf42 24 v dc 5v/40a dc 15v/2a dc 24v/2.8a dc central controller 6es5 188-3ua52 expansion units 6es5 185-3ua43 the 5 v and 15 v output voltages are regulated; the 24 v output voltage has coarse stabilization. all four power supply units have safe electrical separation according to vde 0805/en 60950. note power supply units are exclusively adapted to operation with ccs/eus. power supply types central controllers and expansion units power suppl y unit s
4-20 system manual c79000-g8576-c199-07 the power supply units offer the following functions:  system power supply all the system voltages required for operation of the modules in a cc or eu are supplied.  power supply for backup (in the cc and eu 185): a lithium battery or an external battery ensure data backup when the system voltage is switched off or fails. the lithium battery remains in the cc/eu and ensures backup, even during replacement of the power supply unit instead of the lithium battery, an external battery can be connected for data backup purposes. situated on the front plate of the power supply unit are two sockets to connect an external battery. the rechargeable battery (in the power supply) continues to back up while either the lithium battery or external battery is being replaced or fails, ensuring that no data are lost.  heat removal three independent fans which are individually replaceable during operation remove the dissipated power. if a fan fails, the supply voltage for this fan is switched off and the other two fans continue operation at increased speed. the power supply units contain monitoring functions to detect the following faults:  failure of system voltage  failure of output voltages  failure of an externally applied 24 v dc load voltage (voltage monitor)  fan failure or inadequate air flow  lithium battery failure  rechargeable battery failure in this context, a voltage failure is equivalent to a drop of the monitored voltage below a preset limit (see section 4.3.6 of the technical specifications). the failure of a monitored function is signaled by the power supply units:  via led indicators on the front plate;  via relays with which signaling circuits can be switched;  via signals to the s5 bus. basic functions monitoring functions signaling functions central controllers and expansion units power suppl y unit s
4-21 system manual c79000-g8576-c199-07 based on the example of the 6es5 955-3lf41 power supply unit, the following figure shows the arrangement of inputs and outputs on the front plate of the power supply units: 6es5955-3lf42 l1 n 12 3 4 5 67 8 9 10 11 14 12 15 13 16 17 18 + + + + ac120v4,5a ac230v2,6a caution! disconnect before removing power supply! voltage selector unlock fan 1 unlock fan2 unlock fan3/res.batt . input dc 24v ext. ac line 50/60 hz enable power supply voltage monitor fan battery ext.batt. dc 4,5v fault warning alarm warning max. ac 250v/3a max. ac 250 v/ 3a voltage low fan1 mb low fan2 rb low 5vo.k. fan3 reset alarm en uh power i i 1 234 5 6 7 8 9 10 batt. 3,6v/5ah replace by trained personnel only! use battery holder c98100-a1155-b21 only! siemens output dc 24v 2,8a dc 5/15/24v internal 3v=40a 15vo.k. 24vo.k. batt.+fan the following table provides an overview of the labelling and purpose of the inputs and outputs: id label element purpose a ac 120v 4.5a ac 230v 2.6a screw terminals 1, 2, 3 ac connection and protective conductor b en screw terminal 4 enable power supply control input for power supply c u h screw terminal 5 supply for en d input dc 24v ext. screw terminals 6 and 7 voltage monitor monitors 24 v load voltage for > 16 v e fan warning max. 250v/3a screw terminals 8, 9, 10 (relay) indicates failure of a fan f fan alarm max. 250v/3a screw terminals 11, 12, 13 (relay) indicates failure of at least two fans and inadequate air flow; if jumper set accordingly, output enable is the second signal source g battery warning max. 250v/3a screw terminals 14, 15, 16 (relay) indicates that lithium battery or rechargeable battery has dropped below limit h 3v = 40a 2 test sockets current measurement sockets for test purposes only; no continuous operation; linearity range 0.5 v/6.6 a to 3 v/40 a i output dc 24v 2.8a screw terminals 17, 18 enable voltage for i/o modules j ext.batt. dc 4.5v 2 input sockets input for an external 4.5 v backup voltage inputs and outputs central controllers and expansion units power suppl y unit s
4-22 system manual c79000-g8576-c199-07 apart from the jumpers, the leds and controls of the power supply unit are fitted on the front plate. the following figure shows their locations: 6es5955-3lf42 l1 n 12 3 4 5 67 8 9 10 11 14 12 15 13 16 17 18 + + + + ac120v4,5a ac230v2,6a caution! disconnect before removing power supply! voltage selector unlock fan 1 unlock fan2 unlock fan3/res.batt . input dc 24v ext. ac line 50/60 hz enable power supply voltage monitor fan battery ext.batt. dc 4,5v fault warning alarm warning max. ac 250v/3a max. ac 250 v/ 3a voltage low fan1 mb low fan2 rb low 5vo.k. fan3 reset alarm en uh power i i 1234 5 6 7 89 10 batt. 3,6v/5ah replace by trained personnel only! use battery holder c98100-a1155-b21 only! siemens output dc 24v 2,8a dc 5/15/24v internal 3v=40a 15vo.k. 24vo.k. batt.+fan g d a h i f b c l k j m e the labelling and purpose of the leds and controls are given in the following table: id label element purpose a voltage selector 1) switch voltage selector switch: choice of 120 v or 230 v b power switch standby on/off switch (not system on/off switch) c voltage low red led low voltage at load voltage monitor input d fan 1 red led failure of fan 1 e fan 2 red led failure of fan 2 f fan 3 red led failure of fan 3 g alarm red led indicates failure of at least two fans of insufficient air flow h mb low yellow led lithium battery/external battery voltage below preset limit (3v) i rb low yellow led rechargeable battery voltage below preset limit (3v) j reset batt.+fan pushbutton reset of leds d, e, f, g, h, i when fault cleared k 5v o.k. green led lights up to indicate output voltage within permissible range l 15v o.k. green led lights up to indicate output voltage within permissible range m 24v o.k. green led lights up to indicate output voltage within permissible range 1) only on the 6es5 955-3lc42 and 6es5 955-3lf42 leds and controls central controllers and expansion units power suppl y unit s
4-23 system manual c79000-g8576-c199-07 4.3.2 setting and connecting the power supply unit before starting up your power supply unit, you must carry out certain steps according to your requirements with respect to power supply behavior in the event of a fault. power supply units are delivered in the following state:  fitted in the cc or eu frame which you ordered  with preset jumpers  ac line voltage set to 230 v (-3lc42, -3lf42) if you wish to retain this setting, you can skip steps 2 to 4 and 9. if you do not wish to fit a filter subdrawer, skip step 8. step action 1 check the setting and cabling 2 remove the power supply unit if required 3 set the jumpers if required 4 fit the power supply unit if required 5 wire the power supply unit to the installation (including fitting an isolating device to disconnect the ac line voltage) 6 fit the lithium battery 7 remove the right-hand fan and connect the rechargeable battery 8 fit the filter subdrawer if required 9 set the voltage selector switch if required 10 switch the psu on for the first time central controllers and expansion units power suppl y unit s
4-24 system manual c79000-g8576-c199-07 the following table shows the procedure for placing the power supply unit (psu) in operation without changing the jumper setting: stage description 1 fit the plc, allowing for clearances for access in the event of repairs and for adequate ventilation. observe chassis grounding. 2 fit the lithium battery (if available) in the battery compartment on the right front of the power supply unit (ensure correct polarity). note. you have to order the lithium battery separately (see ordering information). 3 remove the right-hand fan subassembly, plug in the red positive lead of its rechargeable battery and reinsert the fan. 4 check that the voltage selector switch is set to your desired voltage. 5 connect the 24 v load voltage leads to the avoltage monitoro terminals. 6 when connecting the ac leads, fit an isolating device to isolate the power supply unit from the ac line voltage. 7 connect the primary voltage leads and the protective conductor. 8 switch on the primary voltage and the 24 v load voltage. 9 use the apowero switch to switch on the power supply unit. 10 if the required basic load is in circuit, no red led lights up and the power supply unit is operational. all activities relating to startup of the power supply units are described in detail on the following pages. brief instructions for startup central controllers and expansion units power suppl y unit s
4-25 system manual c79000-g8576-c199-07 the power supply unit is delivered with the settings shown in bold print in the following table. mark your chosen settings in the right-hand column and use this chart for the subsequent implementation. function selection jumper setting application/note (x) battery monitor switched on for rechargeable battery and battery mm - nn ma - na closed closed redundant backup switched on for battery and off for rechargeable battery mm - nn ma - na closed open if, for example, no redundancy is required in backup, i.e. the rechargeable battery is missing switched off mm - nn ma - na open irrelevant for example, monitoring is not needed for eu without backup reaction of battery monitoring following battery failure /bau signal active following return of line voltage mb - nb open /bau signal active following return of line voltage and during operation mb - nb closed the possibility of evaluating the battery monitoring during operation is dependent on the cpu in use after failure of more than one fan or inadequate air flow psu shutdown f-r closed no psu shutdown f-r open caution: to prevent overheating of modules, the psu must be shut down after 60 s at the latest (for example, by time relay) voltage monitor switched off ba-ex closed monitoring of load voltage input switched off switched on ba-ex open monitoring of load voltage input switched on relay alarm fault message initiated by fan f il / i hibi i b driven by fan monitor and output inhibit bb-aa closed gy failure/output inhibit active; can be signaled to control room, for example. driven only by fan monitor bb-aa open fault message initiated by fan failure; can be signaled to control room, for example. establishing the jumper settings central controllers and expansion units power suppl y unit s
4-26 system manual c79000-g8576-c199-07 function selection (x) application/note setting jumper mains buffering fx-va 6-22 closed closed a stored energy time of 5 to 10 ms is guaranteed in the event of a power failure. the stored energy time is dependent on the input voltage and the load. fx-va 6-22 closed open a stored energy time of 20 to 30 ms is guaranteed in the event of a power failure. the stored energy time is not dependent on the input voltage and the load. fx-va 6-22 open irrelevant a stored energy time of  20 ms is guaranteed in the event of a power failure. the stored energy time is dependent on the input voltage and the load. if your selection is the same as all the settings marked in bold print, you need not change the jumper settings. wiring of the power supply unit must be planned within the scope of wiring of the entire control system. the information required for the purpose and decision-making aids, for example, for local or central grounding, can be found in chapter 3: installation guidelines. three relay outputs allow you to install additional external signaling circuits for fault states, for example, to connect a cabinet lamp or horn. the following table contains the information required on the relay states: relay (normal operational state) (fault state/idle state) warning all fans are in order. one or more fans have failed. alarm adequate air flow, at least two fans are running. inadequate air flow or at least two fans have failed. batterywarn ing lithium battery and rechargeable battery are in order (u batt ext not connected). lithium battery or rechargeable battery has failed (no u batt ext ). establishing the wiring establishing the signaling circuits central controllers and expansion units power suppl y unit s
4-27 system manual c79000-g8576-c199-07 the following applies to input en (enable power supply):  input en monitors the voltage for < 3.6 v; it enables the output voltage at 3.2 v.  if two or more units are to be controlled jointly, connect input en of the psu in the central controller to the en inputs of the psus in the expansion unit. connect the auxiliary voltage u h , for example, to these inputs. in the event of failure of the psu in the central controller, all units will then be switched off with the appropriate jumper settings. not more than 7 en inputs may be connected to one u h output (front terminal). the following applies to selecting the cables for the terminals: terminals cabling max. permissible conductor cross-sections power supply ac line dc line phase l 1 neutral n protective cond. pe positive l + chassis 0 v m protective cond. pe 4 mm 2 solid or 2.5 mm 2 flexible 4 mm 2 solid or 2.5 mm 2 flexible 4 mm 2 solid or 2.5 mm 2 flexible 4 mm 2 solid or 2.5 mm 2 flexible 4 mm 2 solid or 2.5 mm 2 flexible 4 mm 2 solid or 2.5 mm 2 flexible load voltage input (voltage monitor, ext. 24 v dc) 24 v input (may be omitted if jumper ba-ex is closed) 4 mm 2 solid or 2.5 mm 2 flexible enable power supply set jumper from en-u h or apply  3.2 v voltage at en, with respect to output chassis ground 4 mm 2 solid or 2.5 mm 2 flexible relay terminals, also suitable to 230 v ac / 3 a 4 mm 2 solid or 2.5 mm 2 flexible monitor output for 24 v 4 mm 2 solid or 2.5 mm 2 flexible note a voltage of more than 50 v must not develop between the output voltages and the protective conductor potential. setting up the control input for the power supply establishing the cables central controllers and expansion units power suppl y unit s
4-28 system manual c79000-g8576-c199-07 you must remove the power supply unit if you:  change the jumper settings  send the power supply unit in for repair. ! caution power supply units may only be removed when power is switched off. if 230 v i/o modules are fitted, you must ensure before removing the power supply unit that the subrack is grounded when the psu is removed, or the 230 v supply for these modules is switched off. when the power supply unit is removed, the connection between backup battery and backplane bus remains; this ensures backup of the user program. proceed according to the following steps to remove the power supply unit: step action 1 switch the power switch off (standby on/off). 2 disconnect the power supply unit form the ac line voltage. 3 detach the connections of all leads from the front terminals. 4 important ! p before pulling out the psu, wait at least 8 minutes after switching off the power so that the electrolytic capacitors can discharge. 5 slacken the fixing screws on the left and right of the psu. 6 pull the psu out. there are grips to pull it out under the unlock fan openings. removing the power supply unit when to remove the psu how to remove the psu central controllers and expansion units power suppl y unit s
4-29 system manual c79000-g8576-c199-07 the jumper locations are given in the following figure: nb mb ma na nn mm f r bb aa ba ex bb aa ba ex fx va 22 6 to change the jumper settings, it is best to use pincers or a fine screwdriver. proceed as follows to change the jumper settings: if... then... you wish to open the jumper, press the flexible jumper wire down and pull it out. you wish to close the jumper, press the flexible jumper wire down and insert it. setting the jumpers locations of jumpers setting the jumpers central controllers and expansion units power suppl y unit s
4-30 system manual c79000-g8576-c199-07 ! caution for safety reasons, the power supply unit may only be operated in the housing provided for the purpose. the protective conductor must always be connected. after carrying out setting, installation and repair work, proceed according to the following steps to refit the power supply unit in the frame: step action 1 push the psu into the guide rails until it locks in place. you can use one hand to support the psu from below; this facilitates fitting in the guide rails. 2 secure the psu with the fixing screws on the left and right of the unit. ! caution since the fixing screws also provide the protective conductor connection to the subrack, they must be tightened before the power cable is connected. wiring of the psu is carried out within the scope of overall wiring for your controller, according to your requirements and the section entitled aestablishing the settings and cabling.o terminals with dangerous touch-voltages must be covered with caps. use only the original self-tapping screws provided when you fit the caps for the first time. fitting the power supply unit how to fit the psu wiring the power supply unit how to wire the psu central controllers and expansion units power suppl y unit s
4-31 system manual c79000-g8576-c199-07 whether or not you require a lithium battery depends on what type of backup you require for your system. the following table will help you to decide. if... then... you require long backup times and do not want to supply an external backup voltage, you need a lithium battery. you require redundant backup and do not want to supply an external backup voltage, you need a lithium battery. short backup times are sufficient, you do not need a lithium battery. you do not require redundant backup, you do not need a lithium battery. the lithium battery must be ordered separately (see ordering information). the backup battery (type c) contains lithium (more than 0.5 g) and is delivered separately from the power supply unit, because of special shipping regulations. depending on the manufacturer, the battery's plus pole may have a protective cover. you must remove this cover before you place the battery in the battery compartment. ! caution improper replacement of the battery can result in the danger of explosion. if should only be replaced by the same type or an equivalent one recommended by the manufacturer. used batteries should be disposed of according to the manufacturer's instructions. the backup battery must be fitted before the programmable controller is started up. without a backup voltage, the plc will remain in the stop state after system voltage is switched on. only use battery compartments marked -a1155-b21 (red label). fit the lithium battery in the following steps: step action 1 slide the battery compartment cover (a) downwards. 2 pull the battery compartment (b) out. 3 insert the lithium battery in the battery compartment. important: ensure correct polarity. 4 slide the battery compartment in. 5 close the cover. starting up with a lithium battery when do you require a lithium battery? notes relating to the lithium battery how to fit the lithium battery central controllers and expansion units power suppl y unit s
4-32 system manual c79000-g8576-c199-07 cover (a) battery compartment (b) * + ! warning risk of danger to persons and property, danger of giving off harmful substances. if handled incorrectly, a lithium battery can explode. if disposed of incorrectly, old lithium batteries can release harmful substances. you must therefore observe the following guidelines:  do not throw new or discharged batteries onto a fire and do not solder onto the body of the cell (max. temperature 100 5 c (212 5f)). do not recharge them. order your replacement battery from siemens only (for order number see ordering instructions). this ensures that you only use a short-circuit-protected type.  the lithium battery is subject to regulations for hazardous materials. you should observe these regulations when you ship the battery, for example, by using the original packaging. used batteries should be returned to the manufacturer or a recycling station if possible or disposed of as hazardous waste. the guidelines for transporting hazardous materials should be observed. if you want to start up one of the central controllers or expansion units without a battery, you can do either of the following:  you can connect only the rechargeable battery, or  you can supply an external backup voltage. apply a backup voltage of 4.5 v dc via the input sockets labelled aext.batt. dc 4.5 v.o the input sockets are situated on the front panel of the power supply. ensure that you have the correct polarity. starting up without a lithium battery supplying an external backup voltage central controllers and expansion units power suppl y unit s
4-33 system manual c79000-g8576-c199-07 the three fans are situated under the power supply unit. the rechargeable battery is fitted in the right-hand fan subassembly. proceed according to the following steps: step action result 1 place one hand under the right-hand fan; with the other hand, insert a screwdriver (din 5265, blade width 3.5-6.5 mm) into the right-hand unlock fan opening. when the screwdriver is pulled out, the snap hook is released. by pulling on the round hole on the underside of the fan subassembly it swings down and can be pulled out. 2 connect the red connecting cable to the battery. the battery is connected. 3 insert the fan subassembly in the housing with the tab situated at the rear, and swivel it up. the fan subassembly locks in place. the following figure shows how to release the fan lock: unlock fan unlock fan unlockfan unlockfan replace by trained personnel only! batt.3,6v/5ah siemens use battery holder c98100-a1155-b21 only! 1 2 3 4 5 67 89 10 removing the right-hand fan and connecting the rechargeable battery location of fans and rechargeable battery how to connect the rechargeable battery releasing the fan lock central controllers and expansion units power suppl y unit s
4-34 system manual c79000-g8576-c199-07 the filter subdrawer with fixing grid, two plug-in guide rails and the corresponding filter mats are available as an option (see the ordering instructions for the order numbers). to insert a filter, you must secure the filter subdrawer to the lower side of the power supply unit housing. proceed as follows: step action 1 install the guide rails in such a way that the round tabs fit into the corresponding openings on the lower side of the psu. 2 insert a filter mat in the filter subdrawer and secure it with the enclosed fixing grid. 3 position the filter subdrawer in the guide rails, push it back and swivel it up so that it locks in place. on the ac power supply units, the voltage selector switch is situated on the front plate and marked voltage selector. you can select a voltage of 120 v or 230 v. the factory setting is 230 v. set the voltage according to your requirements step action 1 disconnect the power supply unit from the line voltage. 2 use a screwdriver to remove the transparent cover. 3 set the voltage selector switch to your required voltage. 4 refit the transparent cover. fitting the filter subdrawer option where to fit the filter subdrawer how to fit the filter subdrawer setting the voltage selector switch how to set the voltage selector switch central controllers and expansion units power suppl y unit s
4-35 system manual c79000-g8576-c199-07 ! caution if you have set the voltage selector switch to 120 v, but the actual voltage value is 230 v, the power supply unit may be damaged when line voltage is switched on. when you have made all the settings, switch the power supply unit on as follows: step action result 1 switch the power supply unit on with the power switch. 2 switch the system voltage on. if the required basic load (see section 4.4.6, technical specifications) is in circuit, the power supply unit will start. the green leds a5v o.k.o a15v o.k.o a24v o.k.o light up. the fans run. after a maximum of 6 minutes, the rechargeable battery has been charged sufficiently for you to be able to start up the central controller or the expansion unit. the charge time for the rechargeable battery can be up to 46 hours, depending on how low the battery was. note that during this time, backup using the rechargeable battery is restricted. once the rechargeable battery is fully charged, the following load-dependent backup times apply: i backup ma 0.25 1 2 3 4 5 backup time in weeks 18.8 6.3 3.4 2.3 1.7 1.4 switching on the power supply unit for the first time how to switch on the power supply unit central controllers and expansion units power suppl y unit s
4-36 system manual c79000-g8576-c199-07 4.3.3 fault indications/fault diagnostics this section explains where and how faults are indicated, and how to interpret the leds. faults of the system power supply, load power supply, battery supply and fans are indicated by leds on the front plate of the power supply unit. when all monitoring circuits are switched on (jumper settings), the following indications can appear: led indication cause action avoltage lowo led lights up. the voltage at the voltage monitor is less than 14 v. amb lowo led lights up. the lithium battery has failed or the battery compartment is faulty. (precondition: no external battery voltage is present). replace backup battery or battery compartment arb lowo led lights up. the rechargeable battery has failed. replace rechargeable battery afan 1o led lights up. the speed of fan 1 has dropped or fan 1 has stopped. replace fan afan 2o led lights up. the speed of fan 2 has dropped or fan 2 has stopped. replace fan afan 3o led lights up. the speed of fan 3 has dropped or fan 3 has stopped. replace fan at least 2 afano leds light up as well as the aalarmo led. at least 2 fans have failed. replace fan all 3 afano leds flash and the aalarmo led lights up. the air flow is inadequate. replace filter mat the fan error is indicated approximately 6 s after the monitoring circuits are switched on or 6 s after a reset is performed. where are faults indicated? how are faults indicated and interpreted? central controllers and expansion units power suppl y unit s
4-37 system manual c79000-g8576-c199-07 other faults can be indicated by the green leds on the front plate going off. leds possible cause action green leds go off and the power lfil the enable jumper is out of place check the jumper. supply fails. latching off-switching by overvoltage at output switch the supply voltage off and on again. if this does not clear the fault, there is an internal fault. internal fault in the psu send in the psu for repair. base load too low increase the base load other faults central controllers and expansion units power suppl y unit s
4-38 system manual c79000-g8576-c199-07 the following table contains several examples. requirement : enable en present, jumper f - r closed causes led indication relay reaction fans air filter/ air flow fan1 to fan3 alarm fan warning fan alarm all fans in order in order all leds dark dark - 5 v, 15 v, 24 v present, fans 1 to 3 running one fan failed in order corresponding led lit dark active 5 v, 15 v, 24 v present, faulty fan switched off, the other two fans running at increased speed two fans failed in order corresponding leds lit lit active active power supply switches off all fans in order dirty/halved all leds flashing lit active power supply switches off requirement : enable en present, jumper f - r open causes led indication relay reaction fans air filter/ air flow fan1 to fan3 alarm fan warning fan alarm all fans in order in order all leds dark dark 5 v, 15 v, 24 v present, fans 1 to 3 running one fan failed in order corresponding led lit dark active 5 v, 15 v, 24 v present, faulty fan switched off, the other two fans running at increased speed two fans failed in order corresponding leds lit lit active active 5 v, 15 v, 24 v present, faulty fans switched off, one fan running at increased speed all fans in order dirty/halved all leds flashing lit active 5 v, 15 v, 24 v present, fans 1 to 3 running note : when the jumper abb - aao is closed the relay afan alarmo is also activated by the aoutput inhibito signal (basp via baspa). fans and fan monitoring central controllers and expansion units power suppl y unit s
4-39 system manual c79000-g8576-c199-07 the following table contains several examples. causes relay led indication rechargeable battery battery or external supply jumpers battery warning rb mb /bau in order in order ma-na closed mm-nn closed mb-nb open dark dark inactive faulty in order ma-na closed mm-nn closed mb-nb open active lit dark inactive in order faulty ma-na closed mm-nn closed mb-nb open active dark lit inactive faulty faulty ma-na offen mm-nn closed mb-nb open active lit lit active not monitored in order ma-na open mm-nn closed mb-nb open dark dark inactive not monitored faulty ma-na open mm-nn closed mb-nb open active dark lit active not monitored not monitored ma-na irrelevant mm-nn open mb-nb open dark dark inactive note: jumper mb - nb open: when line voltage returns the signal /bau (battery failure) is activated by a corresponding error. jumper mb - nb closed: when line voltage returns and during operation the signal /bau (battery failure) is activated by a corresponding error. rechargeable battery and battery monitoring central controllers and expansion units power suppl y unit s
4-40 system manual c79000-g8576-c199-07 4.3.4 maintenance and repairs the lithium battery should be replaced when a battery failure is indicated. the backup times of the lithium battery are given in the following table: i backup ma 0.25 1 2 3 4 5 new battery, backup time in weeks 81.5 27.4 14.5 9.9 7.5 6.0 battery 3 years old, backup time in weeks 64.2 21.6 11.5 7.8 5.9 4.8 if a fan fails, replace it as quickly as possible. the behavior of the power supply in the event of fan failure is described in section 4.3.5. the rechargeable battery should be replaced at regular intervals (service life of 6 years at 40 o c (104 o f) ambient temperature). with a failed power supply and failed battery, the backup times of the rechargeable battery are as follows: i backup ma 0.25 1 2 3 4 5 backup time in weeks 18.8 6.3 3.4 2.3 1.7 1.4 the replacement intervals for the filter mat (with the air filter option) depend on the ambient conditions under which the power supply unit is in operation. lithium battery fans rechargeable battery filter mat central controllers and expansion units power suppl y unit s
4-41 system manual c79000-g8576-c199-07 the lithium battery can be replaced without memory loss if the psu is switched on, the rechargeable battery is in order or you apply an external (4.5 v) voltage to the aext.batt.o terminals. replace the lithium battery in the following steps: step action 1 slide the battery compartment cover down. 2 pull the battery compartment out. 3 remove the old lithium battery from the battery compartment by inserting a screwdriver through a hole in the compartment base to push the battery upwards. 4 insert the new lithium battery in the battery compartment important: ensure correct polarity. 5 slide the battery compartment in. 6 close the cover. 7 press the reset button. result (only with psu on): amb lowo led goes off. contacts 14 and 15 of the battery warning relay are bridged. the three fans are situated at the bottom of the power supply unit and can be individually replaced during operation. if you operate your power supply with a filter, you must first release the filter subdrawer and pull it out before you can replace a fan (see section entitled areplacing the filter mato). replacing the lithium battery how to replace the lithium battery replacing a fan location of the fans before replacement central controllers and expansion units power suppl y unit s
4-42 system manual c79000-g8576-c199-07 the following steps are necessary to replace a fan: step action result 1 place one hand under the fan you wish to replace, and use the other hand to insert a screwdriver (din 5265, blade width 3.5-6.5 mm) into the unlock fan opening. when the screwdriver is pulled out, the snap hook is released. by pulling on the round hole on the underside of the fan subassembly it swings down and can be pulled out. 2 if this is not the right-hand fan subassembly, go directly to step 3 after removing the old fan subassembly. if this is the right-hand fan subassembly, proceed as follows: step action 2a unscrew the rechargeable battery from below. 2b disconnect the connecting cable. 2c insert the rechargeable battery in the new fan subassembly (see section entitled areplacing the rechargeable batteryo) and reconnect the connecting cable. important: ensure correct polarity. 3 insert the new fan subassembly with the tab at the rear into the housing, and swivel it up. the fan subassembly locks in place. how to replace a fan central controllers and expansion units power suppl y unit s
4-43 system manual c79000-g8576-c199-07 the following figure shows how to release the fan lock: unlock fan unlock fan unlockfan unlockfan replace by trained personnel only! batt.3,6v/5ah siemens use battery holder c98100-a1155-b21 only! 1 2 3 4 5 67 89 10 after replacement, press the reset button, the monitor will become active 6 secs after the reset button is pressed. if... then... the relevant afano led goes off, the fan is correctly installed. the relevant afano led does not go off, the fan is incorrectly installed. make a step-by-step check to ensure correct replacement. the relevant afano led goes off but the awarningo relay does not pick up, another fan has failed and another afano led lights up. replace the second fan also. releasing the fan lock after replacement central controllers and expansion units power suppl y unit s
4-44 system manual c79000-g8576-c199-07 the rechargeable battery is situated in the right-hand fan subassembly. ! caution do not place the rechargeable battery in contact with fire or heat and do not short-circuit it. the rechargeable battery must not be destroyed or disassembled! nickel-cadmium batteries contain an alkali electrolyte which can harm the skin and damage clothing. if your skin or your eyes make contact with the electrolyte, rinse immediately with clean water and consult a doctor. if you operate your power supply with a filter, you must first release the filter subdrawer and pull it out before dismantling the right-hand fan and replacing the rechargeable battery (see section entitled areplacing the filter mato). the rechargeable battery can be replaced during operation. proceed as follows: step action 1 insert a screwdriver (din 5265, blade width 3.5-6.5 mm) into the right-hand unlock fan opening. 2 swing the right-hand fan subassembly out (by placing your finger in the round opening on the underside at the front and pulling downwards). result: afan 3o led indicates failure of the right-hand fan and the other two fans operate at increased speed. 3 slacken the screws on the bottom of the fan subassembly and pull out the rechargeable battery. 4 disconnect the connecting cable of the rechargeable battery. 5 connect the cable to the new rechargeable battery. important: ensure correct polarity (red terminal on plus, black terminal on minus, see figure areplacing the rechargeable battery in the fan subassemblyo). 6 insert the new rechargeable battery pack in the left-front part of the fan subassembly (plus pole to the right). ensure that the black connecting cable is lying on the floor of the battery compartment when you insert the battery. secure it with the screws from below. 7 insert the fan subassembly with the tab at the rear into the housing and swivel it up until it locks in place. 8 press the reset button. with a fully discharged battery, the message can only be acknowledged after at least 6 minutes. replacing the rechargeable battery location of the rechargeable battery before replacement how to replace the rechargeable battery central controllers and expansion units power suppl y unit s
4-45 system manual c79000-g8576-c199-07 the recharging time for the battery may be up to 46 hours, depending on its state of charge. please note that backup via the battery is only possible within limits during this time. if the rechargeable battery does not work after replacement, there may be the following faults: if... then... arb lowo led does not go off after 6 minutes, the rechargeable battery is incorrectly connected or faulty or the charging circuit in the psu is faulty. arb lowo led goes off but the relay does not pick up, the battery has failed and the yellow amb lowo led lights up or the battery compartment is faulty. red black hole fan subassembly rechargeable battery after replacement replacing the rechargeable battery in the fan subassembly central controllers and expansion units power suppl y unit s
4-46 system manual c79000-g8576-c199-07 if the filter mat is clogged and the power supply unit no longer receives sufficient air, the aalarmo led lights up, leds for afan 1,o afan 2o and afan 3o flash and the aalarmo relay picks up. the fault can be cleared by replacing the filter mat (see ordering information for the order number). correct the fault in the following steps: step action 1 release the filter subdrawer. 2 swivel the filter subdrawer downwards and pull it forwards and out. 3 remove the old filter mat. 4 insert a new filter mat in the filter subdrawer. 5 place the distance grid on the new filter mat. 6 insert the filter subdrawer in the guide rails, slide it back and swivel it up so that it locks in place. 7 press the reset button. result: fault leds for aalarm,o afan 1,o afan 2o and afan 3o go off. contacts 11 and 12 are closed in the aalarmo relay. replacing the filter mat inadequate air flow how to replace the filter mat central controllers and expansion units power suppl y unit s
4-47 system manual c79000-g8576-c199-07 if it should be necessary to replace the power supply unit in a system during commissioning or during operation, we recommend you proceed as follows: requirement: redundant backup, aspare power supplyo without rechargeable battery (standard spare part). the lithium battery in the rack is in full working order. step action 1 disconnect the faulty power supply from the system voltage and remove it. 2 set the jumpers on the spare power supply according to your needs. 3 push the spare power supply into the rack and screw it in place. 4 remove the right-hand fan subassembly from the defective power supply. 5 remove the rechargeable battery from the fan subassembly. 6 replace the right-hand fan subassembly in the defective power supply. 7 remove the right-hand fan subassembly from the spare power supply. 8 connect up the spare power supply. 9 switch on the system voltage and the power supply in any order. reaction: the system runs up both fans run at an increased speed the leds afan 3o and arb lowo light up. 10 insert the rechargeable battery in the fan subassembly and connect it up. 11 reinsert the right-hand fan subassembly. 12 after the system has run up, press the reset switch on the spare power supply. reaction: the led afan 3o goes out the fans run at their normal speed again the led arb lowo shows the charge state of the rechargeable battery. replacing a power supply unit central controllers and expansion units power suppl y unit s
4-48 system manual c79000-g8576-c199-07 requirement : redundant backup, aspare power supplyo with rechargeable battery. the lithium battery in the rack is in full working order. step action 1 disconnect the faulty power supply from the system voltage and remove it. 2 set the jumpers on the spare power supply according to your needs. 3 push the spare power supply into the rack and screw it in place. 4 remove the right-hand fan subassembly from the spare power supply. 5 connect up the replacement power supply. 6 switch on the system voltage and the power supply in any order. reaction: the system runs up both fans run at an increased speed the leds afan 3o and arb lowo light up. 7 reinsert the right-hand fan subassembly. 8 after the system has run up, press the reset switch on the spare power supply. reaction: the led afan 3o goes out the fans run at their normal speed again the led arb lowo shows the battery charge state. requirement: no backup step action 1 disconnect the faulty power supply from the system voltage and remove it. 2 set the jumpers on the spare power supply according to your needs. 3 push the spare power supply into the rack and screw it in place. 4 connect up the spare power supply. 5 switch on the system voltage and the power supply in any order. reaction: the system runs up. central controllers and expansion units power suppl y unit s
4-49 system manual c79000-g8576-c199-07 4.3.5 description of internal sequences in the power supply unit given in this section is background information on internal sequences in the power supply unit. the behavior of the power supply unit after a system supply failure is governed by the duration of the failure: if the system supply failure... then... is shorter than the stored energy time for power failure the psu output voltages are within tolerance ranges; no indication appears on the front plate and no signal is sent to the s5 bus. is longer than the stored energy time for power failure a data save routine is initiated on the cpu/cpus and an output inhibit is issued. to ensure data backup, your cc and eu 185 are provided with a lithium battery, and the power supply unit with a rechargeable battery. in the event of system supply failure or switch-off, data backup is provided by the lithium battery and, in the event of battery failure, by the rechargeable battery which is permanently recharged to remain constantly operative. after replacement of a defective lithium battery, the new one resumes data backup and you must acknowledge the fault led on the front panel. as the rechargeable battery is withdrawn during the replacement of a power supply unit, data backup is temporarily performed by the lithium battery. behavior upon failure of the system supply when the system supply fails redundant data backup central controllers and expansion units power suppl y unit s
4-50 system manual c79000-g8576-c199-07 if a fan fails (its speed decreases) a fault is indicated, i.e. the red led assigned to the fan lights up: afan 1o led = left fan failed afan 2o led = middle fan failed afan 3o led = right fan failed if a fan fails, the following takes place: stage description 1 a fan fails. result: the red led assigned to the fan lights up. 2 contacts 9 and 10 in the awarningo relay are closed. 3 the faulty fan is switched off. 4 the other two fans operate at increased voltage and an audibly higher speed. if another fan fails, the following takes place: stage description 5 another fan fails. result: the red led assigned to the fan lights up. 6 contacts 12 and 13 in the aalarmo relay are closed. result: aalarmo led lights up. two afano-red leds light up. 7 a data save routine is started and, with the appropriate jumper setting, an output inhibit is issued. 8 the power supply switches off, with the appropriate jumper setting. when the fault has been cleared (faulty fan replaced, filter mat replaced), you can reset the fault messages by pressing the reset button. ! caution you can suppress the shutdown of the power supply by opening jumper f-r. in this case, you must ensure that the power supply is switched off after 60 secs at the latest. this can be achieved with a time relay, for example. this prevents modules from overheating and being damaged. behavior upon failure of fans failure indication if a fan fails if another fan fails resetting the fault message central controllers and expansion units power suppl y unit s
4-51 system manual c79000-g8576-c199-07 4.3.6 technical specifications of the power supply units important for the usa and canada the following approval has been obtained: ul-recognition-mark (for usa) underwriters laboratories (ul) to standard ul 508, report e 143289 cul-recognition-mark (for canada) to canadian national standard c 22.2, no. 142, report e 143289 6es5 955-3lc42 6es5 955-3lf42 safety specifications the power supply units comply with safety specifications vde 0805 / en 60950 / iec 60950 / vde 0160 and vde 0106 part 101. shock protection only insured in the installed state data for emc in the installed state see technical specifications of the s5-135u/155u cc safe isolation is ensured. input rated input voltage 120 v (93-132 v) ac 230 v (187-264 v) ac 120 v (93-132 v) ac 230 v (187-264 v) ac rated input frequency 50/60 hz (47-63 hz) 50/60 hz (47-63 hz) input current i i/p at rated load and rated v i/p = 120v = 230v 2.5 a rms 1.5 a rms 4.5 a rms 2.6 a rms peak inrush current i i/p max 26 a for 2 s, otherwise < 5 a (repetition rate 100 secs) 25 a for 2 ms (repetition rate 100 secs) i  t value of inrush current 4 a  s 5.2 a  s efficiency at rated load (with fans) and v i/p  230/120 v ac > 0.63 > 0.68 max. heat dissipation at rated load at v o/p1 , v o/p2 , v o/p3 (with fans) 80 w 147 w efficiency at rated load (without fans) and v i/p  230/120 v ac 0.70 0.71 max. heat dissipation (without fans) 53 w 123 w stored energy time during power failure at rated load and v i/p  187/93 v ac (adjustable) >20 ms 20 ms 5 ms >20 ms 20 ms 5 ms input fuse wickmann g 19343-t4a/250v, 500 a  s wickmann g 19340-8a/250v, 200 a  s external battery supply 4.5 v 4.5 v central controllers and expansion units power suppl y unit s
4-52 system manual c79000-g8576-c199-07 6es5 955-3lf42 6es5 955-3lc42 output 1 rated output voltage vo/pn1 5.1 v dc  1.2% 5.1 v dc  1.2% rated output current io/pn1 18 a 40 a basic load 0.5 a 1.6 a (typical) 3.1 a (worst case) ripple  1% of v o/p1  1% of v o/p1 spikes  4% of v o/p1  4% of v o/p1 static voltage tolerances at 95% load variation at 15% variation of v i/p at temperature variation / 1k  0.005% of v o/p1  0.0005% of v o/p1  0.02% of v o/p1  0.08% of v o/p1  0.0005% of v o/p1  0.02% of v o/p1 dynamic voltage tolerances at load surge 50% to 100% i i/on overshoot settling time  3% of v o/p1  5 ms  3% of v o/p1  5 ms maximum permitted capacity 100 mf 750 mf protection and monitoring voltage monitor monitors voltage for < 14 v and > 16 v monitors voltage for < 14 v and > 16 v overvoltage shutdown v o/p1 6v  5% 6v  5% undervoltage signal v o/p1 4.75 v + 3% 4.75 v + 3% current limiting for overload 1.0 to 1.2 i o/pn1 1.0 to 1.2 i o/pn1 test sockets for i o/p1 on front plate (3 v  18 a) linearity range: 0.5 v/2.8 a to 3 v/18 a on front plate (3 v  40 a) linearity range: 0.5 v/6.6 a to 3 v/40 a signaling section signals for simatic s5, relays afan warning, fan alarm, warningo 250v/3a signals for simatic s5, relays afan warning, fan alarm, warningo 250v/3a green led: a5v o.k.o for v o/p1 led lights up if 4.75 v < v o/p1 led lights up if 4.75 v < v o/p1 output 2 rated output voltage v o/pn2 dc 24 v (+ 25%, -12.5%) dc 24 v (+ 25%, -12.5%) rated output current i o/pn2 1 a 2.8 a total current x2 and front terminals 1 a max. 2.8 a max. ripple  1% of v o/p2  1% of v o/p2 spikes  2% of v o/p2  2% of v o/p2 protection and monitoring current limiting for overload 1 to 1.3 i o/pn2 1 to 1.3 i o/pn2 green led a24v o.k.o for v o/p2 led lights up if v o/p2 > 19.9 v to 21.1 v led lights up if v o/p2 > 19.9 v to 21.1 v maximum permitted capacity 0.2 mf 0.8 mf central controllers and expansion units power suppl y unit s
4-53 system manual c79000-g8576-c199-07 6es5 955-3lf42 6es5 955-3lc42 output 3 rated output voltage v o/pn3 15 v dc (  5%) 15 v dc (  5%) rated output current i o/pn3 0.5 a 2 a ripple  1% of v o/p3  1% of v o/p3 spikes  3% of v o/p2  3% of v o/p2 protection and monitoring overvoltage shutdown v o/p3 17 v  5% 17 v  5% current limiting for overload 1 to 1.5 i o/pn3 during startup 4  i an3 for 40 ms 1 to 1.5 i o/pn3 green led a15v o.k.o for v o/p3 led lights up if 14.2 to 14.7 v < u a3 < 16.1 to 17.9 v led lights up if 14.2 to 14.7 v < u a3 < 16.1 to 17.9 v maximum permitted capacity 10 mf 10 mf backup battery type capacity no-load voltage voltage under load storage life service life in operation (see section 4.3.4 for backup times) lithium thionyl chloride 5 ah 3.6 v 3.4 v approx. 10 years 3 years max. rechargeable battery type capacity rated voltage service life in operation (see section 4.3.4 for backup times) protection against exhaustive discharge nickel cadmium 1.2 ah 3.6 v 6 years at 40 5 c (104 5 f) yes service life of fans approx. 50.000 h at 40 5 c approx. 50.000 h at 40 5 c weight approx. 5.8 kg approx. 5.8 kg noise emission 58 dba 58 dba environmental data see technical specifications of the s5-135u/155u cc central controllers and expansion units power suppl y unit s
4-54 system manual c79000-g8576-c199-07 6es5 955-3nc42 6es5 955-3nf42 safety specifications the power supply units comply with safety specifications vde 0805 / en 60950 / iec 950 / vde 0160 and vde 0106 part 101. shock protection only ensured in the installed state. data for emc in the installed state see technical specifications of the s5-135u/155u cc safe electrical separation is ensured. 1) input rated input voltage (including ripple) 24 v dc (19.2 - 33 v) 24 v dc (19.2 - 33 v) input current i i/p at rated load and rated v i/p = 24 v 9.5 a 20 a polarity reversal protection yes yes peak inrush current i i/pmax 100 a for 1  s 200 a for 1 ms i  t value of inrush current 2.7 a  s 18 a  s efficiency at rated load (with fans) and v i/p  24v 0.60 0.67 max. heat dissipation at rated load (with fans) at v o/p1 , v o/p2 , v o/p3 90 w 153 w efficiency at rated load (without fans) and v i/p  230/120 v ac 0.65 0.70 max. heat dissipation (without fans) 66 w 129 w stored energy time during power failure at rated load and v i/p  19.2 v dc (adjustable) >20 ms 20 ms 5 ms >20 ms 20 ms 5 ms input fuse littlefuse 322020, 220 a  s littlefuse 322030, 620 a  s extenal battery supply 4.5 v 4.5 v output 1 rated output voltage v o/pn1 5.1 v dc  1.2% 5.1 v dc  1.2% rated output current i o/pn 18 a 40 a basic load 0.5 a 1.6 a (typical) 3.1 a (worst case) ripple  1% of v o/p1  1% of v o/p1 spikes  4% of v o/p1  4% of v o/p1 static voltage tolerances at 95% load variation at 15% variation of v i/p at temperature variation / 1k  0.08% of v o/p1  0.0005% of v o/p1  0.02% of v o/p1  0.08% of v o/p1  0.0005% of v o/p1  0.02% of v o/p1 dynamic voltage tolerances at load surge from 50% to 100% i o/pn overshoot settling time*  3% of v o/p1  5 ms  3% of v o/p1  5 ms 1) these power supply units have a separation between the input circuit (24 vdc) and the secondary circuit which fulfills the requirements for 230 vac. central controllers and expansion units power suppl y unit s
4-55 system manual c79000-g8576-c199-07 6es5 955-3nf42 6es5 955-3nc42 protection and monitoring voltage monitor monitors voltage for <14 v and >16 v monitors voltage for <14 v and >16 v overvoltage shutdown v o/p1 6 v  5% 6 v  5% undervoltage signal v o/p1 4.75 v + 3% 4.75 v + 3% current limiting for overload 1.0 to 1.2 i o/pn1 1.0 to 1.2 i o/pn1 test sockets for io/p 1 on front plate (3 v  18 a) linearity range 0.5 v/2.8 a to 3 v/18 a (3 v  40 a) linearity range 0.5 v/6.6 a to 3 v/40 a signaling section signals for simatic s5, relays afan warning, fan alarm, warningo 250 v/3 a signals for simatic s5, relays afan warning, fan alarm, warningo 250 v/3 a green led: a5v o.k.o for v o/p1 led lights up if 4.75 v < v o/p1 led lights up if 4.75 v < v o/p1 output 2 rated output voltage v o/pn2 dc 24 v (+ 25%, -12.5%) dc 24 v (+ 25%, -12.5%) rated output current i o/pn2 1 a 2.8 a total current x2 and front terminals 1 a max. 2.8 a max. ripple  1% of v o/p2  1% of v o/p2 spikes  2% of v o/p2  2% of v o/p2 protection and monitoring current limiting for overload 1 to 1.3 i o/pn2 1 to 1.3 i o/pn2 green led: a24v o.k.o for v o/p2 led lights up if v o/p2 > 19.9 v to 21.1 v led lights up if v o/p2 > 19.9 v to 21.1 v maximum permitted capacity 0.2 mf 0.8 mf output 3 rated output voltage v o/pn3 dc 15 v (  5%) dc 15 v (  5%) rated output current i o/pn3 0.5 a 2 a ripple  1% of v o/p3  1% of v o/p3 spikes  3% of v o/p2  3% of v o/p2 maximum permitted capacity 100 mf 750 mf protection and monitoring overvoltage shutdown v o/p1 17 v  5% 17 v  5% current limiting for overload 1 to 1.5 i an3 during startup 4  i an3 for 40 ms 1 to 1.5 i an3 green led: a15v o.k.o for v o/p3 led lights up if 14.2 to 14.7 v < v o/p3 < 16.1 to 17.9 v led lights up if 14.2 to 14.7 v < v o/p3 < 16.1 to 17.9 v maximum permitted capacity 10 mf 10 mf central controllers and expansion units power suppl y unit s
4-56 system manual c79000-g8576-c199-07 6es5 955-3nf42 6es5 955-3nc42 backup battery type capacity no-load voltage voltage under load storage life service life in operation (see section 4.3.4 for backup times) lithium thionyl chloride 5 ah 3.6 v 3.4 v approx. 10 years 3 years max. rechargeable battery type capacity rated voltage service life in operation (see section 4.3.4 for backup times) protection against exhaustive discharge nickel cadmium 1.2 ah 3.6 v 6 years at 40 5 c (104 5 f) yes service life of fans approx. 50.000 h at 40 5 c approx. 50.000 h at 40 5 c weight approx. 5.8 kg approx. 5.8 kg noise emission 58 dba 58 dba environmental data see technical specifications of the s5-135u/155u cc central controllers and expansion units power suppl y unit s
4-57 system manual c79000-g8576-c199-07 4.4 6es5 955-3na12 power supply unit your 135u central controller (6es5 135-3ua41) contains the following power supply unit (psu): type of psu designation input voltage output voltage 6es5 955-3na12 (primary/secondary, non-floating) 24 v dc 5 v/10 a dc permissible range 0 to 10 a 24 v/0.8 a dc permissible range 0 to 0.8 a 4.4.1 technical description the power supply unit offers the following functions:  system power supply all system voltages needed to operate the cc are supplied. the 15 v supply needed to operate the sinec h1 system can be incorporated in the power supply unit by fitting an auxiliary submodule.  data backup a lithium battery ensures data backup when power is switched off or fails.  heat dissipation the power dissipation is removed by fans. central controllers and expansion units power suppl y unit s
4-58 system manual c79000-g8576-c199-07 the following indicators and controls are arranged on the front plate: 12345678910 dc line monitor output 24v dc + - l+ m disconnect before removing power supply! siemens caution relay max. 250v ac3/a fan fault enable power supply battery batt. reset low internal 5v/15v/24v dc batt. 3,4v5ah replace by trained personnel only id label element purpose 1 fan fault red led the led lights up to indicate a fan fault. the psu then switches off (jumper f-r closed). if, for technical reasons, you cannot immediately switch off the plc, you must open jumper f-r. however, switch off the plc after 60 s at the latest (overheating of modules). 2 batt. low yellow led the led lights up if the battery voltage has dropped below 2.7 v; the data stored in the ram may be lost after apower off/on.o 3 reset button if the plc is in the apower offo state, the battery must be replaced after apower ono when the abatt. lowo led is lit. you must press the reset button after changing the battery. 4 power supply o.k. green led the led lights up when the 5 v output voltage is present. 5 test 5 v test socket to measure output voltage v o/p1 (standard setting: 5.1 v dc  0.5%) 6 3 v = 10 a test socket to measure output i o/p1 (3 v = max. output current of the psu) linearity range 0.5 v/1.6 a to 3 v/40 a 7 power supply o.k. (bus) green led the led lights up to indicate presence of the 15 v output voltage (if the 15 v auxiliary submodule is fitted) and 24 v output voltage 8 dc 15v/24v (bus) test sockets a) to measure output voltage v o/p2 (24 v dc +25 %/-24 %) b) to measure output voltage v o/p3 (15 v dc  5 %, provided that 15 v aux. submodule is fitted) 9 power supply o.k. (terminal) led the green led lights up to indicate presence of the output voltage at the adc 24 vo terminal for the enable supply. 10 batt. 3.4v/5ah battery drawer the backup battery is arranged so that it can be replaced during operation and the psu can be replaced during battery backup without the backup voltage being interrupted. leds and controls central controllers and expansion units power suppl y unit s
4-59 system manual c79000-g8576-c199-07 12 2 2 2 3 4 56 7 dc line monitor output 24v dc + - l+m disconnect before removing power supply! siemens caution relay max. 250v ac/9a fan fault enable power supply battery internal 5v/15v/24 dc batt. 3,4v/5ah replace by trained personnel only id label element purpose 1 protective conductor terminal for psu module and housing. 2 strain reliefs for connecting cables, with metal contact surface for cable shields. 3 dc line screw terminals system connection, 24 v input voltage 4 monitor output relay output standstill of one or both fans is signaled via led and relay contact, and results in shutdown of output voltages (can be shut down via jumper f-r of the psu; then only relay signal and led indication). 5 enable power supply input/ output no voltage at the en input results in shutdown of the psu. not more than 7 en inputs may be driven with one u h output (front terminal). 6 dc 24 v; 0.4 a output this output can be used to power the enable inputs of the u periphery. 7 ext.batt. 3.4 v sockets sockets for external 3.4 v backup voltage. ! caution observe the appropriate vde specifications, especially vde 0100. the terminals at the front are suitable for a conductor cross-section of up to 4 mm 2 , solid, or 2.5 mm 2 , flexible. ensure adequate strain relief of the connections. you can add a 15 v auxiliary submodule to the 6es5 955-3na12 power supply unit (for example, if you wish to use sinec h1). the auxiliary submodule produces a stabilized 15 v output voltage from the 24 v output voltage. the auxiliary submodule is short-circuit protected. the output voltage is monitored. if the voltage is too low, the green a15/24 v o.k.o led on the front plate goes off. if the voltage is too high, the output is short-circuited by a thyristor. terminals 15 v auxiliary submodule central controllers and expansion units power suppl y unit s
4-60 system manual c79000-g8576-c199-07 4.4.2 setting the power supply unit the figure shows the jumper settings when the unit is delivered. connector x1 connector x2 rr front plate ll mm nn r f the jumper settings in bold print indicate the status when the unit is delivered. function jumpers battery monitor (bau ) on battery monitor (bau ) off nn-mm closed nn-mm open psu shutdown after fan fault no psu shutdown after fan fault (only led indication, relay signal) f-r closed f-r open battery fault will be indicated by fault state of the signaling relay (contacts 2-3 closed). battery undervoltage (< 2.7v) results in battery fault signal (jumper mm-nn). apart from abatt. lowo led and output of signal bau, the signaling relay can be activated as of version 6 of the psu battery fault will not be indicated by fault state of the signaling relay rr-ll closed rr-ll open locations of jumpers functions of the jumpers central controllers and expansion units power suppl y unit s
4-61 system manual c79000-g8576-c199-07 you can set jumper f-r on the power supply units to choose whether or not the air flow monitor should switch off the internal supply voltage v o/p (5 v) when a fan fails.  jumper f-r closed: v o/p shutdown (signaled by contact)  jumper f-r open: no v o/p shutdown (signaled by contact) if one or both fans are at standstill, the signaling relay drops out (monitor output). the afan faulto led lights up simultaneously.  relay contacts 2-1 closed: fan running  relay contacts 2-3 closed: fan failure relay contacts 2-3 closed; this is also the normally closed contact during power off (failsafe). ! caution if an immediate shutdown is not possible, jumper f-r must be opened. in this case you must ensure that the power supply is switched off after 60 s at the latest. this can be achieved with a time relay, for example. it avoids overheating and destruction of modules. setting the fan monitor central controllers and expansion units power suppl y unit s
4-62 system manual c79000-g8576-c199-07 as of version 6 of psu 6es5 955-3na12, you can set jumper rr-ll to choose whether the signaling relay (monitor output) should switch in the event of battery failure as well as fan failure:  jumper rr-ll open (state when delivered): relay will signal only a fan failure  jumper rr-ll closed: relay will signal a fan and battery failure. if the backup voltage fails or a fan is at standstill, or in both cases, the signaling relay will drop out (monitor output). the abatt. lowo led will also light up.  relay contacts 2-1 closed: battery backup voltage in order and fan running  relay contacts 2-3 closed: backup voltage under 2.7 v or fan failure note the signaling relay in the power supply unit will drop out in the event of a fan fault or backup battery fault. the user's circuitry for the signaling relay must therefore be suitable for both types of fault. if the signaling relay drops out because of a backup battery fault and the programmable controller is therefore switched off, the program in the main memory may be lost. loss of program can be avoided if an external backup voltage (3.4 v) is present at the sockets on the front plate of the power supply unit during shutdown of the programmable controller. setting the backup battery monitor central controllers and expansion units power suppl y unit s
4-63 system manual c79000-g8576-c199-07 4.4.3 installation to install the power supply unit, push it into the rack. press it in firmly until the front plate is at the rack. the spring pressure of the contact elements must be overcome. then tighten the two screws to the left and right of the front plate in the rack. the protective conductor jumper on the left must be permanently connected to the front plate terminal and the central rack. ! caution power supply units may only be removed when no power is applied. when the power supply unit is pulled out, the connection between backup battery and backplane bus is retained; the backup supply for the modules is thus ensured. the auxiliary submodule (see ordering information for order number) may only be inserted when the power is off. remove the power supply unit, fit the 15 v auxiliary submodule at the location shown in the following figure. connector x1 connector x2 bb rr aa ll front plate trans- former space for auxiliary submodule installing the 15 v auxiliary submodule central controllers and expansion units power suppl y unit s
4-64 system manual c79000-g8576-c199-07 4.4.4 operation before placing the power supply unit in operation, please comply with the following.  this power supply unit does not have potential isolation between its primary and secondary circuits.  no voltage of more than 50 v may develop between the power supply outputs and the protective conductor of the power supply unit.  the protective conductor must always be connected, as must the jumper between cc rack and front plate of the power supply unit.  in the event of overvoltage of the internal dc supply voltages v o/p1 = +5 v and v o/p3 = +15 v, the power supply unit is switched off retentively. there is a voltage of  0.5 v at v o/p1 and v o/p3 in the off state (see section 4.4.6, technical specifications, for overvoltage shutdown). the storage flip-flop is reset by switching the external supply voltage off and on again, and the power supply unit is again operational if the overvoltage was not the result of an internal fault.  you can insert an air filter with filter holder in the bottom of the housing of the power supply unit.  observe the voltage level of 3.4 v and correct polarity when applying an external backup voltage.  before startup, a lithium backup battery must be fitted or an external backup battery with a voltage level of 3.4 v dc must be connected. without a backup battery, the programmable controller will remain in the stop state when system voltage has been switched on. the backup battery must be fitted for startup. press the reset button, then perform an overall reset.  the jumper from terminals u h to en will enable the power supply. you can lock out the plc in the event of a fault by means of suitable circuitry between the monitoring outputs and the en inputs. general notes on the power supply unit central controllers and expansion units power suppl y unit s
4-65 system manual c79000-g8576-c199-07 power supply faults are indicated via relay contacts and leds. the following table shows when the relay contacts are open or closed: power supply relay contacts 1-2 relay contacts 2-3 switched off open closed in normal operation closed open during fault open closed the leds indicate the following faults: led cause action afan faulto led lights up. a fan fault has occurred. replace fan abatt. lowo led lights up. the battery voltage has dropped below 2.7 v. replace backup battery fault indications/ diagnostics central controllers and expansion units power suppl y unit s
4-66 system manual c79000-g8576-c199-07 4.4.5 maintenance ! caution incorrect replacement of the battery can result in the danger of explosion. it should only be replaced by the same type or an equivalent type recommended by the manufacturer. used batteries should be disposed of according to the manufacturer's instructions. you can replace the backup battery without loss of data if the power supply unit is switched on, or if you apply an external voltage (3.4 v) at the aext. batt.o sockets. the backup battery must be replaced every 3 years at the latest, irrespective of memory configuration and backup operation. replace the battery as follows: step action 1 pull the cover downwards. 2 pull the battery submodule forwards and out, and remove it. 3 replace the battery. 4 ensure correct polarity. 5 once the new battery is fitted and system voltage is on, press the reset button on the power supply unit. cover battery submodule sockets for external backup voltage * + only use battery submodules with the order number 6xg3 400-2ck00. replacing the lithium battery battery submodule central controllers and expansion units power suppl y unit s
4-67 system manual c79000-g8576-c199-07 ! caution ensure correct polarity when inserting the battery or applying backup voltage. ! warning risk of danger to persons and property, danger of giving off harmful substances. if handled incorrectly, a lithium battery can explode. if disposed of incorrectly, old lithium batteries can release harmful substances. you must therefore observe the following guidelines:  do not throw new or discharged batteries onto a fire and do not solder onto the body of the cell (max. temperature 100 5 c (212 5 f)). do not recharge them. order your replacement battery from siemens only (for order number see ordering instructions). this ensures that you only use a short-circuit-protected type .  the lithium battery is subject to regulations for hazardous materials. you should observe these regulations when you ship the battery, for example, by using the original packaging. used batteries should be returned to the manufacturer or a recycling station if possible or disposed of as hazardous waste. the guidelines for transporting hazardous materials should be observed. the expected service life of the fans (see technical specifications) depends on their operating time, ambient temperature and ambient conditions. in the event of fan failure during operation, subsequent damage to modules, for example, is avoided by the activated fan monitor (jumper f-r closed); the power supply unit is switched off. in individual cases, a preventive replacement of fans at suitable intervals may be advisable. proceed as follows to replace the fans: step action 1 disconnect power from the power supply. 2 remove the power supply. 3 slacken the fixing screws of the fans. 4 pull off the plug-in contacts of the fan supply. 5 connect the plug-in contacts of the new fans. 6 tighten the fixing screws of the fans. 7 refit the power supply. 8 switch the power supply on. the order numbers for the backup battery and fan unit can be found in the ordering information. replacing the fans central controllers and expansion units power suppl y unit s
4-68 system manual c79000-g8576-c199-07 4.4.6 technical specifications important for the usa and canada the following approvals habe been obtained:  ul-recognition-mark underwriters laboratories (ul) to standard ul 508, report e 116536  csa-certification-mark canadian standard association (csa) to standard c 22.2 no. 142, report lr 63534 safety specifications the power supply unit complies with safety specifications vde 0805 / en 60950 / iec 60950 / vde 0160 and vde 0106 part 101. input rated input voltagev i/pn dc 24 v +25% / -16.66% undervoltage signal v i/p  20 v dc input current i i/pn at rated load and v i/pn = 24 v dc 4.8 a inrush current peak i i/pmax 100 a i  t value of inrush current 20 a  s efficiency at rated load and v i/pn = 20 v without fan with fan 0.71 typical 0.60 typical stored energy time for power failure > 5 ms input fuse 6 a fast; 250 v; 6.3 x 32 mm output 1 rated output voltage v o/pn1 5.1 v dc  0.5% rated output current i o/pn1 10 a ripple  1% of v o/p1 static voltage tolerances at 10% load variation at 5% variation of ue at temperature variation /1 k  0.02% of v o/p1  0.04% of v o/p1  0.02% of v o/p1 dynamic voltage tolerances at load surge from 50 % to 100 % overshoot settling time  5% of v o/p1  5 ms protection and monitoring overvoltage shutdown v o/p1 undervoltage signal v o/p1 current limiting for overload 6 v  5% 4.75 v + 5% 1.05 to 1.15 i o/pn1 test sockets for v o/p1 i o/p1 on front plate on front plate (3 v  10 a) linearity range 0.5 v/1.6 a to 3 v/10 a signaling section signals for simatic s5 central controllers and expansion units power suppl y unit s
4-69 system manual c79000-g8576-c199-07 output 2 (bus) rated output voltage v o/p2 24 v dc +25% / -20% rated output current i o/p2 0.8 a total current rating 24v-/ 15v output  0.8 a ripple input voltage ripple protection and monitoring fuse for overcurrent protection test sockets for v o/p2 green led 15v/24v o.k. for v o/p2 (fuse monitor) 1.5 a fast; 250 v; 6.3 x 32 mm on front plate (24 v test) the led lights up when v o/p2 > 17.9 to 18.5 v output 2 (front) rated output voltage v o/pn4 24 v dc +25% / -24% rated output current i o/pn4 0.4 a capacitive load < 100 nf protection and monitoring overcurrent protection by current limiting i o/p4 test sockets for v o/p2 green led 24v o.k. for v o/p4 > 0.44 a on front plate (24 v test) the led lights up when v o/p4 > 16 v  20% total current rating of 24 v voltages (bus and front) must not exceed 0.8 a output 3 with 15 v auxiliary submodule rated output voltage v o/pn3 15 v dc  5% rated output current i o/pn3 0.5 a ripple  5% of v o/pn3 protection and monitoring overvoltage protection (output is short-circuited at v o/p3 ) undervoltage signal (led 15v/24v o.k. on front plate goes off at) overcurrent protection i o/p3 by current limiting test socket for v o/p3  18.5 v  14 v  3% > 0.5 to 1.5 a on front plate (15 v test) fans fan type 2 axial fans input voltage 24 v dc flow rate per fan 160 m3/h (no-load value) fan monitoring air flow monitoring with ptc thermistors as sensors; stoppage of one or both fans is detected and signaled to the exterior via fan fault led and relay contacts, and results in shutdown of output voltage (switched off via jumper f-r). expected service life of a fan 30 000 to 40 000 h typical at 55 o c; 40 000 to 50 000 h typical at 30 o c; isolation primary/secondary and test voltages no weight 3.75 kg environmental data see technical specifications of the s5-135u/155u cc rfi suppression din vde 0871, a central controllers and expansion units power suppl y unit s
4-70 system manual c79000-g8576-c199-07 4.5 fan submodules 4.5.1 technical description the fan submodule variants 6es5 988-3la11 (230 v ac) and 6es5 988-3na11 (24 v dc) are described in the following section. a fan submodule has the following function:  heat dissipation the fan submodule dissipates any excess heat created in the central controller or expansion unit. the following terminals and leds are fitted on the front plate (the front plate of the -3la11 is shown as an example): 6es5 988-3la11 ac 230v caution! disconnect before removing voltage selector inside the unit! ac line l1 n siemens monitor output use copper wire 60/75 c only! tightening torque: terminals 0.8nm/ 1.8 nm fan fault relay max. 250v ac/3a 13 2 power supply! 12 3 45 67 8 910 id label element purpose 1 protective conductor terminal for fan submodule and housing. 2 strain reliefs for connecting cables, with metal contact surface for cable shields. 3 230 v ac screw terminals l1, n ac connection (details for -3la11) 24 v dc screw terminals + 24 v dc supply (details for -3na11) 4 monitor output relay output standstill of one or both fans is signaled via led and relay contact. 5 fan fault red led the led lights up to indicate a fan fault. connections and leds central controllers and expansion units power suppl y unit s
4-71 system manual c79000-g8576-c199-07 ! caution observe the appropriate vde specifications, especially vde 0100. the terminals at the front are suitable for a conductor cross-section of 4 mm 2 solid or 2.5 mm 2 flexible. ensure adequate strain relief for the connections. the figure shows the setting of the voltage selector switch when delivered (230 v). front plate 2 1 f12 s13 230v id element purpose 1 fuse f12 protecting the fan submodule against overload 2 voltage selector switch s13 (-3la11 only) setting the fan submodule -3la11 for the available line voltage: (115 v or 120 v or 230 v) position of the voltage selector switch and the fuse central controllers and expansion units power suppl y unit s
4-72 system manual c79000-g8576-c199-07 4.5.2 setting and connecting the fan submodule before starting up your fan submodule, you must perform certain steps according to your requirements with respect to fan submodule behavior in the event of a fault. the fan submodule is delivered in the following state:  fitted in the cc or eu frame you ordered  ac line voltage set to 230 v if you wish to retain this setting, you can skip steps 2 to 5. step action 1 check the setting and cabling 2 remove the fan submodule if required 3 fit the fan submodule if required 4 wire the fan submodule to the installation (including fitting an isolating device to disconnect the ac line voltage) 5 on the -3la11 set the voltage selector switch (factory setting 230 v) if required 6 switch on the fan submodule for the first time wiring of the fan submodule must be planned within the scope of wiring the entire control system. the information required for the purpose and decision-making aids (for example, for local or central grounding) can be found in chapter 3, installation guidelines. two relay outputs allow you to install additional external signaling circuits for fault states, for example, to connect a cabinet lamp or horn. establishing the wiring establishing the signaling circuits central controllers and expansion units power suppl y unit s
4-73 system manual c79000-g8576-c199-07 the following applies to selecting the cables for the terminals: terminals cabling max. permissible cable cross-sections power supply ac line phase l 1 4 mm 2 solid or 2.5 mm 2 flexible neutral n 4 mm 2 solid or 2.5 mm 2 flexible protective conductor 4 mm 2 solid or 2.5 mm 2 flexible relay terminals, also suitable to 230 v ac / 3 a 4 mm 2 solid or 2.5 mm 2 flexible for installing and removing the fan submodule, refer to the instructions in section 4.3.2 on the power supply unit. these also apply in principle here. for wiring up the fan submodule, refer to the instructions in section 4.3.2 on the power supply unit. these also apply in principle here. the fan submodule is switched on when the line voltage for the central controller or expansion unit is switched on. ! caution if you have set the voltage selector switch on the -3la11 to 120 v, but the actual voltage value is 230 v, the fan submodule may be damaged when line voltage is switched on. fan submodule faults are indicated via relay contacts (amonitor outputo) and an led. the following table shows when the relay contacts are open or closed: fan submodule relay contact 1-2 relay contact 2-3 switched off open closed in normal operation closed open during fault open closed in the case of a fault, the red led afan faulto lights up. selecting cables installing and removing the fan submodule wiring up the fan submodule switching on the fan submodule for the first time fault indications/ fault diagnostics central controllers and expansion units power suppl y unit s
4-74 system manual c79000-g8576-c199-07 4.5.3 technical specifications important for the usa and canada the following approvals have been obtained:  ul-recognition-mark underwriters laboratories (ul) to standard ul 508, report e 116536  csa-certification-mark canadian standard association (csa) to standard c 22.2 no. 142, report lr 63534 6es5 988-3la11 6es5 988-3na11 safety specifications the power supply units comply with safety specifications vde 0805 / en 60950 / iec 60950 / vde 0160 and vde 0106 part 101. shock protection only ensured in the installed state. data for emc in the installed state see technical specifications of the s5-135u/155u cc safe isolation is ensured. input rated input voltage 110 v ac (93.5-121 v), 220 v ac (187-242 v) 24 v dc (20 - 30 v) input frequency 50/60 hz (48-63 hz) input current i i/pn approx. 0.48 a (and v i/pn = 120 v) approx. 0.24 a (and v i/pn = 230 v) approx. 1 a peak inrush current i i/pmax < 5 a < 10 a max. heat dissipation at rated load (with fans) approx. 52 w approx. 24 w max. heat dissipation at rated load (without fans) approx. 12 w approx. 9 w stored energy time during power failure > 20 ms input fuse 1.5 a fast; 250 v; 2.4 a 2 s service life approx. 42.000 h at 40 o c weight approx. 4 kg environmental data see technical specifications of the s5-135u/155u cc central controllers and expansion units power suppl y unit s
5-1 system manual c79000-g8576-c199-07 cpus, memory cards, memory submodules, interface submodules this chapter contains information on the cpus, memory cards, modules and submodules which you can use in your programmable controller. the following cpus may be fitted in an s5-135u/155u central controller:  cpu 948  cpu 928b  cpu 928  cpu 922. a programmable controller containing a cpu 948 is known as an S5-155U plc. a programmable controller containing cpus 928b, 928 and/or 922 (and not the cpu 948) is known as an s5-135u plc. you can fit a flash eprom memory card containing your user program in the cpu 948, 928b -3ua21 and 928 -3ua21. for the cpus 928b, 928 and 922, there are ram or eprom submodules for the purpose. cpus 948 and 928b have, apart from the programmer interface, a second serial interface. an interface submodule is required for physical adaptation. section description page 5.1 cpu 948b -3ua13 or cpu 948b -3ua23 5-2 5.2 cpu 948 5-17 5.3 cpu 928b -3ub21 5-30 5.4 cpu 928b 5-42 5.5 cpu 928 -3ua21 5-54 5.6 cpu 928 5-62 5.7 cpu 922 5-71 5.8 374 flash eprom cards 5-80 5.9 376 memory submodules 5-82 5.10 377 memory submodules 5-84 5.11 interface submodules 5-92 chapter overview 5
5-2 system manual c79000-g8576-c199-07 5.1 cpu 948b -3ua13 or cpu 948b -3ua23 this section contains the hardware description and technical specifications of the cpu 948b -3ua13 or the cpu 948b -3ua23. details on programming the cpu 948 can be found in the cpu 948 programming guide. 5.1.1 technical description this section contains information on the application, design and structure of the cpu 948. you can use the cpu 948 in single and multiprocessor operation in the s5-135u/155u central controller (see chapter 6). there are two versions of cpu 948:  the cpu 948-1 offers 640 kbytes of internal user memory (ram).  the cpu 948-2 offers 1664 kbytes of internal user memory (ram). as an external memory medium, you can use a memory card 374. the following program processing levels are possible:  cyclic  time-controlled (9 different timebases, real-time controlled, timeout)  interrupt-driven from the s5 bus (8 process interrupts at block boundaries via ib0 or, alternatively, 4 system interrupts)  soft stop. the electronic circuitry of the cpu 948b is on one pcb in the double eurocard format. the front plate width is 1 1/3 standard plug-in stations, i.e. 20 mm. in the central controller rack, the cpu 948b -3ua13 or the cpu 948b -3ua23 occupies one slot. application design cpus, memor y cards, memor y submodules, interface submodules
5-3 system manual c79000-g8576-c199-07 5.1.2 installation and startup there are four system interrupts for interrupt-driven program processing with the cpu 948:  inta/b/c/d (depending on the cpu slot, see also section 4.1.1)  inte  intf  intg. the interrupts you wish to use must be enabled by inserting the jumper plugs provided. the jumper socket is situated on the basic board above the receptacle for the memory card. the exact location is given in figure 5-1: figure 5-1 location of jumper socket if you want to operate an im308c in the im3/im4 area and additional digital or analog modules in the central controller, you must insert the jumper shown in figure 5-1. jumper settings cpus, memor y cards, memor y submodules, interface submodules
5-4 system manual c79000-g8576-c199-07 note all other jumpers on the cpu 948b -3ua13 or the cpu 948b -3ua23 are required for quality testing by the manufacturer. you must not change these jumper settings. ! caution switch off the power supply before removing or inserting the module. proceed as follows to insert the cpu in the central controller: step action 1 release the upper locking bar of the central controller and ensure that the locking pin for the module is correctly positioned with the slot-head horizontal. 2 select the correct slot (based on the labelling of the locking bar). insert the cpus in the s5-135u/155u cc from slot 11. 3 push the module evenly into the guide rail until the lever over the locking pin is horizontal. 4 press the locking pin inwards on the bottom of the module and rotate it 90  clockwise. 5 secure the upper locking bar. note if you install the cpu 948 -3ua13 or the cpu 948 -3ua23 as the replacement for a double-width cpu 948, you must cover the slot which has become avaible with a blanking plate. removing and inserting the module insertion cpus, memor y cards, memor y submodules, interface submodules
5-5 system manual c79000-g8576-c199-07 proceed as follows to remove the cpu: step action 1 release the upper locking bar of the central controller. 2 release the locking pin of the module. 3 press the release lever downwards and pull the module forwards and out of the central controller. note only operate the cpu 948 -3ua13 or the cpu 948 -3ua23 with the submodule receptacle closed. you close it either by fitting an interface submodule or with the cover supplied. removal cpus, memor y cards, memor y submodules, interface submodules
5-6 system manual c79000-g8576-c199-07 the controls and indicators are arranged on the front plate of the cpu module: cpu 948u qvz adf zyk basp run stop reset si2 ov reset siemens 6es5948-3ua13 si1 s-f receptacle for user memory submodule momentary-contact mode switch mode switch run led (green) stop led (red) fault indicator led (red) pg interface, 15-pin interface si1 release lever locking pin order number and version sys fault led (red) si1 interface fault indicator led (red) si2 interface fault indicator led (red) figure 5-2 front plate of the cpu 948-3ua13 or the cpu 948-3ua23 controls and indicators cpus, memor y cards, memor y submodules, interface submodules
5-7 system manual c79000-g8576-c199-07 the mode switch has two settings: in the run setting, the cpu 948 processes the user program when the green run led is lit. the cpu 948 goes to the stop state when you switch from run to stop. the red stop led then lights up. you can initiate the overall reset, reset and restart functions with the momentary-contact mode switch: momentary-contact switch down with an overall reset, all ram areas are erased and initialized (both on the cpu and on a ram submodule). momentary-contact switch up during a reset, all flags, timers, counters and the process image will be erased. ob 20 will be invoked. processing of the user program will start from the beginning again. momentary-contact switch at midpoint with a restart, processing of the user program will continue from the point of interruption. the statuses of flags, timers, counters, and the process image are retained during stoppage of the cpu. mode switch run stop momentary- contact mode switch overall reset reset restart cpus, memor y cards, memor y submodules, interface submodules
5-8 system manual c79000-g8576-c199-07 given in the following overview are the functions of the run, stop and sys fault status leds. the stop led indicates a soft stop; the sys fault led indicates a hard stop. the cpu 948 can process a user program (ob 39) cyclically at the soft stop, but the digital outputs remain inhibited. at the hard stop, no program can run and the cpu has astopped.o this state can only be exited by switching the system voltage off and on again. run led stop led sys fault led status on off off the cpu is in the run state (cyclic operation). on on on appears briefly after power-up of the unit. off off off cpu is in the initial start or program check state. off on off cpu is in the soft stop state. off rapid flashing off cpu is in the soft stop state. overall reset has been requested by switch or from the operating system. off slow flashing off cpu is in the soft stop state. an error has occurred; see the cpu 948 programming guide for possible causes. off off on cpu is in the hard stop state. no program processing is taking place. you can only exit from this state by switching the system voltage off and on again. status indicators cpus, memor y cards, memor y submodules, interface submodules
5-9 system manual c79000-g8576-c199-07 given in the following overview are the causes for leds lighting up: qvz led on a module addressed by the program no longer acknowledges although/because  either it has acknowledged in single-processor operation upon restart of the cpu 948 in the area of the process image (ib0 to 127, qb0 to 127) and has been entered as present in the so-called 9th track;  or it has been entered in multi or single-processor operation in db 1 (address list) and has been recognized as present during the restart;  or it was addressed in direct access by operations lpy, lpw, tpy, tpw, loy, low, toy, tow;  or the data handling blocks cannot access the module. possible causes:  module failure  module removed during operation, in the stop state or in the off state without subsequent restart. a timeout occurred during access to the user memory. adf led on the user program has referred to an address in the process image under which no module was inserted in the i/os or was not entered in db 1 during the last restart. zyk led on the preset cycle time monitor has responded and cyclic program processing is interrupted. basp led on command output is inhibited and the digital outputs will be directly switched to the safe state (0). a detailed description of interrupt and error handling can be found in the cpu 948 programming guide. leds for fault indication and signaling cpus, memor y cards, memor y submodules, interface submodules
5-10 system manual c79000-g8576-c199-07 leds si1 and si2 indicate faults in communication via interfaces si1 and si2: led si1 led si2 cause on on communication is not possible at both interfaces. internal fault. on off si1: no communication possible. internal fault. si2: interface is initialized and ready. led si2 is always off if no interface module is inserted. off on si1: interface is initialized and ready. si2: no communication possible. wrong module inserted or internal fault. off off both interfaces are initialized and ready. led si2 is always off if no interface module is inserted. fault leds si1 and si2 cpus, memor y cards, memor y submodules, interface submodules
5-11 system manual c79000-g8576-c199-07 the module must be inserted at the correct slot in the central controller. the backup battery must be fitted and in order for the cpu to start. proceed as follows: step action result 1 set the mode switch to stop 2 switch the system voltage on. the following leds must light up on the cpu: red stop led (flashing rapidly) red basp led 3 hold the operating mode switch in the overall reset setting and simultaneously set the mode switch from stop to run. the red stop led is now permanently lit. if the red sys fault led also lights up, an error has occurred during overall reset. in this case the measures described must be repeated. if necessary, switch the system voltage off and on again. if the led is still lit, the module is faulty. continue as follows: step action result 1 set the mode switch to stop. 2 hold the mc switch in the reset setting and simultaneously set the mode switch from stop to run. red stop led goes off green run led lights up red basp led goes off the cpu is now in the run state but still has no user program. startup overall reset reset cpus, memor y cards, memor y submodules, interface submodules
5-12 system manual c79000-g8576-c199-07 you can also carry out a manual restart of the cpu 948 with the mode switch. the cpu 948 programming guide will indicate when a manual restart is permissible. step action result 1 set the mode switch from stop to run red stop led goes off run led lights up red basp led goes off for maintenance purposes or in the event of a fault, this startup without user program in single-processor operation can serve to establish whether the cpu is operating without errors. restart cpus, memor y cards, memor y submodules, interface submodules
5-13 system manual c79000-g8576-c199-07 5.1.3 interfaces of the cpu 948 this section contains information on the interfaces of the cpu 948. you can use the pg interface on the cpu 948 either via the front connector or via the 923c coordinator module and the s5 bus. note simultaneous operation of the pg interface via the front connector of the cpu 948 and via the 923c coordinator is not possible. switching the pg online without a job request is already sufficient to operate the interface. electrically, it is merely a pg interface which can be operated via two different terminals. the connection to the pg can be established in every operational state of the cpu. you can optionally use the second interface of the cpu 948 -3ua13 or the cpu 948 -3ua23 as:  a pg interface (for pg and operator panels)  interface for the rk 512 computer link  interface for data transmission with procedures 3964/3964r  interface for data transmission with the aopen drivero  interface for data transmission via the sinec l1 bus. to utilize the second interface as the pg interface, you need the  pg submodule. you need one of the following interface submodules for the rk 512 computer link, for data transmission with procedures 3964/3964r and for data transmission with the aopen drivero:  v.24 submodule (rs 232c)  tty submodule  rs422 a/485 submodule (only in the rs422 a module). to utilize the second interface for data transmission via the sinec l1 bus, you need the  sinec l1 submodule. the cpu 948 -3ua13 or the cpu 948 -3ua23 is delivered without an interface submodule. you can operate the cpu 948 -3ua13 or the cpu 948 -3ua23 without an integral interface submodule. the opening to accept a submodule in the front plate is closed by a cover. only remove the cover to fit an interface submodule. a description of interface submodules can be found in section 5.11, and the order numbers in the ordering information. a detailed description of the second interface can be found in the cpu 928b/cpu 948 communication manual. pg interface si1 second interface si2 cpus, memor y cards, memor y submodules, interface submodules
5-14 system manual c79000-g8576-c199-07 a pg-plc link via sinec h1 allows very advanced communication between the partners. for example, the user software can be loaded into the cpu 948 up to eight-times faster than with serial communication. for this link you will need, in addition to the cpu 948, a cpu 143 (version  2.1) in the plc and a pg7xx with sinec h1 connection and the step 5 single-tasking software from version 6.0 or multi-tasking from version 2.0. note you cannot implement communication via sinec h1 in parallel with the serial interfaces. communication via sinec h1 is described in detail in the cpu 948 programming guide. communication via backplane bus with sinec h1 cpus, memor y cards, memor y submodules, interface submodules
5-15 system manual c79000-g8576-c199-07 5.1.4 technical specifications important for the usa and canada the following approvals have been obtained:  ul listing mark underwriters laboratories (ul) to standard ul 508, report e 85972  csa certification mark canadian standard association (csa) to standard c 22.2 no. 142, report lr 63533 degree of protection ip 00 climatic ambient conditions see technical specifications of the s5-135u/155u cc mechanical ambient conditions see technical specifications of the s5-135u/155u cc noise immunity, electromagnetic compatibility (emc) see technical specifications of the s5-135u/155u cc supply voltage 5 v  5 % 24 v + 25 %/ 17 % current consumption at 5 v 1.5 a typical backup voltage 3.4 v backup current 20  a typical (at 25  c) p area o area im3 area im4 area total digital inputs with process image digital inputs without process image or analog inputs 1024 max. 1024 max. 64 max. 2048 max. 128 max. 2048 max. 128 max. 2048 max. 128 max. 1024 max. 7168 max. 448 max. digital outputs with process image digital outputs without process image or analog outputs 1024 max. 1024 max. 64 max. 2048 max. 128 max. 2048 max. 128 max. 2048 max. 128 max. 1024 max. 7168 max. 448 max. flags 2048 s flags 32768 timers 256 counters 256 size of user memory 64 x 2  bytes max., ram transmission rate of the serial pg interface 9600 bps program blocks pb 256 sequence blocks sb 256 function blocks fb 256 function blocks fx 256 cpus, memor y cards, memor y submodules, interface submodules
5-16 system manual c79000-g8576-c199-07 data blocks db 256, of which 253 are freely available data blocks dx 256, of which 253 are freely available organization blocks ob ob 1 to 39 (interfaces for operating system) integrated special function organization blocks ob ob 121, 122, 124-126, 131-133, 141-143, 150, 151, 153, 200, 202-205, 222, 223, 254, 255 integrated serial interface pg interface optional serial interface via interface submodules, optionally as v.24, tty, rs422 a/485 submodule, sinec l1 or pg interface backplane bus s5 bus dimensions (w x h x d) 20.32 x 233.4 x 160 mm weight approx. 0.6 kg cpus, memor y cards, memor y submodules, interface submodules
5-17 system manual c79000-g8576-c199-07 5.2 cpu 948 this section contains the hardware description and the technical specifications of the cpu 948. details on programming the cpu 948 can be found in the cpu 948 programming guide. 5.2.1 technical description this section contains information on the application, design and structure of the cpu 948. you can use the cpu 948 in single and multiprocessor operation in the s5-135u/155u central controller (see chapter 6). there are two versions of cpu 948:  the cpu 948-1 offers 640 kbytes of internal user memory (ram).  the cpu 948-2 offers 1664 kbytes of internal user memory (ram). a simatic s5 flash eprom memory card (known as a memory card for short in the following) can be inserted in the cpu 948 as the storage medium for user program and user data. the contents of the memory card are copied into the internal ram of the cpu upon overall reset. the programming language is step 5 (lad, csf, stl, scl). the cpu 948 processes all step 5 operations at very high speed, and uses fast floating-point arithmetic. the following program processing levels are possible:  cyclic  time-controlled (9 different timebases, real-time controlled, timeout)  interrupt-driven from the s5 bus (8 process interrupts at block boundaries via ib0 or, alternatively, 4 system interrupts)  soft stop. the electronic circuitry of the cpu 948, including the ram, is on two pcbs of double eurocard format which are screwed to each other. the two pcbs must not be separated. the front plate width of the module is 2 2/3 standard plug-in stations, i.e. 40 mm. in the central controller rack, the cpu 948 occupies two slots. application design cpus, memor y cards, memor y submodules, interface submodules
5-18 system manual c79000-g8576-c199-07 5.2.2 installation and startup this section explains the installation and removal of the module in the cc, controls and indicators on the front plate of the cpu, and the procedure for module startup. there are four system interrupts for interrupt-driven program processing with the cpu 948:  inta/b/c/d (depending on the cpu slot, see also section 4.1.1)  inte  intf  intg. the interrupts you wish to use must be enabled by inserting the jumper plugs provided. the jumper socket is situated on the basic board above the receptacle for the memory card. the exact location is given in figure 5-3: intf intg inte inta/b/c/d view of underside of module jumper front panel figure 5-3 location of jumper socket location of an additional jumper for the functions described below if you want to operate an im308c in the im3/im4 area and additional digital or analog modules in the central controller, you must insert the jumper shown in figure 5-3. jumper settings cpus, memor y cards, memor y submodules, interface submodules
5-19 system manual c79000-g8576-c199-07 note all other jumpers are required for quality testing by the manufacturer. you must not change these jumper settings. ! caution switch off the power supply before removing or inserting the module. the basic board and expansion board of the cpu 948 are one unit and must not be separated. proceed as follows to insert the cpu in the central controller: step action 1 release the upper locking bar of the central controller and ensure that the locking pin for the module is correctly positioned with the slot-head horizontal. 2 select the correct slot (based on the labelling of the locking bar). insert the cpus in the s5-135u/155u plc from the extreme left at slot 11. 3 push the module evenly into the guide rail until the lever over the locking pin is horizontal. 4 press the locking pin inwards on the bottom of the module and rotate it 90  clockwise. 5 secure the upper locking bar. proceed as follows to remove the cpu: step action 1 release the upper locking bar of the central controller. 2 release the locking pin of the module. 3 press the release lever downwards and pull the module forwards and out of the central controller. removing and inserting the module insertion removal cpus, memor y cards, memor y submodules, interface submodules
5-20 system manual c79000-g8576-c199-07 the controls and indicators are arranged on the front plate of the cpu module: siemens 6es59483ua11 run stop run stop sys fault reset rcksetzen url?schen overall reset qvz adf zyk basp init si1 si2 receptacle for S5-155U cpu948 memory card mode switch led (green) led (red) led (red) momentary-contact mode switch fault indicator leds (red) fault indicator led (red) interface fault indicator leds (red) order number and v ersion interface si1 pg interface, 15-pin release lever locking pin si1 si2 second serial interface si2 receptacle for interface module figure 5-4 controls and indicators of the cpu 948 controls and indicators cpus, memor y cards, memor y submodules, interface submodules
5-21 system manual c79000-g8576-c199-07 the mode switch has two settings: in the run setting, the cpu 948 processes the user program when the green run led is lit. the cpu 948 will go to a soft stop when you switch over from run to stop. the red stop led will then light up. you can initiate the overall reset, reset and restart functions with the momentary-contact mode switch and the mode changeover switch: momentary-contact switch down during an overall reset, the internal ram is reinitialized, i.e. existing data will be erased and the contents of the memory card, if present, will be copied into the internal ram. momentary-contact switch up during a reset, all flags, timers, counters and the process image will be erased. ob 20 will be invoked. processing of the user program will start from the beginning again. momentary-contact switch at midpoint with a restart, processing of the user program will continue from the point of interruption. the statuses of flags, timers, counters and the process image are retained during stoppage of the cpu. mode switch run stop momentary- contact mode switch overall reset reset restart cpus, memor y cards, memor y submodules, interface submodules
5-22 system manual c79000-g8576-c199-07 given in the following overview are the functions of the run, stop and sys fault status leds. the stop led indicates a soft stop; the sys fault led indicates a hard stop. the cpu 948 can process a user program (ob 39) cyclically at the soft stop, but the digital outputs remain inhibited. at the hard stop, no program can run and the cpu has astopped.o this state can only be exited by switching the system voltage off and on again. run led stop led sys fault led status on off off the cpu is in the run state (cyclic operation). on on on appears briefly after power-up of the unit. off off off cpu is in the initial start or program check state. off on off cpu is in the soft stop state. off rapid flashing off cpu is in the soft stop state. overall reset has been requested by switch or from the operating system. off slow flashing off cpu is in the soft stop state. an error has occurred; see the cpu 948 programming guide for possible causes. off off on cpu is in the hard stop state. no program processing is taking place. you can only exit from this state by switching the system voltage off and on again. status indicators cpus, memor y cards, memor y submodules, interface submodules
5-23 system manual c79000-g8576-c199-07 given in the following overview are the causes for leds lighting up: qvz led on a module addressed by the program no longer acknowledges although/because  either it has acknowledged in single-processor operation upon restart of the cpu 948 in the area of the process image (ib0 to 127, qb0 to 127) and has been entered as present in the so-called 9th track;  or it has been entered in multi or single-processor operation in db 1 (address list) and has been recognized as present during the restart;  or it was addressed in direct access by operations lpy, lpw, tpy, tpw, loy, low, toy, tow;  or the data handling blocks cannot access the module. possible causes:  module failure  module removed during operation, in the stop state or in the off state without subsequent restart. a timeout occurred during access to the user memory. adf led on the user program has referred to an address in the process image under which no module was inserted in the i/os or was not entered in db 1 during the last restart. zyk led on the preset cycle time monitor has responded and cyclic program processing is interrupted. basp led on command output is inhibited and the digital outputs will be directly switched to the safe state (0). init led on this led is continuously lit for a short time during initialization after power on and during operation in the event of system faults. a detailed description of interrupt and error handling can be found in the cpu 948 programming guide. leds for fault indication and signaling cpus, memor y cards, memor y submodules, interface submodules
5-24 system manual c79000-g8576-c199-07 leds si1 and si2 indicate faults in communication via interfaces si1 and si2: led si1 led si2 cause on on communication is not possible at both interfaces. internal fault. on off si1: no communication possible. internal fault. si2: interface is initialized and ready. led si2 is always off if no interface module is inserted. off on si1: interface is initialized and ready. si2: no communication possible. wrong module inserted or internal fault. off off both interfaces are initialized and ready. led si2 is always off if no interface module is inserted. fault leds si1 and si2 cpus, memor y cards, memor y submodules, interface submodules
5-25 system manual c79000-g8576-c199-07 the modules must be inserted at the correct slots in the central controller. the backup battery must be fitted and in order for the cpu to start. proceed as follows: step action resultat 1 set the mode switch to stop. 2 switch the system voltage on. the following leds must light up on the cpu: red stop led (flashing rapidly) red init led, briefly red basp 2) led 3 hold the mc 1) switch in the overall reset setting and simultaneously set the mode switch from stop to run. the red stop led is now permanently lit. 1) mc: momentary-contact 2) basp: command output inhibit if the red sys fault led also lights up, an error has occurred during overall reset. in this case the measures described must be repeated. if necessary, switch the system voltage off and on again. if the led is still lit, the module is faulty. continue as follows: step action result 4 set the mode switch to stop. 5 hold the mc switch in the reset setting and simultaneously set the mode switch from stop to run. red stop led goes off green run led lights up red basp led goes off the cpu is now in the run state but still has no user program. startup overall reset reset cpus, memor y cards, memor y submodules, interface submodules
5-26 system manual c79000-g8576-c199-07 you can also carry out a manual restart of the cpu 948 with the mode switch. the cpu 948 programming guide will indicate when a manual restart is permissible. step action result 1 set the mode switch from stop to run red stop led goes off run led lights up red basp led goes off for maintenance purposes or in the event of a fault, this startup without user program in single-processor operation can serve to establish whether the cpu is operating without errors. restart cpus, memor y cards, memor y submodules, interface submodules
5-27 system manual c79000-g8576-c199-07 5.2.3 interfaces of the cpu 948 this section contains information on the interfaces of the cpu 948. you can use the pg interface on the cpu 948 either via the front connector or via the 923c coordinator module and the s5 bus. note simultaneous operation of the pg interface via the front connector of the cpu 948 and via the 923c coordinator is not possible. switching the pg online without a job request is already sufficient to operate the interface. electrically, it is merely a pg interface which can be operated via two different terminals. the connection to the pg can be established in every operational state of the cpu. you can also use the second interface of the cpu 948 as a pg interface. physical adaptation is achieved with a pg module (see also section 5.9, interface submodules). a detailed description of pg interfaces can be found in the cpu 948 programming guide. a pg-plc link via sinec h1 allows very advanced communication between the partners. for example, the user software can be loaded into the cpu 948 up to eight-times faster than with serial communication. for this link you will need, in addition to the cpu 948, a cpu 143 (version  2.1) in the plc and a pg7xx with sinec h1 connection and the step 5 single-tasking software from version 6.0 or multi-tasking from version 2.0. note you cannot implement communication via sinec h1 in parallel with the serial interfaces. communication via sinec h1 is described in detail in the cpu 948 programming guide. pg interface si1 interface si2 communication via parallel backplane bus with sinec h1 cpus, memor y cards, memor y submodules, interface submodules
5-28 system manual c79000-g8576-c199-07 5.2.4 technical specifications important for the usa and canada the following approvals have been obtained:  ul listing mark underwriters laboratories (ul) to standard ul 508, report e 85972  csa certification mark canadian standard association (csa) to standard c 22.2 no. 142, report lr 63533 degree of protection ip 00 climatic ambient conditions see technical specifications of the s5-135u/155u cc mechanical ambient conditions see technical specifications of the s5-135u/155u cc noise immunity, electromagnetic compatibility (emc) see technical specifications of the s5-135u/155u cc supply voltage 5 v  5 % current consumption at 5 v 3.6 a typical backup voltage 3.4 v backup current 10  a typical (at 25 5 c) p area o area im3 area im4 area total digital inputs with process image digital inputs without process image or analog inputs 1024 max. 1024 max. 64 max. 2048 max. 128 max. 2048 max. 128 max. 2048 max. 128 max. 1024 max. 7168 max. 448 max. digital outputs with process image digital outputs without process image or analog outputs 1024 max. 1024 max. 64 max. 2048 max. 128 max. 2048 max. 128 max. 2048 max. 128 max. 1024 max. 7168 max. 448 max. flags 2048 s flags 32768 timers 256 counters 256 size of user memory 640 or 1664 kbyte ram transmission rate of serial pg interface 9600 bps program blocks pb 256 sequence blocks sb 256 function blocks fb 256 function blocks fx 256 cpus, memor y cards, memor y submodules, interface submodules
5-29 system manual c79000-g8576-c199-07 data blocks db 256, of which 253 are freely available data blocks dx 256, of which 253 are freely available organization blocks ob ob 1 to 39 (interfaces for operating system) integrated special function organization blocks ob ob 121, 122, 124-126, 131-133, 141-143, 150, 151, 153, 200, 202-205, 222, 223, 254, 255 integrated serial interface pg interface optional serial interface pg interface with pg submodule backplane bus s5 bus dimensions (w x h x d) 40.6 x 233.4 x 160 mm weight approx. 1 kg cpus, memor y cards, memor y submodules, interface submodules
5-30 system manual c79000-g8576-c199-07 5.3 cpu 928b -3ub21 this section contains the hardware description and technical specifications of the cpu 928b -3ub21. details on programming the cpu 928b -3ub21 can be found in the cpu 928b -3ub21 programming guide. 5.3.1 technical description you can use the cpu 928b in single and multiprocessor operation in the s5-135u/155u central controller (see chapter 6). up to four cpus can be used. the cpu 928b is universally applicable, ensuring both very fast bit processing and very fast word processing. the following program processing levels are possible:  cyclic  time-controlled (9 different timebases)  real-time controlled  interrupt-driven (hardware interrupt)  delayed the programming language is step 5. the electronic circuitry of the cpu 928b is on one pcb in the double eurocard format. the board provides the connection to the s5 bus via two backplane connectors. the front plate width is 1 1/3 standard plug-in stations. application design cpus, memor y cards, memor y submodules, interface submodules
5-31 system manual c79000-g8576-c199-07 for storage of your program, user memory in the form of ram is integrated on the board. you can store up to 64 x 2 10 bytes of code and data blocks here. for data blocks, the cpu 928b additionally has an integrated db ram of 46 3/4 x 2 10 bytes. as an external memory medium for user programs and user data, you can use a memory card 374 with flash eprom. there are two independent interfaces on the front of the cpu 928b. you can connect programmers and ops to the first interface. this pg interface si1 is permanently installed on the cpu. you can use pg interface si1 either via the front connector of the cpu 928b or via the front connector of the 923c coordinator module. note simultaneous operation of pg interface si1 via the front connector of the cpu 928b and of the coordinator is not possible. electrically, it is merely a pg interface which can be operated via two different terminals. switching the programmer online without a job request is already sufficient to operate the interface. if you wish to utilize a second pg interface for connection of a pg or op, the connection must be made via the second pg interface with the pg submodule. apart from pg interface si1, the second interface si2 can also be used as a pg interface in parallel with the first one. you can only use the second pg interface via the front connector of the pg submodule on the cpu 928b. a detailed description of operations with the two pg interfaces can be found in the cpu 928b -3ub21 programming guide. the connection to the pg can be established with the cpu in any operational state. user memory memory card pg interface si1 cpus, memor y cards, memor y submodules, interface submodules
5-32 system manual c79000-g8576-c199-07 you can optionally use the second interface of the cpu 928b as:  a pg interface (for pg and operator panels)  interface for the rk 512 computer link  interface for data transmission with procedures 3964/3964r  interface for data transmission with the aopen drivero  interface for data transmission via the sinec l1 bus (from version 6es5 928-3ub12). to utilize the second interface as the pg interface, you need the  rg submodule you need one of the following interface submodules for the rk 512 computer link, for data transmission with procedures 3964/3964r and for data transmission with the aopen drivero:  v.24 submodule (rs 232c)  tty submodule  rs422 a/485 submodule (only in the rs422 a mode). to utilize the second interface for data transmission via the sinec l1 bus, you need the  sinec l1 submodule (from version 6es5 928-3ub12). the cpu 928b is delivered without an interface submodule. you can operate the cpu 928b without an integral interface submodule. the opening to accept a submodule in the front plate is closed by a cover. only remove the cover to fit an interface submodule. a description of interface submodules can be found in section 5.11, and the order numbers in the ordering information. a detailed description of the second interface can be found in the cpu 928b/cpu 948 communication manual. there is an interrupt line in the plc for each cpu. it can be used when the reaction to an event must occur with higher priority than the reaction to other events. to process an interrupt, cyclic program processing is interrupted and the program stored in ob 2 (ob for interrupt processing) is inserted (refer to the cpu 928b -3ub21 programming guide for further details). this interrupt-driven program processing is only possible using an interrupt-capable digital input module or a suitable operating cp/ip module. no jumper setting on the cpu 928b is required. please note, however, that the usable interrupt line on the backplane bus depends on the cpu slot and must be set accordingly on the i/o module (see section 4.1). second interface si2 process interrupt processing cpus, memor y cards, memor y submodules, interface submodules
5-33 system manual c79000-g8576-c199-07 5.3.2 installation and startup note all jumpers on the cpu 928b are required by the manufacturer for quality testing. you must not change the jumper settings. ! caution switch off the power supply before removing or inserting the module. proceed as follows to insert the cpu in the central controller: step action 1 release the upper locking bar of the central controller and ensure that the locking pin for the module is correctly positioned with the slot-head horizontal. 2 select the correct slot (based on the labelling of the locking bar). insert the cpus in the s5-135u/155u from slot 11. 3 push the module evenly into the guide rail until the lever over the locking pin is horizontal. 4 press the locking pin inwards on the bottom of the module and rotate it 90  clockwise. 5 secure the upper locking bar. note if you install the cpu 928b -3ub21 as the replacement for a double-width cpu 928 or 928b, you must cover the slot which has become avaible with a blanking plate. jumper settings removing and inserting the module insertion cpus, memor y cards, memor y submodules, interface submodules
5-34 system manual c79000-g8576-c199-07 proceed as follows to remove the cpu: step action 1 release the upper locking bar of the central controller. 2 release the locking pin of the module. 3 press the release lever downwards and pull the module forwards and out of the central controller. note only operate the cpu 928b with the submodule receptacle closed. you close it either by fitting an interface submodule or with the cover supplied. removal cpus, memor y cards, memor y submodules, interface submodules
5-35 system manual c79000-g8576-c199-07 the controls and indicators are arranged on the front plate of the cpu module: cpu 928b qvz adf zyk basp run stop reset si2 overall reset receptacle for user memory submodule momentary-contact mode switch mode switch leds (green) led (red) fault indicator leds (red) pg interface, 15-pin interface si 1 release lever locking pin order number and version siemens 6es5928-3ub21 interface fault indicator led (red) interface fault indicator led (red) interface 1 interface 2 receptacle for interface submodule interface si 2 figure 5-5 front plate of the cpu 928b-3ub21 controls and indicators cpus, memor y cards, memor y submodules, interface submodules
5-36 system manual c79000-g8576-c199-07 the mode switch has two settings: in the run setting, the cpu 928b processes the user program when the green run led is lit. the cpu 928b goes to the stop state when you switch from run to stop. the red stop led then lights up. you can initiate the overall reset, reset and restart functions with the momentary-contact mode switch: momentary-contact switch down with an overall reset, all ram areas are erased and initialized (both on the cpu and on a ram submodule). momentary-contact switch up during a reset, all flags, timers, counters and the process image will be erased. ob 20 will be invoked. processing of the user program will start from the beginning again. momentary-contact switch at midpoint with a restart, processing of the user program will continue from the point of interruption. the statuses of flags, timers, counters and the process image are retained during stoppage of the cpu. mode switch run stop momentary- contact mode switch overall reset reset restart cpus, memor y cards, memor y submodules, interface submodules
5-37 system manual c79000-g8576-c199-07 run led stop led status on off the cpu is in the run state. off on the cpu is in the stop state. after a stop request by switch or pg function, the stop led is continuously lit because the transition to the stop state was requested by the user or, in multiprocessor operation, by another cpu, and was not caused by the cpu itself. off off the cpu is in the initial start or program check state. off slow flashing the cpu is in the stop state. the cpu has caused a transition to the stop state (possibly also for the other cpus). if you set the mode switch to stop, the flashing led becomes continuously lit. off rapid flashing the cpu is in the stop state. an overall reset has been requested. this request can be initiated by the cpu itself or by operator action. qvz led on during direct access or process image update, a module addressed by the program no longer acknowledges although  either it has acknowledged in single-processor operation upon reset of the cpu 928b in the area of the process image (ib 0 to 127, qb 0 to 127) and has been entered as present in the a9th tracko (see programming guide, cpu 928b -3ub21), it h b t d i db 1 ( dd li t) i  or it has been entered in db 1 (address list) in multiprocessor or single-processor operation and has been recognized as present during the reset. possible causes  module failure.  module was pulled out during operation, in the stop state or in the off state without a subsequent reset. status indicators leds for fault indication and signaling cpus, memor y cards, memor y submodules, interface submodules
5-38 system manual c79000-g8576-c199-07 adf led on the user program has referenced an i/o address in the process image under which no module is inserted. zyk led on the maximum cycle monitoring time has been exceeded. basp led on command output is inhibited and the digital outputs will be directly switched to the safe state. a detailed description of interrupt and error handling can be found in the cpu 928b -3ub21 programming guide. led si1 led si2 cause on on no communication possible at both interfaces. internal error. on off si1: no communication possible. internal error. si2: if used, interface is initialized and ready. off on si1: interface is initialized and ready. si2: no communication possible. wrong interface submodule inserted or wrong parameters for interface or internal error. off off first interface and, if used, second interface are initialized and ready. cpus, memor y cards, memor y submodules, interface submodules
5-39 system manual c79000-g8576-c199-07 the modules must be inserted at the correct slots in the central controller. the backup battery must be fitted and in order for the cpu to start. step action result 1 set the mode switch to stop 2 switch the system voltage on. the following leds must light up on the cpu: red stop led (flashing rapidly) red basp 2) led 3 hold the mc 1) switch in the overall reset setting and simultaneously set the mode switch from stop to run. the red stop led is now permanently lit. 1) mc: momentary-contact 2) basp: command output inhibit step action result 1 set the mode switch to stop. 2 hold the mc switch in the reset setting and simultaneously set the mode switch from stop to run. red stop led goes off green run led lights up red basp led goes off the cpu is now in the run state but still has no user program. you can also carry out a manual restart of the cpu 928b with the mode switch. the cpu 928b -3ub21 programming guide will indicate when a manual restart is permissible. step action result 3 set the mode switch from stop to run. red stop led goes off green run led lights up red basp led goes off for maintenance purposes or in the event of a fault, this startup without user program in single-processor operation can serve to establish whether the cpu is operating without errors. startup overall reset reset restart cpus, memor y cards, memor y submodules, interface submodules
5-40 system manual c79000-g8576-c199-07 5.3.3 technical specifications important for the usa and canada the following approvals have been obtained:  ul listing mark underwriters laboratories (ul) to standard ul 508, report e 85972  csa certification mark canadian standard association (csa) to standard c 22.2 no. 142, report lr 63533 degree of protection ip 00 climatic ambient conditions see technical specifications of the s5-135u/155u cc mechanical ambient conditions see technical specifications of the s5-135u/155u cc noise immunity, electromagnetic compatibility (emc) see technical specifications of the s5-135u/155u cc supply voltage 5 v  5 % 24 v + 25 %/ 17 % current consumption at 5 v 0.5 a typical current consumption at 24 v 760 ma max. backup voltage 3.4 v backup current 20  a typical (at 25  c) p area o area im3 area im4 area total digital inputs with process image digital inputs without process image or analog inputs 1024 max. 1024 max. 64 max. 2048 max. 128 max. 2048 max. 128 max. 2048 max. 128 max. 1024 max. 7168 max. 448 max. digital outputs with process image digital outputs without process image or analog outputs 1024 max. 1024 max. 64 max. 2048 max. 128 max. 2048 max. 128 max. 2048 max. 128 max. 1024 max. 7168 max. 448 max. flags 2048 s flags 8192 timers 256 counters 256 size of user memory 64 x 2  bytes max., ram db ram 46 x 2  bytes transmission rate of the serial pg interface 9600 bps program blocks pb 256 sequence blocks sb 256 function blocks fb 256 function blocks fx 256 data blocks db 256, of which 253 are freely available data blocks dx 256, of which 253 are freely available cpus, memor y cards, memor y submodules, interface submodules
5-41 system manual c79000-g8576-c199-07 organization blocks ob ob 1 to 39 (interfaces for operating system) integrated special function organization blocks ob see pocket guide integrated serial interface pg interface optional serial interface via interface submodules, optionally as v.24, tty, rs 422a/485 or pg interface backplane bus s5 bus dimensions (w x h x d) 20.32 x 233.4 x 160 mm weight approx. 0.6 kg cpus, memor y cards, memor y submodules, interface submodules
5-42 system manual c79000-g8576-c199-07 5.4 cpu 928b this section contains the hardware description and technical specifications of the cpu 928b. details on programming the cpu 928b can be found in the cpu 928b programming guide. 5.4.1 technical description you can use the cpu 928b in single and multiprocessor operation in the s5-135u/155u central controller (see chapter 6). up to four cpus can be used. the cpu 928b is universally applicable, ensuring both very fast bit processing and very fast word processing:  cyclic  time-controlled (9 different timebases)  real-time controlled  interrupt-driven (hardware interrupt)  delayed (from version 6es5 928-3ub12) the programming language is step 5. the electronic circuitry of the cpu 928b is on two pcbs (basic and expansion boards) in the double eurocard format. both pcbs are screwed together, linked via connectors, and must not be separated. the basic board provides the connection to the s5 bus via two backplane connectors. the front plate width is 2 2/3 standard plug-in stations. application design cpus, memor y cards, memor y submodules, interface submodules
5-43 system manual c79000-g8576-c199-07 you require a user memory submodule (ram or eprom) for storage of your program. you can store up to 64 x 2 10 bytes of code and data blocks here. for data blocks, the cpu 928b additionally has an integrated db ram of 46 x 2 10 bytes. a description of the memory submodules can be found in sections 5.9 and 5.10; order numbers are given in the ordering information. there are two independent interfaces on the front of the cpu 928b. you can connect programmers and ops to the first interface. this pg interface si1 is permanently installed on the cpu. you can use pg interface si1 either via the front connector of the cpu 928b or via the front connector of the 923c coordinator module. note simultaneous operation of pg interface si1 via the front connector of the cpu 928b and of the coordinator is not possible. electrically, it is merely a pg interface which can be operated via two different terminals. switching the programmer online without a job request is already sufficient to operate the interface. if you wish to utilize a second pg interface for connection of a pg or op, the connection must be made via the second pg interface with the pg submodule. apart from pg interface si1, the second interface si2 can also be used as a pg interface in parallel with the first one. you can only use the second pg interface via the front connector of the pg submodule on the cpu 928b. a detailed description of operations with the two pg interfaces can be found in the cpu 928b programming guide. the connection to the pg can be established with the cpu in any operational state. user memory pg interface si1 cpus, memor y cards, memor y submodules, interface submodules
5-44 system manual c79000-g8576-c199-07 you can optionally use the second interface of the cpu 928b as:  a pg interface (for pg and operator panels)  interface for the rk 512 computer link  interface for data transmission with procedures 3964/3964r  interface for data transmission with the aopen drivero  interface for data transmission via the sinec l1 bus (from version 6es5 928-3ub12). to utilize the second interface as the pg interface, you need the  pg submodule. you need one of the following interface submodules for the rk 512 computer link, for data transmission with procedures 3964/3964r and for data transmission with the aopen drivero:  v.24 submodule (rs 232c)  tty submodule  rs422 a/485 submodule (only in the rs422 a module). to utilize the second interface for data transmission via the sinec l1 bus, you need the  sinec l1 submodule (from version 6es5 928-3ub12). the cpu 928b is delivered without an interface submodule. you can operate the cpu 928b without an integral interface submodule. the opening to accept a submodule in the front plate is closed by a cover. only remove the cover to fit an interface submodule. a description of interface submodules can be found in section 5.11, and the order numbers in the ordering information. a detailed description of the second interface can be found in the cpu 928b communication manual. there is an interrupt line in the plc for each cpu. it can be used when the reaction to an event must occur with higher priority than the reaction to other events. to process an interrupt, cyclic program processing is interrupted and the program stored in ob 2 (ob for interrupt processing) is inserted. (refer to the cpu 928b programming guide for further details.) this interrupt-driven program processing is only possible using an interrupt-capable digital input module or a suitable operating cp/ip module. no jumper setting on the cpu 928b is required. please note, however, that the usable interrupt line on the backplane bus depends on the cpu slot and must be set accordingly on the i/o module (see section 4.1). second interface si2 process interrupt processing cpus, memor y cards, memor y submodules, interface submodules
5-45 system manual c79000-g8576-c199-07 5.4.2 installation and startup note all jumpers on the cpu 928b are required by the manufacturer for quality testing. you must not change the jumper settings. ! caution switch off the power supply before removing or inserting the module. the basic board and expansion board of the cpu 928b are one unit and must not be separated. proceed as follows to insert the cpu in the central controller: step action 1 release the upper locking bar of the central controller and ensure that the locking pin for the module is correctly positioned with the slot-head horizontal. 2 select the correct slot (based on the labelling of the locking bar). insert the cpus in the s5-135u/155u from slot 11. 3 push the module evenly into the guide rail until the lever over the locking pin is horizontal. 4 press the locking pin inwards on the bottom of the module and rotate it 90 o clockwise. 5 secure the upper locking bar. jumper settings removing and inserting the module insertion cpus, memor y cards, memor y submodules, interface submodules
5-46 system manual c79000-g8576-c199-07 proceed as follows to remove the cpu: step action 1 release the upper locking bar of the central controller. 2 release the locking pin of the module. 3 press the release lever downwards and pull the module forwards and out of the central controller. note only operate the cpu 928b with the submodule receptacle closed. you close it either by fitting an interface submodule or with the cover supplied. removal cpus, memor y cards, memor y submodules, interface submodules
5-47 system manual c79000-g8576-c199-07 the controls and indicators are arranged on the front plate of the cpu module: siemens receptacle for user memory submodule mode switch led (green) led (red) momentary-contact mode switch fault indicator leds (red) pg interface, 15-pin interface si 1 release lever locking pin interface fault indicator leds (red) interface 1 interface 2 run stop run stop rcksetzen reset url?schen overall reset si1 si2 qvz adf zyk basp order number and v ersion receptacle for interface submodule interface si 2 si2 si1 6es5928-3ub12 cpu 928b figure 5-6 front plate of the cpu 928b controls and indicators cpus, memor y cards, memor y submodules, interface submodules
5-48 system manual c79000-g8576-c199-07 the mode switch has two settings: in the run setting, the cpu 928b processes the user program when the green run led is lit. the cpu 928b goes to the stop state when you switch from run to stop. the red stop led then lights up. you can initiate the overall reset, reset and restart functions with the momentary-contact mode switch: momentary-contact switch down with an overall reset, all ram areas are erased and initialized (both on the cpu and on a ram submodule). momentary-contact switch up during a reset, all flags, timers, counters and the process image will be erased. ob 20 will be invoked. processing of the user program will start from the beginning again. momentary-contact switch at midpoint with a restart, processing of the user program will continue from the point of interruption. the statuses of flags, timers, counters and the process image are retained during stoppage of the cpu. mode switch run stop momentary- contact mode switch overall reset reset restart cpus, memor y cards, memor y submodules, interface submodules
5-49 system manual c79000-g8576-c199-07 run led stop led status on off the cpu is in the run state. off on the cpu is in the stop state. after a stop request by switch or pg function, the stop led is continuously lit because the transition to the stop state was requested by the user or, in multiprocessor operation, by another cpu, and was not caused by the cpu itself. off off the cpu is in the initial start or program check state. off slow flashing the cpu is in the stop state. the cpu has caused a transition to the stop state (possibly also for the other cpus). if you set the mode switch to stop, the flashing led becomes continuously lit. off rapid flashing the cpu is in the stop state. an overall reset has been requested. this request can be initiated by the cpu itself or by operator action. qvz led on during direct access or process image update, a module addressed by the program no longer acknowledges although  either it has acknowledged in single-processor operation upon reset of the cpu 928b in the area of the process image (ib 0 to 127, qb 0 to 127) and has been entered as present in the a9th tracko (see programming guide, cpu 928b), it h b t d i db 1 ( dd li t) i  or it has been entered in db 1 (address list) in multiprocessor or single-processor operation and has been recognized as present during the reset. possible causes  module failure.  module was pulled out during operation, in the stop state or in the off state without a subsequent reset. status indicators leds for fault indication and signaling cpus, memor y cards, memor y submodules, interface submodules
5-50 system manual c79000-g8576-c199-07 adf led on the user program has referenced an i/o address in the process image under which no module is inserted. zyk led on the maximum cycle monitoring time has been exceeded. basp led on command output is inhibited and the digital outputs will be directly switched to the safe state. a detailed description of interrupt and error handling can be found in the cpu 928b programming guide. led si1 led si2 cause on on no communication possible at both interfaces. internal error. on off si1: no communication possible. internal error. si2: if used, interface is initialized and ready. off on si1: interface is initialized and ready. si2: no communication possible. wrong interface submodule inserted or wrong parameters for interface or internal error. off off first interface and, if used, second interface are initialized and ready. cpus, memor y cards, memor y submodules, interface submodules
5-51 system manual c79000-g8576-c199-07 the modules must be inserted at the correct slots in the central controller. the backup battery must be fitted and in order for the cpu to start. step action result 1 set the mode switch to stop. 2 switch the system voltage on. the following leds must light up on the cpu: red stop led (flashing rapidly) red basp 2) led 3 hold the mc 1) switch in the overall reset setting and simultaneously set the mode switch from stop to run. the red stop led is now permanently lit. 1) mc: momentary-contact 2) basp: command output inhibit step action result 1 set the mode switch to stop. 2 hold the mc switch in the reset setting and simultaneously set the mode switch from stop to run. red stop led goes off green run led lights up red basp led goes off the cpu is now in the run state but still has no user program. you can also carry out a manual restart of the cpu 928b with the mode switch. the cpu 928b programming guide will indicate when a manual restart is permissible. step action result 3 set the mode switch from stop to run. red stop led goes off green run led lights up red basp led goes off for maintenance purposes or in the event of a fault, this startup without user program in single-processor operation can serve to establish whether the cpu is operating without errors. startup overall reset reset restart cpus, memor y cards, memor y submodules, interface submodules
5-52 system manual c79000-g8576-c199-07 5.4.3 technical specifications important for the usa and canada the following approvals have been obtained:  ul listing mark underwriters laboratories (ul) to standard ul 508, report e 85972  csa certification mark canadian standard association (csa) to standard c 22.2 no. 142, report lr 63533 degree of protection ip 00 climatic ambient conditions see technical specifications of the s5-135u/155u cc mechanical ambient conditions see technical specifications of the s5-135u/155u cc noise immunity, electromagnetic compatibility (emc) see technical specifications of the s5-135u/155u cc supply voltage 5 v  5 % 24 v + 25 %/ -17 % current consumption at 5 v 5 a typical current consumption at 24 v 760 ma max. backup voltage 3.4 v backup current 20  a typical (at 25  c) p area o area im3 area im4 area total digital inputs with process image digital inputs without process image or analog inputs 1024 max. 1024 max. 64 max. 2048 max. 128 max. 2048 max. 128 max. 2048 max. 128 max. 1024 max. 7168 max. 448 max. digital outputs with process image digital outputs without process image or analog outputs 1024 max. 1024 max. 64 max. 2048 max. 128 max. 2048 max. 128 max. 2048 max. 128 max. 1024 max. 7168 max. 448 max. flags 2048 s flags 8192 timers 256 counters 256 size of user memory 64 x 2  bytes max., eprom or ram db ram 46 x 2  byte transmission rate of the serial pg interface 9600 bps program blocks pb 256 sequence blocks sb 256 function blocks fb 256 function blocks fx 256 data blocks db 256, of which 253 are freely available data blocks dx 256, of which 253 are freely available cpus, memor y cards, memor y submodules, interface submodules
5-53 system manual c79000-g8576-c199-07 organization blocks ob ob 1 to 39 (interfaces for operating system) integrated special function organization blocks ob see pocket guide integrated serial interface pg interface optional serial interface via interface submodules, optionally as v.24, tty, rs 422a/485 or pg interface sinec l1 interface from version 6es5 928-3ub12 backplane bus s5 bus dimensions (w x h x d) 40.64 x 233.4 x 160 mm weight approx. 1 kg cpus, memor y cards, memor y submodules, interface submodules
5-54 system manual c79000-g8576-c199-07 5.5 cpu 928 -3ua21 this section contains the hardware description and technical specifications of the cpu 928 -3ua21. details on programming the cpu 928 can be found in the cpu 928 programming guide. 5.5.1 technical description you can use the cpu 928 in single and multiprocessor operation in the s5-135u/155u central controller (see chapter 6). up to four cpus can be used. the cpu 928 is universally applicable, ensuring both very fast bit processing (optimized for open-loop tasks) and word processing (optimized for closed-loop tasks). the following program processing levels are possible:  cyclical  time-controlled (9 different timebases)  interrupt-driven (hardware interrupt) the programming language is step 5. the electronic circuitry of the cpu 928 is on one pcb in the double eurocard format. the board provides the connection to the s5 bus via two backplane connectors. the front plate width is 1 1/3 standard plug-in stations. application design cpus, memor y cards, memor y submodules, interface submodules
5-55 system manual c79000-g8576-c199-07 for storage of your program, user memory in the form of ram is integrated on the board. you can store up to 64 x 2 10 bytes of code and data blocks here. for data blocks, the cpu 928 additionally has an integrated db ram of 46 x 2 10 bytes. note the db ram is loaded with db/dx blocks when the user memory is full. there is an interrupt line (ir) in the plc for each cpu. it can be used when the reaction to one or more events must occur with higher priority than the reaction to other events. to process a process interrupt, cyclic program processing is interrupted and the program stored in ob 2 (ob for interrupt processing) is inserted. (refer to the cpu 928 programming guide for further details.) this interrupt-driven program processing is only possible using an interrupt-capable digital input module (e.g. 6es5 432-...) or a cp/ip module which operates in this way. user memory process interrupt processing cpus, memor y cards, memor y submodules, interface submodules
5-56 system manual c79000-g8576-c199-07 5.5.2 installation and startup ! caution switch off the power supply before removing or inserting the module. proceed as follows to insert the cpu in the central controller: step action 1 release the upper locking bar of the central controller and ensure that the locking pin for the module is correctly positioned with the slot-head horizontal. 2 select the correct slot (based on the labelling of the locking bar). insert the cpus in the s5-135u/155u from slot 11. 3 push the module evenly into the guide rail until the lever over the locking pin is horizontal. 4 press the locking pin inwards on the bottom of the module and rotate it 90 o clockwise. 5 secure the upper locking bar. note if you install the cpu 928 -3ua21 as the replacement for a double-width cpu, you must cover the slot which has become available with a blanking plate. proceed as follows to remove the cpu: step action 1 release the upper locking bar of the central controller. 2 release the locking pin of the module. 3 press the release lever downwards and pull the module forwards and out of the central controller. removing and inserting the module insertion removal cpus, memor y cards, memor y submodules, interface submodules
5-57 system manual c79000-g8576-c199-07 the controls and indicators are arranged on the front plate of the cpu module: cpu 928a qvz adf zyk basp run stop reset si1 overall reset receptacle for user memory submodule momentary-contact mode switch mode switch led (green) led (red) fault indicator leds (red) pg interface, 15-pin release lever locking pin order number and version siemens es5928-3ua21 interface fault indicator led (red) figure 5-7 front plate of the cpu 928 -3ua21 controls and indicators cpus, memor y cards, memor y submodules, interface submodules
5-58 system manual c79000-g8576-c199-07 the mode switch has two settings: in the run setting, the cpu 928-3ua21 processes the user program when the green run led is lit. the cpu 928-3ua21 goes to the stop state when you switch from run to stop. the red stop led then lights up. you can initiate the overall reset, reset and restart functions with the momentary-contact mode switch: momentary-contact switch down with an overall reset, all ram areas are erased and initialized. momentary-contact switch up during a reset, all flags, timers, counters and the process image will be erased. ob 20 will be invoked. processing of the user program will start from the beginning again. momentary-contact switch at midpoint with a restart, processing of the user program will continue from the point of interruption. the statuses of flags, timers, counters and the process image are retained during stoppage of the cpu. run led stop led status on off the cpu is in the run state. off on the cpu is in the stop state. after a stop request by switch or pg function, the stop led is continuously lit because the transition to the stop state was requested by the user or, in multiprocessor operation, by another cpu, and was not caused by the cpu itself. off off the cpu is in the initial start or program check state. off slow flashing the cpu is in the stop state. the cpu has caused a transition to the stop state (possibly also for the other cpus). if you set the mode switch to stop, the flashing led becomes continuously lit. off rapid flashing the cpu is in the stop state. an overall reset has been requested. this request can be initiated by the cpu itself or by operator action. mode switch run stop momentary- contact mode switch overall reset reset restart status indicators cpus, memor y cards, memor y submodules, interface submodules
5-59 system manual c79000-g8576-c199-07 qvz led on during direct access or process image update, a module addressed by the program no longer acknowledges although  either it has acknowledged in single processor operation upon reset of the cpu 928 in the area of the process image (ib 0 to 127, qb 0 to 127) and has been entered as present in the a9th tracko (see programming guide, cpu 928), it h b t d i db 1 ( dd li t) i  or it has been entered in db 1 (address list) in multiprocessor or single-processor operation and has been recognized as present during the reset. possible causes  module failure.  module was pulled out during operation, in the stop state or in the off state without a subsequent reset. adf led on the user program has referenced an i/o address under which no module is inserted. zyk led on the maximum cycle time has been exceeded. basp led on command output is inhibited and the digital outputs will be directly switched to the safe state. a detailed description of interrupt and error handling can be found in the cpu 928 programming guide. leds for fault indication and signaling cpus, memor y cards, memor y submodules, interface submodules
5-60 system manual c79000-g8576-c199-07 the module must be inserted at the correct slot in the central controller. the backup battery must be fitted and in order for the cpu to start. step action result 1 set the mode switch to stop 2 switch the system voltage on. the following leds must light up on the cpu: red stop led (flashing rapidly) red basp led 3 hold the mc 1) switch in the overall reset setting and simultaneously set the mode switch from stop to run. the red stop led is now permanently lit. 1) mc: momentary-contact step action result 1 set the mode switch to stop. 2 hold the mc switch in the reset setting and simultaneously set the mode switch from stop to run. red stop led goes off green run led lights up red basp led goes off the cpu is now in the run state but still has no user program. you can also carry out a manual restart of the cpu 928-3ua21 with the mode switch. the cpu 928 programming guide will indicate when a manual restart is permissible. step action result 1 set the mode switch from stop to run. red stop led goes off green run led lights up red basp led goes off for maintenance purposes or in the event of a fault, this startup without user program in single-processor operation can serve to establish whether the cpu is operating without errors. startup overall reset reset restart cpus, memor y cards, memor y submodules, interface submodules
5-61 system manual c79000-g8576-c199-07 5.5.3 technical specifications important for the usa and canada the following approvals have been obtained:  ul listing mark underwriters laboratories (ul) to standard ul 508, report e 85972  csa certification mark canadian standard association (csa) to standard c 22.2 no. 142, report lr 63533 degree of protection ip 00 climatic ambient conditions see technical specifications of the s5-135u/155u cc mechanical ambient conditions see technical specifications of the s5-135u/155u cc noise immunity, electromagnetic compatibility (emc) see technical specifications of the s5-135u/155u cc supply voltage 5 v  5 % current consumption at 5 v 0.5 a typical backup voltage 3.4 v backup current 20  a typical (at 25  c) p area o area im3 area im4 area total digital inputs with process image digital inputs without process image or analog inputs 1024 max. 1024 max. 64 max. 2048 max. 128 max. 2048 max. 128 max. 2048 max. 128 max. 1024 max. 7168 max. 448 max. digital outputs with process image digital outputs without process image or analog outputs 1024 max. 1024 max. 64 max. 2048 max. 128 max. 2048 max. 128 max. 2048 max. 128 max. 1024 max. 7168 max. 448 max. flags 2048 timers 256 counters 256 size of user memory max. of 64 x 2 10 words, ram db ram 46 x 2 10 bytes transmission rate of serial pg interface 9600 bps program blocks pb 256 sequence blocks sb 256 function blocks fb 256 function blocks fx 256 data blocks db 256, of which 253 are freely available data blocks dx 256, of which 253 are freely available organization blocks ob ob 1 to 39 (interfaces for operating system) integrated special function organization blocks ob see pocket guide dimensions (w x h x d) 20.32 x 233.4 x 160 mm weight approx. 0.6 kg cpus, memor y cards, memor y submodules, interface submodules
5-62 system manual c79000-g8576-c199-07 5.6 cpu 928 this section contains the hardware description and technical specifications of the cpu 928. details on programming the cpu 928 can be found in the cpu 928 programming guide. 5.6.1 technical description you can use the cpu 928 in single and multiprocessor operation in the s5-135u/155u central controller (see chapter 6). up to four cpus can be used. the cpu 928 is universally applicable, ensuring both very fast bit processing (optimized for open-loop tasks) and word processing (optimized for closed-loop tasks). the following program processing levels are possible:  cyclical  time-controlled (9 different timebases)  interrupt-driven (hardware interrupt) the programming language is step 5. the cpu 928 comprises two pcbs (pcb 1 and pcb 2) in the double eurocard format, in a sandwich assembly. the two pcbs have plug-in interconnections and are bolted together as a unit when delivered. pcb 2 serves as the basic board which provides the connection to the s5 bus via two backplane connectors. the front plate width is 2 2/3 standard plug-in stations. application design cpus, memor y cards, memor y submodules, interface submodules
5-63 system manual c79000-g8576-c199-07 you require a user memory submodule (ram or eprom) for storage of your program. you can store up to 64 x 2 10 bytes of code and data blocks here. for data blocks, the cpu 928 additionally has an integrated db ram of 46 x 2 10 bytes. note the db ram is loaded with db/dx blocks when the ram submodule is full or an eprom submodule is plugged in. a description of the memory submodules can be found in sections 5.9 and 5.10; order numbers are given in the ordering information. there is an interrupt line (ir) in the plc for each cpu. it can be used when the reaction to one or more events must occur with higher priority than the reaction to other events. to process an interrupt, cyclic program processing is interrupted and the program stored in ob 2 (ob for interrupt processing) is inserted. (refer to the cpu 928 programming guide for further details.) this interrupt-driven program processing is only possible using an interrupt-capable digital input module (e.g. 6es5 432-...) or a cp/ip module which operates in this way. user memory process interrupt processing cpus, memor y cards, memor y submodules, interface submodules
5-64 system manual c79000-g8576-c199-07 5.6.2 installation and startup ! caution switch off the power supply before removing or inserting the module. the basic board and expansion board of the cpu 928 are one unit and must not be separated. proceed as follows to insert the cpu in the central controller: step action 1 release the upper locking bar of the central controller and ensure that the locking pin for the module is correctly positioned with the slot-head horizontal. 2 select the correct slot (based on the labelling of the locking bar). insert the cpus in the s5-135u/155u from slot 11. 3 push the module evenly into the guide rail until the lever over the locking pin is horizontal. 4 press the locking pin inwards on the bottom of the module and rotate it 90 o clockwise. 5 secure the upper locking bar. proceed as follows to remove the cpu: step action 1 release the upper locking bar of the central controller. 2 release the locking pin of the module. 3 press the release lever downwards and pull the module forwards and out of the central controller. removing and inserting the module insertion removal cpus, memor y cards, memor y submodules, interface submodules
5-65 system manual c79000-g8576-c199-07 the controls and indicators are arranged on the front plate of the cpu module: siemens receptacle for user memory submodule mode switch led (green) led (red) momentary-contact mode switch fault indicator leds (red) pg interface, 15-pin release lever locking pin run stop run stop rcksetzen reset url?schen overall reset qvz adf zyk basp order number and version 6es5928-3ua12 figure 5-8 front plate of the cpu 928 controls and indicators cpus, memor y cards, memor y submodules, interface submodules
5-66 system manual c79000-g8576-c199-07 the mode switch has two settings: in the run setting, the cpu 928 processes the user program when the green run led is lit. the cpu 928 goes to the stop state when you switch from run to stop. the red stop led then lights up. you can initiate the overall reset, reset and restart functions with the momentary-contact mode switch: momentary-contact switch down with an overall reset, all ram areas are erased and initialized (both on the cpu and on a ram submodule). momentary-contact switch up during a reset, all flags, timers, counters and the process image will be erased. ob 20 will be invoked. processing of the user program will start from the beginning again. momentary-contact switch at midpoint with a restart, processing of the user program will continue from the point of interruption. the statuses of flags, timers, counters and the process image are retained during stoppage of the cpu. mode switch run stop momentary- contact mode switch overall reset reset restart cpus, memor y cards, memor y submodules, interface submodules
5-67 system manual c79000-g8576-c199-07 run led stop led status on off the cpu is in the run state. off on the cpu is in the stop state. after a stop request by switch or pg function, the stop led is continuously lit because the transition to the stop state was requested by the user or, in multiprocessor operation, by another cpu, and was not caused by the cpu itself. off off the cpu is in the initial start or program check state. off slow flashing the cpu is in the stop state. the cpu has caused a transition to the stop state (possibly also for the other cpus). if you set the mode switch to stop, the flashing led becomes continuously lit. off rapid flashing the cpu is in the stop state. an overall reset has been requested. this request can be initiated by the cpu itself or by operator action. status indicators cpus, memor y cards, memor y submodules, interface submodules
5-68 system manual c79000-g8576-c199-07 qvz led on during direct access or process image update, a module addressed by the program no longer acknowledges although  either it has acknowledged in single processor operation upon reset of the cpu 928 in the area of the process image (ib 0 to 127, qb 0 to 127) and has been entered as present in the a9th tracko (see programming guide, cpu 928), it h b t d i db 1 ( dd li t) i  or it has been entered in db 1 (address list) in multiprocessor or single-processor operation and has been recognized as present during the reset. possible causes  module failure.  module was pulled out during operation, in the stop state or in the off state without a subsequent reset. adf led on the user program has referenced an i/o address under which no module is inserted. zyk led on the maximum cycle time has been exceeded. basp led on command output is inhibited and the digital outputs will be directly switched to the safe state. a detailed description of interrupt and error handling can be found in the cpu 928 programming guide. leds for fault indication and signaling cpus, memor y cards, memor y submodules, interface submodules
5-69 system manual c79000-g8576-c199-07 the modules must be inserted at the correct slots in the central controller. the backup battery must be fitted and in order for the cpu to start. step action result 1 set the mode switch to stop 2 switch the system voltage on. the following leds must light up on the cpu: red stop led (flashing rapidly) red basp led 3 hold the operating mode switch in the overall reset setting and simultaneously set the mode switch from stop to run. the red stop led is now permanently lit. step action result 1 set the mode switch to stop. 2 hold the mc switch in the reset setting and simultaneously set the mode switch from stop to run. red stop led goes off green run led lights up red basp led goes off the cpu is now in the run state but still has no user program. you can also carry out a manual restart of the cpu 928 with the mode switch. the cpu 928 programming guide will indicate when a manual restart is permissible. step action result 1 set the mode switch from stop to run. red stop led goes off green run led lights up red basp led goes off for maintenance purposes or in the event of a fault, this startup without user program in single-processor operation can serve to establish whether the cpu is operating without errors. startup overall reset reset restart cpus, memor y cards, memor y submodules, interface submodules
5-70 system manual c79000-g8576-c199-07 5.6.3 technical specifications important for the usa and canada the following approvals have been obtained:  ul listing mark underwriters laboratories (ul) to standard ul 508, report e 85972  csa certification mark canadian standard association (csa) to standard c 22.2 no. 142, report lr 63533 degree of protection ip 00 climatic ambient conditions see technical specifications of the s5-135u/155u cc mechanical ambient conditions see technical specifications of the s5-135u/155u cc noise immunity, electromagnetic compatibility (emc) see technical specifications of the s5-135u/155u cc supply voltage 5 v  5 % current consumption at 5 v 3.5 a typical backup voltage 3.4 v backup current without user ram submodule 20  a typical (at 25  c) p area o area im3 area im4 area total digital inputs with process image digital inputs without process image or analog inputs 1024 max. 1024 max. 64 max. 2048 max. 128 max. 2048 max. 128 max. 2048 max. 128 max. 1024 max. 7168 max. 448 max. digital outputs with process image digital outputs without process image or analog outputs 1024 max. 1024 max. 64 max. 2048 max. 128 max. 2048 max. 128 max. 2048 max. 128 max. 1024 max. 7168 max. 448 max. flags 2048 timers 256 counters 256 size of user memory max. of 64 x 2 10 words, eprom or ram db ram 46 x 2 10 bytes transmission rate of serial pg interface 9600 bps program blocks pb 256 sequence blocks sb 256 function blocks fb 256 function blocks fx 256 data blocks db 256, of which 253 are freely available data blocks dx 256, of which 253 are freely available organization blocks ob ob 1 to 39 (interfaces for operating system) integrated special function organization blocks ob see pocket guide dimensions (w x h x d) 40.64 x 233.4 x 160 mm weight approx. 1 kg cpus, memor y cards, memor y submodules, interface submodules
5-71 system manual c79000-g8576-c199-07 5.7 cpu 922 this section contains the hardware description and technical specifications of the cpu 922 (also known as the r processor). details on programming can be found in the cpu 922 programming guide. 5.7.1 technical description you can use the cpu 922 in single and multiprocessor operation in the s5-135u/155u cc (see chapter 6). up to four cpus can be used. the cpu 922 is particularly suitable for word processing (closed-loop control and arithmetic calculation). binary signal processing is also possible. the following program processing levels are possible:  cyclic  time-controlled (1 timebase)  interrupt-driven (hardware interrupt). the programming language is step 5. the module is designed as a plug-in pcb of double eurocard format. the module provides the connection to the s5 bus via two backplane connectors. the front plate width is 1 1/3 standard plug-in stations. application design cpus, memor y cards, memor y submodules, interface submodules
5-72 system manual c79000-g8576-c199-07 you require a user memory submodule (ram or eprom) for storage of your program. you can store up to 64 x 2 10 bytes of code and data blocks here. for data blocks, the cpu 922 additionally has an integrated db ram of 22 x 2 10 bytes. note the db ram is only loaded with db/dx blocks when the ram submodule is full or an eprom submodule is inserted. a description of the memory submodules can be found in sections 5.9 and 5.10; order numbers are given in the ordering information. there is an interrupt line (ir) in the s5-135u/155u plc for each cpu. it can be used when the reaction to one or more events must occur with higher priority than the reaction to other events. to process an interrupt, cyclic program processing is interrupted and the program stored in ob 2 is inserted. refer to the cpu 922 programming guide for further details. this interrupt-driven program processing is only possible using an interrupt-capable digital input module (e.g. 6es5 432-...) or a suitably operating cp/ip module. user memory process interrupt processing cpus, memor y cards, memor y submodules, interface submodules
5-73 system manual c79000-g8576-c199-07 5.7.2 installation and startup ! caution switch off the power supply before removing or inserting the module. proceed as follows to insert the cpu in the central controller: step action 1 release the upper locking bar of the central controller. 2 select the correct slot (based on the labelling of the locking bar). insert the cpus in the s5-135u/155u from slot 11. 3 push the module evenly into the guide rail. 4 secure the upper locking bar. proceed as follows to remove the cpu: step action 1 release the upper locking bar of the central controller. 2 use the grips and gentle upward and downward motion to pull the cpu forwards out of the cc. removing and inserting the module insertion removal cpus, memor y cards, memor y submodules, interface submodules
5-74 system manual c79000-g8576-c199-07 the controls and indicators are arranged on the front plate of the cpu module: siemens receptacle for user memory submodule mode switch led (green) led (red) momentary-contact mode switch fault indicator leds (red) pg interface, 15-pin run stop run reset stop rcksetzen url?schen overall reset qvz adf zyk basp order number and version grip grip 6es5922-3ua11 figure 5-9 front plate of the cpu 922 controls and indicators cpus, memor y cards, memor y submodules, interface submodules
5-75 system manual c79000-g8576-c199-07 the mode switch has two settings: in the run setting, the cpu 922 processes the user program when the green run led is lit. the cpu 922 goes to the stop state when you switch from run to stop. the red stop led then lights up. you can initiate the overall reset, reset and restart functions with the momentary-contact mode switch: momentary-contact switch down with an overall reset, all ram areas are erased and initialized (both on the cpu and on a ram submodule). momentary-contact switch up during a reset, all flags, timers, counters and the process image will be erased. ob 20 will be invoked. processing of the user program will start from the beginning again. momentary-contact switch at midpoint with a restart, processing of the user program will continue from the point of interruption. the statuses of flags, timers, counters and the process image are retained during stoppage of the cpu. mode switch run stop momentary- contact mode switch overall reset reset restart cpus, memor y cards, memor y submodules, interface submodules
5-76 system manual c79000-g8576-c199-07 run led stop led status on off the cpu is in the run state. off on the cpu is in the stop state. after a stop request by switch or pg function, the stop led is continuously lit because the transition to the stop state was requested by the user or, in multiprocessor operation, by another cpu, and was not caused by the cpu itself. off off the cpu is in the initial start or program check state. off slow flashing the cpu is in the stop state. the cpu has caused a transition to the stop state (possibly also for the other cpus). if you set the mode switch to stop, the flashing led becomes continuously lit. off rapid flashing the cpu is in the stop state. an overall reset has been requested. this request can be initiated by the cpu itself or by operator action. status indicators cpus, memor y cards, memor y submodules, interface submodules
5-77 system manual c79000-g8576-c199-07 qvz led on during direct access or process image update, a module addressed by the program no longer acknowledges although  either it has acknowledged in single processor operation upon reset of the cpu 922 in the area of the process image (ib 0 to 127, qb 0 to 127) and has been entered as present in the a9th tracko (see programming guide, cpu 922), it h b t d i db 1 ( dd li t) i  or it has been entered in db 1 (address list) in multiprocessor or single-processor operation and has been recognized as present during the reset. possible causes  module failure.  module was pulled out during operation, in the stop state or in the off state without a subsequent reset. adf led on the user program has referenced an i/o address under which no module is inserted. zyk led on the maximum cycle time has been exceeded. basp led on command output is inhibited and the digital outputs will be directly switched to the safe state. a detailed description of interrupt and error handling can be found in the cpu 922 programming guide. leds for fault indication and signaling cpus, memor y cards, memor y submodules, interface submodules
5-78 system manual c79000-g8576-c199-07 the modules must be inserted at the correct slots in the central controller. the backup battery must be fitted and in order for the cpu to start. step action result 1 set the mode switch to stop 2 switch the system voltage on. the following leds must light up on the cpu: red stop led (flashing rapidly) red basp led 3 hold the mc 1) switch in the overall reset setting and simultaneously set the mode switch from stop to run. the red stop led is now permanently lit. 1) mc: momentary-contact step action result 1 set the mode switch to stop. 2 hold the mc switch in the reset setting and simultaneously set the mode switch from stop to run. red stop led goes off green run led lights up red basp led goes off the cpu is now in the run state but still has no user program. you can also carry out a manual restart of the cpu 922 with the mode switch. the cpu 922 programming guide will indicate when a manual restart is permissible. step action result 1 set the mode switch from stop to run. red stop led goes off green run led lights up red basp led goes off for maintenance purposes or in the event of a fault, this startup without user program in single-processor operation can serve to establish whether the cpu is operating without errors. startup overall reset reset restart cpus, memor y cards, memor y submodules, interface submodules
5-79 system manual c79000-g8576-c199-07 5.7.3 technical specifications important for the usa and canada the following approvals have been obtained:  ul listing mark underwriters laboratories (ul) to standard ul 508, report e 85972  csa certification mark canadian standard association (csa) to standard c 22.2 no. 142, report lr 63533 degree of protection ip 00 climatic ambient conditions see technical specifications of the s5-135u/155u cc mechanical ambient conditions see technical specifications of the s5-135u/155u cc noise immunity, electromagnetic compatibility (emc) see technical specifications of the s5-135u/155u cc supply voltage 5 v  5 % current consumption at 5 v 2.2 a typical backup voltage 3.4 v backup current without user ram submodule 20  a typical (at 25  c) p area o area im3 area im4 area total digital inputs with process image digital inputs without process image or analog inputs 1024 max. 1024 max. 64 max. 2048 max. 128 max. 2048 max. 128 max. 2048 max. 128 max. 1024 max. 7168 max. 448 max. digital outputs with process image digital outputs without process image or analog outputs 1024 max. 1024 max. 64 max. 2048 max. 128 max. 2048 max. 128 max. 2048 max. 128 max. 1024 max. 7168 max. 448 max. flags 2048 timers 128 counters 128 size of user memory max. of 64 x 2 10 words, eprom or ram db ram 22 x 2 10 bytes transmission rate of serial pg interface 9600 bps program blocks pb 256 sequence blocks sb 256 function blocks fb 256 function blocks fx 256 data blocks db 256, of which 253 are freely available data blocks dx 256, of which 253 are freely available organization blocks ob ob 1 to 39 (interfaces for operating system) integrated special function organization blocks ob see pocket guide dimensions (w x h x d) 20.32 x 233.4 x 160 mm weight approx. 0.5 kg cpus, memor y cards, memor y submodules, interface submodules
5-80 system manual c79000-g8576-c199-07 5.8 374 flash eprom cards this section provides a summary  of the use of the 374 flash eprom cards (known as the 374 memory cards in the following) in the cpu 948, cpu 928b-3ub21 and cpu 928-3ua21  and of the technical specifications. 5.8.1 technical description the 374 memory card serves as a storage medium for user programs and user data. it contains electrically erasable flash eproms. the 374 memory card is available in the following capacities:  256 kbytes  512 kbytes  1024 kbytes  2048 kbytes  4096 kbytes the order numbers for the simatic s5 memory cards can be found in the ordering information. 5.8.2 notes on operation you can program and erase the 374 memory card off-line on the simatic s5 programmers. the link to the pg is provided by a special connector or programming adapter, into which the memory card is inserted. a description of eprom programming can be found in the step 5 manual. memory cards can be inserted and removed at any time, even whilst the cpu is running, as long as they are not being accessed (see the cpu 948 programming guide). the contents of the memory cards are only copied automatically into the internal ram of the cpu upon overall reset of the cpu. memory cards are electrically erasable. ordering information programming a memory card inserting and removing a memory card loading data erasing a memory card cpus, memor y cards, memor y submodules, interface submodules
5-81 system manual c79000-g8576-c199-07 5.8.3 technical specifications important for the usa and canada the following approvals have been obtained:  ul listing mark underwriters laboratories (ul) to standard ul 508, report e 85972  csa certification mark canadian standard association (csa) to standard c 22.2 no. 142, report lr 63533 supply voltage during a read operation +5 v  5 % current consumption during a read operation (at 5 v) 200 ma max. access time t acc 200 ns operating temperature 0 to 55 5 c storage temperature - 40 5 c to 70 5 c relative humidity up to 95 % at 25 5 c, no condensation number of programming cycles 10,000 dimensions (h x d x w) 54 x 85 x 5 mm weight approx. 50 g cpus, memor y cards, memor y submodules, interface submodules
5-82 system manual c79000-g8576-c199-07 5.9 376 memory submodules this section provides a summary  of the use of the 376 memory submodules in the 928b (up to -3ub12), 928 (up to -3ua12) and 922 cpus,  and of the technical specifications. note you cannot use the memory submodule 376 for the cpu 928b from version 3ub21, nor for the cpu 928 from version 3ua21. 5.9.1 technical description the 376 memory submodules serve as a storage medium for user programs and user data. they contain uv-erasable cmos eproms. 376 memory submodules are available in the following capacities:  16 kbytes  32 kbytes  64 kbytes the order numbers for the simatic s5 memory submodules can be found in the ordering information. 5.9.2 notes on operation you program the 376 memory submodules off-line on the simatic s5 programmers. the link to the pg is provided by the eprom programming interface integrated in the pg. a description of eprom programming can be found in the step 5 manual. use an adhesive label to cover the eprom window (erasing window) after programming. ! caution cmos memory submodules are destroyed by programming with the wrong programming number. a list of valid order numbers (mlfbs) and programming numbers can be found in your step 5 software in the eprom package. before inserting a 376 memory submodule in the module receptacle of the cpu,  set the cpu mode switch to stop  and switch off the plc (power off). 376 memory submodules can be erased with a uv eraser. before erasing, remove the plastic cover and the adhesive label from the erasing window. ordering information programming the memory submodules inserting a memory submodule erasing a memory submodule cpus, memor y cards, memor y submodules, interface submodules
5-83 system manual c79000-g8576-c199-07 5.9.3 technical specifications important for the usa and canada the following approvals have been obtained:  ul listing mark underwriters laboratories (ul) to standard ul 508, report e 85972  csa certification mark canadian standard association (csa) to standard c 22.2 no. 142, report lr 63533 supply voltage during a read operation +5 v  5 % current consumption during a read operation (at 5 v) 200 ma max. access time t acc 250 ns operating temperature 0 to 55 5 c storage temperature - 40 5 c to 70 5 c relative humidity up to 95 % at 25 5 c, no condensation number of programming cycles 10,000 dimensions (h x d x w) 54 x 58 x 14 mm weight approx. 40 g cpus, memor y cards, memor y submodules, interface submodules
5-84 system manual c79000-g8576-c199-07 5.10 377 memory submodules this section provides a summary  of the use of the 377 memory submodules in the 928b (up to -3ub12), 928 (up to -3ua12) and 922 cpus,  and of the technical specifications. note you cannot use the memory submodule 377 for the cpu 928b from version 3ub21, nor for the cpu 928 from version 3ua21. 5.10.1 technical description 377 memory submodules (ram submodules) are available with or without battery backup in the following capacities: without battery backup with battery backup 16 kbytes 64 kbytes 32 kbytes 64 kbytes the order numbers for the 377 memory submodules can be found in the ordering information. 5.10.2 notes on operation 377 memory submodules are loaded online (from the pg) in the cpu. a description of loading the individual submodules or the entire program can be found in the step 5 manual. loading ram submodules cpus, memor y cards, memor y submodules, interface submodules
5-85 system manual c79000-g8576-c199-07 5.10.3 ram submodules with battery backup ram submodules with battery backup are used when the contents of the memory submodules must be retained even outside the cpu. you can then remove the battery-backed 377 memory submodule from the cpu without loss of data. an integral battery protects the submodule from data loss, and ensures that the data will be retained until the ram submodule is used again. note the ram submodule with battery backup is not a substitute for an eprom submodule. the contents can be overwritten by a step 5 program. the battery can discharge if the submodule is at standby for a long time. this can result in the loss of data. to protect the battery, the 377 memory submodule has a cover on both sides. the button cell battery with terminal lugs is secured on the submodule with screws on two holders. when the grip is swivelled in, you can see the battery fault led. there are three different operational states for the ram submodule with battery backup: in this state  the battery-backed ram submodule is in the cpu;  the programmable controller (plc) is switched on (power on);  and neither the backup battery of the plc nor the battery of the ram submodule is supplying power. note the ram submodule must not be inserted or removed during the run state; this can result in data corruption, loss of data or cpu malfunctions. operational states normal operation cpus, memor y cards, memor y submodules, interface submodules
5-86 system manual c79000-g8576-c199-07 in this standby state of the unit  the battery-backed ram submodule is in the cpu;  the plc is switched off (power off);  the backup battery of the plc is providing backup of the ram submodule;  the submodule battery is not supplying power. note it is only possible to insert and remove the ram submodule in this state without data corruption. if the backup battery in the plc fails in this state, the submodule battery provides backup of the ram submodule. this prevents loss of data. in this standby state of the submodule  the ram submodule has been removed from the cpu;  the submodule battery is providing backup of the ram submodule;  the contents of the battery-backed ram are retained. the battery of the battery-backed ram submodule is monitored. when the ram submodule goes to normal operation (battery-backed ram is in the cpu, supply voltage of the plc is switched on), the battery monitor on the submodule detects the following faults:  submodule battery is not present.  submodule battery is faulty (voltage less than 2.6 v). the red battery fault led on the front of the submodule is continuously lit. note a temporary voltage drop of the submodule battery in the standby state, for example, caused by storage below 0 o c or a battery change, is not detected by the battery monitor if the voltage dip is corrected by plugging in the ram submodule and switching on the plc. however, the voltage dip may have led to a loss or corruption of ram submodule data. standby operation submodule standby battery monitoring and battery fault cpus, memor y cards, memor y submodules, interface submodules
5-87 system manual c79000-g8576-c199-07 before the ram submodule with battery backup is started for the first time, you must insert the battery provided. this is delivered separately to protect it from premature discharge. proceed according to the following steps: step action 1 open the upper side of the cover by releasing the snap-on catch. grasp the cover within the clearance from the pcb and pull it up. 2 insert the submodule battery and secure it with a screw on the left and on the right. ensure correct polarity (+/-). 3 close the cover again. battery m 2.5 screw grip battery fault led figure 5-10 mounting location for backup battery ! caution improper replacement of the battery can result in explosion hazard. it should only be replaced by the same type or an equivalent one recommended by the manufacturer. used batteries should be disposed of according to the manufacturer's instructions. inserting or replacing the backup battery cpus, memor y cards, memor y submodules, interface submodules
5-88 system manual c79000-g8576-c199-07 proceed as follows to replace the submodule battery: step action 1 open the upper side of the cover by releasing the snap-on catch. 2 slacken the screws on the left and right of the battery. 3 replace the submodule battery and secure the new battery with screws, observing the polarity. 4 close the cover again. ! caution eprom-battery-backed ram submodules must not be programmed via the eprom interface of the pg, otherwise they can be destroyed. before inserting or removing the ram submodule into or out of the cpu, switch the plc power supply off: this is to ensure that data of the ram submodule are not corrupted. initial situation:  the cpu is in the programmable controller.  the power supply of the plc is switched off.  the mode switch of the cpu is at stop. step action 1 first insert the battery in the ram submodule. 2 insert the ram submodule in the cpu. 3 switch the power supply of the programmable controller on. 4 carry out an overall reset. 5 connect your programmer (pg) to the cpu. 6 when the user program has been loaded into the ram submodule, reset the cpu. using the ram submodule with battery backup inserting unprogrammed memory submodules cpus, memor y cards, memor y submodules, interface submodules
5-89 system manual c79000-g8576-c199-07 since the contents of the inserted ram submodule are erased with each overall reset, proceed as follows when using programmed ram submodules whose contents are not to be erased: initial situation:  the cpu is in the programmable controller.  the power supply of the plc is switched off.  the mode switch of the cpu is at stop. step action 1 insert another, unprogrammed memory submodule in the cpu. 2 switch the power supply on. 3 carry out an overall reset. 4 switch the power supply off. 5 remove the unprogrammed memory submodule. 6 insert the programmed memory submodule. 7 switch the power supply on. 8 carry out a reset. before removing the ram submodule, check whether the battery is still in order: if the battery fault led on the ram submodule is lit whilst the plc supply voltage is switched on, the contents of the ram submodule will be lost when it is removed. initial situation:  the cpu is in the run state. step action 1 set the cpu mode switch to stop. 2 switch the power supply off. 3 remove the memory submodule. inserting programmed memory submodules removing memory submodules cpus, memor y cards, memor y submodules, interface submodules
5-90 system manual c79000-g8576-c199-07 5.10.4 technical specifications important for the usa and canada the following approvals have been obtained:  ul listing mark underwriters laboratories (ul) to standard ul 508, report e 85972  csa certification mark canadian standard association (csa) to standard c 22.2 no. 142, report lr 63533 supply voltage +5 v  5 % operating temperature 0 to 55 5 c storage temperature - 40 5 c to 70 5 c relative humidity up to 95 % at 25 5 c, no condensation number of programming cycles 10,000 dimensions (h x d x w) 54 x 58 x 14 mm weight approx. 40 g / 60 g current consumption (at 5 v) 100 ma max. (16/64 kbytes) 200 ma max. (32 kbytes) backup current/standby approx. 20  a typ. (16/64 kbytes) approx. 40  a typ. (32 kbytes) backup voltage/ ucmos 2.7 v to 3.6 v access time t acc 150 ns (16/64 kbytes) 200 ns (32 kbytes) all 377 memory submodules submodules without battery backup cpus, memor y cards, memor y submodules, interface submodules
5-91 system manual c79000-g8576-c199-07 current consumption (at 5 v) 140 ma max. backup current 13  a typ. backup voltage/ ucmos 2.7 v to 3.6 v submodule battery lithium button cell 3 v/200 mah type cr 2430 (lf-1/2w) from varta backup time 1 year min. at 25 o c access time t acc 150 ns submodules with battery backup cpus, memor y cards, memor y submodules, interface submodules
5-92 system manual c79000-g8576-c199-07 5.11 interface submodules the second serial interface of the cpu 928b can be optionally used as:  a pg interface (for pg and operator panels)  an interface for the rk 512 computer link  an interface for data transmission with procedures 3964/3964r  an interface for data transmission with the aopen drivero  an interface for data transmission via the sinec l1 bus (from version 6es5 928-3ub12) the second serial interface of the cpu 948 can be used as:  a pg interface (for pg and operator panels) to use the second interface as ... ... you require ... a pg interface the pg submodule an interface for data transmission with rk 512 computer link, procedures 3964/3964r or aopen drivero the v.24 (rs 232c) or tty or rs 422 a/485 submodule (only in rs 422 a mode) an interface for data transmission via the sinec l1 bus the sinec l1 submodule using the interface submodules cpus, memor y cards, memor y submodules, interface submodules
5-93 system manual c79000-g8576-c199-07 5.11.1 installing and removing the interface submodules to use an interface submodule, you must first install it in the cpu (outside the central controller). ! caution switch off the power supply of the programmable controller before removing the cpu. install your interface submodule in the following steps: step action 1 check the jumper settings of your interface submodule: pg submodule see section 5.11.2 v.24 submodule see section 5.11.3 tty submodule see section 5.11.4 rs422 a/485 submodule see section 5.11.5 sinec l1 submodule see section 5.11.6. when the interface submodule is delivered, the jumpers are already set so that you can usually fit it immediately. 2 switch off the power supply of your plc. 3 remove the cpu. 4 remove both screws on the submodule slot. 5 remove the coverplate. 6 insert the interface submodule through the front plate into the plug-in connector (components in the same direction as the cpu). 7 secure the submodule with the two screws (see step 4). 8 insert the cpu in the central rack. 9 switch on the power supply of your plc again. installation cpus, memor y cards, memor y submodules, interface submodules
5-94 system manual c79000-g8576-c199-07 remove your interface submodule in the following steps: step action 1 switch off the power supply of your plc. 2 remove the cpu from the central controller. 3 slacken the two locking screws of the submodule and pull it out of the receptacle. 4 fit another submodule (as already described) or close the receptacle with its cover. use the fixing screws of the submodule. 5 insert the cpu in the central controller. 6 switch the power supply of your plc on again. note since the interface module is secured to the cpu with screws, interference pulses are given a path to ground via the shield of the cpu. removal cpus, memor y cards, memor y submodules, interface submodules
5-95 system manual c79000-g8576-c199-07 5.11.2 pg submodule by means of the pg submodule, you can use the second interface of the cpu as an equally privileged pg interface. the pg submodule can be inserted in the following cpus: interface submodule for use with pg submodule cpu 928b cpu 948 the pg submodule is equipped with a transmitter and a receiver for 20 ma current loop signals. the loop current is always fed in from the pg. the following figure shows the circuitry for current loop signals of the standard cable: transmitter + + receiver current direction arrows cpu with pg + receiver + transmitter pg module + + figure 5-11 pg submodule: loop current direction the rate for data transmission via the pg interface is always 9600 bps. application circuitry data transmission rate cpus, memor y cards, memor y submodules, interface submodules
5-96 system manual c79000-g8576-c199-07 given in the following table are the pin assignments of the 15-pin subminiature d-type connector in the front plate of the pg submodule: pin designation current direction remarks 1 housing/gnd/gnd ext 2 - rxd  8 15 3 vpg + 5 v_ 15 4 + 24 v from bus 5 0 v gnd/gnd int 6 + txd  7 - txd  9 8 housing/gnd/gnd ext 9 1 9 + rxd  10 24 v gnd  current return 11 20 ma  current source, transmitter 12 gnd/gnd int 13 20 ma  current source, receiver 14 vpg + 5 v_ 15 0 v gnd/gnd int  : from partner to cpu  : from cpu to partner pin assignments of the pg submodule cpus, memor y cards, memor y submodules, interface submodules
5-97 system manual c79000-g8576-c199-07 when the pg submodule is delivered, the jumpers are set as shown in the following figure. as a rule, therefore, you can use the pg submodule immediately. backplane connector front connector 15-pin sub. d-type j1 3 2 1 figure 5-12 pg submodule: jumper settings when delivered j1 is set to select whether the pg submodule is to be operated in the cpu 928b/cpu 948 or in the cpu 945: 123 j1 operation in cpu 928b/cpu 948 operation in cpu 945 jumper settings on the pg submodule cpus, memor y cards, memor y submodules, interface submodules
5-98 system manual c79000-g8576-c199-07 standard cables for connecting the pg submodule in the cpu to the pg are available from siemens in various lengths, up to 1000 m. order numbers and lengths can be found in the ordering information. connecting cable: cpu - pg housing, gnd 1 shield housing, gnd 8 24 25 9 2 + rxd rxd receiver 10 22 + txd 6 12 23 12v transmitter 20 6 +12v txd transmitter 7 8 21 receiver 12v +12v 17 4 3 2 + 20 ma + txd txd 20 ma + 20 ma + rxd rxd 20 ma k1 k2 k3 transmission rate setting cpu si1 or si2 with pg submodule pg 675/685 or adapter to pg 7xx figure 5-13 pg submodule: standard connecting cable standard connecting cable for the pb submodule cpus, memor y cards, memor y submodules, interface submodules
5-99 system manual c79000-g8576-c199-07 5.11.3 v.24 submodule the v.24 submodule is used with the rk 512 computer link, data transmission with procedures 3964/3964r, data transmission with the aopen driver.o the v.24 submodule can be inserted in the following cpu: interface submodule... for use with ... v.24 submodule cpu 928b cpu 948 cp 524 cp 544 the following figure shows the circuitry for the v.24 interface (transmit and receive lines): device 1 gnd txd rxd shield device 2 gnd txd rxd shield figure 5-14 v.24 interface apart from the transmit and receive lines, the v.24 submodule has a number of control and signaling lines to ccitt recommendation v.24/v.28. however, these control signals are not needed and not used for the standard procedures of communication types rk 512, 3964/3964r and aopen driver.o (exception: rts/cts with the aopen drivero). the following applies to v.24 signals: logic 0 is represented by a voltage u  + 3 v logic 1 is represented by a voltage u  3 v if you fabricate the connecting cables yourself, note that unused inputs at the partner station may have to be connected to quiescent potential. further details can be found in the appropriate manuals and in ccitt recommendations v.24/v.28. application circuitry cpus, memor y cards, memor y submodules, interface submodules
5-100 system manual c79000-g8576-c199-07 a maximum of 19200 bps is permissible for data transmission with the v.24 submodule. the following table shows the pin assignments of the 25-pin subminiature d-type connector in the front plate of the v.24 submodule: pin des. to din 66020 des. to ccitt v.24 intern abbreviation input/ output remarks 25 13 1 shield 25 2 d1 103 txd output 3 d2 104 rxd input 4 s2 105 rts output 5 m2 106 cts input 6 m1 107 dsr input 7 e2 102 gnd 8 m5 109 dcd input 18 ps3 141 output not supported 14 1 20 s1.2 108.2 dtr output 1 22 m2 125 ri input 23 s4 111 output 25 pm1 142 input not supported the signal numbering complies with din 66020 (v.24/rs 232c); the signal designations are the abbreviations used internationally (rs 232c). data transmission rate pin assignments of the v.24 submodule cpus, memor y cards, memor y submodules, interface submodules
5-101 system manual c79000-g8576-c199-07 when the v.24 submodule is delivered, the jumpers are set as shown in the following figure. as a rule, you can therefore use the v.24 submodule immediately. backplane connector front connector 25-pin sub. d-type j2 j1 j3 j4 br5 br6 br8 br9 br7 figure 5-15 v.24 submodule: jumper settings when delivered you can change over the polarity of the transmit and receive data with jumpers j3 and j5 . 123 j3 transmit data in normal polarity transmit data negated j5 receive data in normal polarity received data negated jumper settings of the v.24 submodule cpus, memor y cards, memor y submodules, interface submodules
5-102 system manual c79000-g8576-c199-07 with jumper j6 , you can set all v.24 receivers so that you only require positive-going signals (positive voltage region). 123 j6 all received signals must be at v.24 signal level. all received signals can be in the positive voltage region. with the submodule 0aa23, bridge 6 has no function; all signals can lie in the positive range (corresponds to bridge setting 2-3). with jumper j9 , cts can be set permanently to quiescent potential, i.e. switched through from the front connector. 123 j9 cts at quiescent potential cts at pin 5 standard cables for connecting the v.24 submodule of the cpu to the partner station are available from siemens in various lengths, up to16 m. order numbers and lengths can be found in the ordering information. connecting cable for cpu, cp 524, cp 525, cp 544 cpu, cp524/525, cp544 rxd 7 shield 2 7 txd receiver transmitter txd 2 3 rxd receiver transmitter housing, gnd housing, gnd 3 11 cpu, cp524/525, cp544 figure 5-16 v.24 submodule: connecting cable for cpu, cp 524, cp 525, cp 544 standard connecting cables of the v.24 submodule cpus, memor y cards, memor y submodules, interface submodules
5-103 system manual c79000-g8576-c199-07 connecting cable: cpu - n10 modem cpu modem n10 rxd 7 shield 3 3 7 1 txd receiver transmitter txd 2 2 rxd receiver transmitter rts cts 4 5 housing,gnd 1 figure 5-17 v.24 submodule: connecting cable for cpu - n10 modem cpus, memor y cards, memor y submodules, interface submodules
5-104 system manual c79000-g8576-c199-07 connecting cable: cpu - dr 210/211, dr 230/231 you can use this connecting cable both with the v.24 and with the tty submodule. ensure that you have the same type of interface in the cpu and in the printer. 13 14 1 10 19 7 shield 32 7 1 receiver transmitter 9 10 18 21 housing 23 receiver transmitter 525 housing, gnd cpu dr 210/211, dr 230/231 rxd txd cts txd rxd busy tty assignments tty assignments figure 5-18 v.24 submodule: connecting cable for cpu - dr 210/211, dr 230/231 cpus, memor y cards, memor y submodules, interface submodules
5-105 system manual c79000-g8576-c199-07 wiring of a connecting cable for rts/cts flow control cpu rxd 7 3 2 7 txd receiver transmitter txd 2 rxd receiver transmitter shield 1 rts cts housing, gnd 1 3 rts cts housing, gnd 4 5 4 5 cpu figure 5-19 example of a connecting cable: cpu - cpu for rts/cts flow control cpus, memor y cards, memor y submodules, interface submodules
5-106 system manual c79000-g8576-c199-07 5.11.4 tty submodule the tty submodule is for use with the rk 512 computer link, data transmission with procedures 3964/3964r, data transmission with the aopen driver.o the tty submodule complies with din 66 258, part 1. the tty submodule can be inserted in the following cpu: interface submodule ... for use with ... tty submodule cpu 928b cpu 948 cp 524 cp 544 the tty submodule is equipped with a transmitter and receiver for 20 ma current loop signals. shown in the following figure is the typical circuitry for current loop signals. current direction arrows transmitter transmitter + + + receiver receiver + + + figure 5-20 tty submodule: loop current direction the loop current can be fed in both by the tty submodule and by the partner station. only the side supplying the current is non-floating. ! caution with longer line lengths, you should arrange your line so that the transmitter always supplies the current. application circuitry cpus, memor y cards, memor y submodules, interface submodules
5-107 system manual c79000-g8576-c199-07 the tty submodule feeds in the current (20 ma) via jumpers in the connector of the standard connecting cable. the 24 v required for generation of loop current is taken from the power supply of the plc. in the quiescent state, with a correct loop current connection, there should be a flow of 20 ma (= logic 1). when the current is interrupted there is a logic 0. the following applies to the tty signals: logic 0 is represented by: no current logic 1 is represented by: current (20 ma) a maximum of 9600 bps is permissible for data transmission with the tty submodule. shown in the figure are the pin assignments of the 25-pin subminiature d-type connector in the front plate of the tty submodule: 13 pin designation current direction remarks 25 13 1 shield 9 24 v external this connection is changed over between 24 v internal and 24 v external with jumper j3 (see next page). 10 + txd  12 + 20 ma  current source, transmitter 13 + rxd  14 14 - rxd  14 1 16 + 20 ma  current source, receiver 19 - txd  21 - 20 ma  current return 24 - 20 ma  current return  : input  : output data transmission rate pin assignments of the tty submodule cpus, memor y cards, memor y submodules, interface submodules
5-108 system manual c79000-g8576-c199-07 when the tty submodule is delivered, the jumpers are set as shown in the following figure. as a rule, therefore, you can use the tty submodule immediately. backplane connector j3 j4 j2 j1 1 2 3 front connector 25-pin sub. d-type 1 2 3 figure 5-21 tty submodule: jumper settings when delivered the polarity of the transmit and receive data is changed over with jumpers j1 and j2: 123 j1 transmit data negated transmit data in normal polarity j2 receive data in normal polarity receive data negated the 24 v source voltage for generation of the loop current can be allocated with jumper j3 : 123 j3 24 v will be applied from pin 9 of the sub. d connector 24 v will be applied from the backplane connector (internally) jumper settings on the tty submodule cpus, memor y cards, memor y submodules, interface submodules
5-109 system manual c79000-g8576-c199-07 standard cables for connecting the tty submodule in the cpu to the partner station are available from siemens in various lengths, up to 1000 m. order numbers and lengths can be found in the ordering information. connecting cable for cpu, cp 524, cp 525, cp 544 cpu, cp 524/525, cp544 transmitter +24v +24v transmitter shield +rxd rxd +20ma +txd txd 13 14 21 10 19 1 +rxd rxd 20ma +txd txd 20ma 12 +20ma receiver receiver housing, gnd housing, gnd 1 19 10 12 14 13 21 cpu, cp 524/525, cp 544 figure 5-22 tty submodule: connecting cable for cpu, cp 524, cp 525, cp 544 standard connecting cables for the tty submodule cpus, memor y cards, memor y submodules, interface submodules
5-110 system manual c79000-g8576-c199-07 connecting cable: cpu - im 512 to generate loop current, the im 512 must be supplied with 24 v at the subminiature d-type connector in the front plate. shield cpu transmitter 13 receiver 14 transmitter + 24 v + 24 v im 512 12 13 23 11 24 25 device id 1 receiver 19 10 housing, gnd housing 0 14 5 2 17 6 18 15 3 2 2 + rxd rxd + txd txd + 20ma 20ma rxd + 20ma + txd txd 20ma + rxd 2 figure 5-23 tty submodule: connecting cable cpu - im 512 cpus, memor y cards, memor y submodules, interface submodules
5-111 system manual c79000-g8576-c199-07 connecting cable: cpu - dr 210/211, dr 230/231 you can use this connecting cable with both the tty and the v.24 submodule. ensure that you have the same type of interface in the cpu and in the printer. 13 14 receiver 1 transmitter +24v +24v receiver transmitter 10 19 7 shield 32 7 1 9 10 18 21 housing 23 525 housing,gnd cpu +rxd rxd +txd txd +20ma +20ma +txd +rxd v.24 assignments v.24 assignments dr 210/211, dr 230/231 figure 5-24 tty submodule: connecting cable cpu - dr 210/211, dr 230/231 cpus, memor y cards, memor y submodules, interface submodules
5-112 system manual c79000-g8576-c199-07 5.11.5 rs422 a/485 submodule the rs422 a/485 submodule is for use exclusively in the rs422 a mode with the rk 512 computer link, data transmission with procedures 3964/3964r, data transmission with the aopen driver.o the rs422 a/485 submodule can be inserted in the following cpu: interface submodule ... for use with ... rs422 a/485 submodule cpu 928b cpu 948 cp 524 cp 544 with the above types of communication, the rs422 a/485 submodule can only be used in full duplex operation implemented by hardware. the electrical characteristics are governed by eia standard rs422 a (ccitt recommendation v.11). shown in the following figure is the circuitry for the interface (transmit and receive lines): device 1 gnd device 2 gnd shield shield t(a) t(b) r(a) r(a) r(b) t(a) t(b) r(b) figure 5-25 rs422 a/485 submodule: full duplex operation apart from the transmit and receive lines, the rs422 a/485 submodule has a number of control and signaling lines to ccitt recommendation x.24 and iso 8481. in association with the above types of communication, however, these control and message signals are not required and need therefore not be wired. the rs422 a/485 is a differential voltage interface and therefore exhibits higher rejection of interference than a tty or v.24 interface. the following applies to the signals to eia standard rs422 a (v.11): logic 0 (on) corresponds to: v a > v b logic 1 (off) corresponds to: v a < v b application circuitry cpus, memor y cards, memor y submodules, interface submodules
5-113 system manual c79000-g8576-c199-07 in the rs422 a/485 submodule, the interface signals are isolated from the supply voltage of the plc. a maximum of 19200 bps is permissible for data transmission with the rs422 a/485 submodule when used in a cpu or cp 524. when the cp 544 is used, a maximum of 76800 bps is possible. shown in the following figure are the pin assignments of the 15-pin subminiature d-type connector in the front plate of the rs422 a/485 submodule: pin des. to ccitt v.24 input/ output remarks 1 shield 8 2 t(a) output 8 15 3 c(a) output 4 r(a) input/output in full duplex operation, only data can be received on this two-wire line. 5 i(a) input 9 6 s(a) input 9 1 7 b(a) output 8 gnd 9 t(b) output 10 c(b) output 11 r(b) input/output in full duplex operation, only data can be received on this two-wire line. 12 i(b) input 13 s(b) input 14 b(b) output 15 x(b) input data transmission rate pin assignments of the rs422 a/485 submodule cpus, memor y cards, memor y submodules, interface submodules
5-114 system manual c79000-g8576-c199-07 when the submodule is delivered, the jumpers are set as shown in the following figure. as a rule, therefore, you can use the rs 422 a/485 submodule immediately. front connector x4 x3 1 19 1 11 2 20 2 12 figure 5-26 rs422-a/485 submodule: jumper settings when delivered with the jumpers on the switch row x3 you can remove the preset for recognizing a break state from the two-wire line r. when delivered, the two-wire line r is preset with the jumpers 12-14 and 4-6 so that the break state can be recognized. pin 4 (r(a)) of the front connector lies above a resistance on +5 v. pin 11 (r(b)) of the front connector lies above a resistance on ground. if you replug the jumpers on 10-12 and 6-8, the two-wire line r is preset as follows: pin 4 (r(a)) of the front connector lies above a resistance on ground. pin 11 (r(b)) of the front connector lies above a resistance on +5 v. the break state cannot be recognized. jumper settings on the rs422 a/485 submodule cpus, memor y cards, memor y submodules, interface submodules
5-115 system manual c79000-g8576-c199-07 if you unplug the jumpers 12-14 and 4-6, the two-wire line r is not preset and the break state cannot be recognized clearly. with the following jumper setting you can switch over the data direction on the two-wire line r: jumper 16-18: setting for full duplex operation. data can only be received on the two-wire line r (default). jumper 18-20: setting for half duplex operation. data can be transmitted or received on the two-wire line r (special driver required). with the following jumper setting you can switch the two-wire line b as an input or an output. jumper 17-19: two-wire line b is switched as an output. the line x(b) can be used as an input. x(a) is connected to ground (default). jumper 15-17: two-wire line b is switched as an input. the line x(b) cannot be used. with the following jumper setting you can either place the signal /ps3 or the internal transmitting frequency (txcint) on the two-wire line b. the two-wire line b must be switched as an output. jumper 2-4: the signal /ps3 can be transmitted via the two-wire line b (default). jumper 4-6: the internal transmitting frequency txcint can be transmitted via the two-wire line b. cpus, memor y cards, memor y submodules, interface submodules
5-116 system manual c79000-g8576-c199-07 with the following jumper setting you can use the frequency transmitted via the two-wire line s as the receive frequency. jumper 7-9 removed: frequency on input s is not used as the receive frequency (default). jumper 7-9 plugged: frequency on input s is used as the receive frequency. with the following jumper setting you can switch the transmit and receive frequencies. jumpers 8-10, 1-3: the internal transmit frequency (txcint) is used as the transmit and receive frequency (default). jumpers 10-12, 1-3: the internal transmit frequency (txcint) is used as the transmit frequency and the internal receive frequency (rxcint) is used as the receive frequency. jumpers 8-10, 3-5: the frequency transmitted via the two-wire line s is used as the transmit and receive frequency. jumpers 10-12, 3-5: the frequency transmitted via the two-wire line s is used as the transmit frequency, the internal receive frequency (rxcint) is used as the receive frequency. with the following jumper setting you can set the submodule for synchronous transmission with frequency control according to the din draft iso 8481. the two-wire line b (identifier x to iso 8481) must be switched as an output. jumpers 1-3, 4-6, 7-9: the internal transmit frequency (txcint) is used as the transmit frequency. the internal transmit frequency is simultaneously transmitted on the two-wire line b. cpus, memor y cards, memor y submodules, interface submodules
5-117 system manual c79000-g8576-c199-07 standard cables for connecting the rs422 a/485 submodule in the cpu to the partner station are available from siemens in various lengths, up to 1200 m. the order numbers and lengths can be found in the ordering information. connecting cable for cpu, cp 524, cp 544 t(a) r(a) t(b) r(b) 2 9 4 11 r(a) t(a) r(b) t(b) gg 4 11 2 9 8 8 shield 11 housing, gnd housing, gnd receiver receiver transmitter cpu, cp 524, cp 544 transmitter gnd gnd cpu, cp 524, cp 544 figure 5-27 rs422-a/485 submodule: connecting cable for cpu, cp 524, cp 544 standard connecting cables for the rs422-a/485 submodule cpus, memor y cards, memor y submodules, interface submodules
5-118 system manual c79000-g8576-c199-07 5.11.6 sinec l1 submodule the sinec l1 submodule is for use with data transmission via the sinec l1 bus. the sinec l1 submodule can be inserted in the following cpu: interface submodule ... for use with ... sinec l1 submodule cpu 928b, from version 6es5 928-3ub12 cpu 948 the sinec l1 submodule is equipped with a transmitter and a receiver for 20 ma current loop signals. shown in the following figure is the circuitry for the current loop signals: transmitter + + receiver current direction arrows partner + receiver + transmitter cpu with sinec l1 submodule + + figure 5-28 sinec l1 submodule: loop current direction data transmission via the sinec l1 interface always takes place at 9600 bps. application circuitry data transmission rate cpus, memor y cards, memor y submodules, interface submodules
5-119 system manual c79000-g8576-c199-07 shown in the following figure are the pin assignments of the 15-pin subminiature d-type connector in the front plate of the sinec l1 submodule: pin designation current direction remarks 1 housing/gnd/gnd ext 2 rxd  8 15 3 vpg + 5 v_ 8 15 4 + 24 v from bus 5 24 v ground 6 + txd  7 txd  8 housing/gnd/gnd ext 9 1 9 + rxd  1 10 24 v ground  current return 11 20 ma  current source, transmitter 12 24 v ground 13 20 ma  current source, receiver 14 vpg + 5 v_ 15 24 v ground  : from partner to cpu  : from cpu to partner pin assignments of the sinec l1 submodules cpus, memor y cards, memor y submodules, interface submodules
5-120 system manual c79000-g8576-c199-07 when the sinec l1 submodule is delivered, the jumpers are set as shown in the following figure. as a rule, therefore, you can use the sinec l1 submodule immediately. backplane connector front connector 15-pin sub. d-type x8 x7 x10 x9 x6 1 32 figure 5-29 sinec l1 submodule: jumper settings when delivered the connection to the sinec l1 bus system is provided by the bt 777 bus terminal. a detailed description of the bus terminal can be found in the manual entitled asinec l1 bus system,o 6es5 998-7la11). the order number can be found in the ordering information. jumper settings on the sinec l1 submodule bt 777 bus terminal cpus, memor y cards, memor y submodules, interface submodules
5-121 system manual c79000-g8576-c199-07 if the cpu communicates as master in a point-to-point link with a slave, a connecting cable can be used instead of the bus terminal. shown in the following figure is connecting cable for point-to-point communication from the sinec l1 submodule in the cpu to a partner. connecting cable: cpu - partner (point-to-point communication) e.g. cpu 928b, 941...945 transmitter + 24v + 24v transmitter shield + rxd rxd + 20 ma + txd txd 9 2 6 7 1 + rxd rxd m + txd txd m 11 + 20 ma receiver receiver housing, gnd housing, gnd 1 7 6 11 2 9 15 cpu 928b cpu 102, 103, ag 90u/95u 15 figure 5-30 sinec l1 submodule: connecting cable for point-to-point communication via the sinec l1 submodule connecting cable for point-to-point communication cpus, memor y cards, memor y submodules, interface submodules
5-122 system manual c79000-g8576-c199-07 5.11.7 technical specifications of the interface submodules important for the usa and canada the following approvals have been obtained:  ul listing mark underwriters laboratories (ul) to standard ul 508, report e 85972  csa certification mark canadian standard association (csa) to standard c 22.2 no. 142, report lr 63533 degree of protection ip 00 ambient temperature in operation for transporation and storage 0 to +55 5 c 40 to +70 5 c relative humidity 95% max. at 25 5 c, no condensation supply voltage 5v  5% 24v + 25%/ 17% transmission rate pg submodule v.24 submodule tty submodule rs422-a/485 submodule sinec l1 submodule 9 600 bps fixed 19 200 bps max. 9600 bps max. 19 200 bps max. (when submodule is used in a cpu) 9600 bps fixed front connector, female pg, rs422 a/485, sinec l1 submodule v.24, tty submodule 15-pin cannon 25-pin cannon transmission cable shielded four-wire line (five-wire line for rs422 a) with braided shield and metal housing on connector, grounding required at both ends. line length pg submodule v.24 submodule tty submodule rs422 a/485 submodule sinec l1 submodule 1000 m max. 16 m max. 1000 m max. 1200 m max. 1000 m max. current consumption at 5 v/24 v 5 v 24 v pg submodule v.24 submodule tty submodule rs422 a/485 submodule sinec l1 submodule 40 ma max. 0.2 a max. 0.1 a max. 0.5 a max. 170 ma max. 380  a 60 ma 100 ma design dimensions (wxhxd) 16.3 mm x 60 mm x 102.7 mm weight per interface submodule approx. 0.1 kg cpus, memor y cards, memor y submodules, interface submodules
6-1 system manual c79000-g8576-c199-07 multiprocessor operation/coordinators this chapter explains how to install multiprocessor operation in the s5-135u/155u programmable controller and start operations. you will require the 923a or 923c coordinator module. the technical functions of these modules are described. section description page 6.1 introduction 6-2 6.2 starting the multiprocessor operation 6-3 6.3 coordinator modes 6-13 6.4 923a coordinator module 6-15 6.5 923c coordinator module 6-18 6.6 technical specifications of the coordinators 6-28 chapter overview 6
6-2 system manual c79000-g8576-c199-07 6.1 introduction the s5-135u/155u is a member of the simatic s5 family of programmable (logic) controllers. the plc can be used both in single and in multiprocessor operation with up to four cpus. you can arbitrarily combine the cpus in the central controller at the cpu slots. cpu slot requirement cpu 948/cpu 928b/cpu 928 2 slots cpu 922, 928-3ua21, 928-3ub21, 948-3ua13, 948-3ua23 1 slot in multiprocessor operation, each cpu processes its individual user program independently of the other cpus. the common s5 bus serves for data interchange with i/o modules, cps, ips and other cpus. in multiprocessor operation, access of the cpus to the s5 bus is controlled by a coordinator. the functioning of this module is described in sections 6.5 and 6.6. for an explanation of data interchange between cpus in multiprocessor operation and the arrangement of your step 5 program, please consult the programming guide for your cpu. a coordinator is required in multiprocessor operation. the following exist for the s5-135u/155u plc:  923a coordinator (cor a) (is no longer supplied) and  923c coordinator (cor c). the coordinator allocates to the cpus the time divisions in which they can access the s5 bus (bus enable time), and contains the global memory for data interchange between the cpus via communication flags. additionally, the cor c contains another memory with four pages for the amultiprocessor communicationo function as well as a serial pg interface with pg multiplexer function (pg mux). slots occupied coordinator multiprocessor operation/coordinators
6-3 system manual c79000-g8576-c199-07 6.2 starting the multiprocessor operation this section guides you through the installation and startup of multiprocessor operation; the following is assumed:  you are familiar with the use and programming of individual modules in single-processor operation. if this is not the case, please consult the relevant chapters in this manual and in the appropriate programming guides. note as soon as a coordinator is inserted in the s5-135u/155u central controller, all cpus are automatically in multiprocessor operation irrespective of the number of inserted cpus. even if the coordinator is only operated with one cpu, the conditions for multiprocessor operation apply to this cpu (db 1 required, dx 0 possibly required, etc.). you can use up to four cpus in the s5-135u/155u programmable controller. the permissible slots are indicated in chapter 4. startup can be subdivided into the following steps: step action 1 set the number of cpus (inserted from the left) on the coordinator. 2 if you use communication flags on cps: mask out the communication flag areas on the coordinator. 3 insert the cpus and the coordinator in the slots provided in the central controller. the cc must be disconnected from system voltage. 4 switch on the system voltage and power switch on the power supply unit. 5 execute an overall reset on all cpus. 6 load your step 5 user programs in all cpus (including db 1, additionally dx 0 for the cpu 948). 7 execute a reset on all cpus. 8 set the mode switch of the coordinator from the stop to run or test setting. procedure, overview multiprocessor operation/coordinators
6-4 system manual c79000-g8576-c199-07 shown in figures 6-1 and 6-2 are the locations of jumpers and switches on the modules, at which the settings required for startup must be made. note the settings of jumpers which are not described in the following text must not be changed . x1 x2 ep 2 ep 7 ep 63 ep 62 ep 43 ep 45 j2 j1 mode switch (run,stop,test) 16 9 8 1 16 9 8 1 1 16 9 8 16 9 8 1 16 9 8 1 8 16 9 1 figure 6-1 location of jumpers on the 923a coordinator (as supplied) (is no longer supplied) setting the jumpers multiprocessor operation/coordinators
6-5 system manual c79000-g8576-c199-07 x1 x2 ep 60 16 9 8 1 (jr) ep 61 16 9 81 (jx) s1 mode switch (run,stop,test) s2 s3 x4 ep 64 16 9 81 (ju) x6 x5 ep 62 16 9 81 (jy) ep 63 16 9 8 1 (jz) front view s1, s2, s3 on off off on off on figure 6-2 location of jumper sockets and switches on the 923a coordinator and front view of switches s1 to s3 (when delivered) note ensure that all the switches are operated clearly (meaning past the latching point). multiprocessor operation/coordinators
6-6 system manual c79000-g8576-c199-07 the individual actions are explained in more detail in the following. setting the number of occupied cpu slots on the coordinator: 923a coordinator number of cpus used jumper(s) at ep 62 2 7 - 10; 8 - 9 1) 3 7 -10 4 8 - 9 923c coordinator coded by inserting only one dil switch s1.4, s1.5 or s1.6 in the front plate recess: (see figure 6-2) dil s. on off effect s1.1 s1.2 s1.3 s1.4 s1.5 s1.6 x x x x x x enable test mode no. of occupied cpu slots = 2 1) no. of occupied cpu slots = 3 no. of occupied cpu slots = 4 1) setting when delivered setting the communication flag areas: if ... then ... you use communication flag areas on cps (please consult the relevant manuals), you must mask out these areas (blocks) on the coordinator without fail, to avoid duplicated addressing of the communication memory. the 256 communication flag bytes can be masked out in groups of 32. you do this by removing jumpers at coding socket ep 7 on coordinator a (see figure 6-1 for location) or ep 60 on coordinator c (see figure 6-2). step 1 step 2 multiprocessor operation/coordinators
6-7 system manual c79000-g8576-c199-07 16 1 ep 7 ep 60 9 8 8 9 1 16 when the unit is delivered, all communication flag areas are activated (see above): on coordinator a by jumpers at ep 7 on coordinator c by jumpers at ep 60 jumper comm. flag byte address 8 - 9 7 - 10 6 - 11 5 - 12 4 - 13 3 - 14 2 - 15 1 - 16 0 to 31 32 to 63 64 to 95 96 to 127 128 to 159 160 to 191 192 to 223 224 to 255 f200h to f21fh f220h to f23fh f240h to f25fh f260h to f27fh f280h to f29fh f2a0h to f2bfh f2c0h to f2dfh f2e0h to f2ffh jumper inserted: area activated (coordinator acknowledges in this area) jumper not inserted: area masked out (coordinator does not acknowledge in this area) you wish to mask out the four communication flag areas with the highest addresses on cor a: 1 8 9 16 ep7 address f200h to f27fh activated (jumper inserted) address f280h to f2ffh masked out (jumper open) figure 6-3 example of addressing the communication memory on cor a examples multiprocessor operation/coordinators
6-8 system manual c79000-g8576-c199-07 you wish to mask out the four communication flag areas with the highest addresses on cor c: 1 8 916 ep 60 address f200h to f27fh activated (jumper inserted) address f280h to f2ffh masked out (jumper open) figure 6-4 example of addressing the communication memory on cor c inserting cpus and coordinator in the central controller:  precondition: the central controller is not yet switched off. substep action reaction 3a insert the cpus and coordinator in the relevant slots. none 3b insert all eprom or ram submodules in the cpus accord- ing to the configuration. the eprom submodules must have been previously programmed with a pg. none 3c set all mode switches on the cpus and on the coordinator to stop. none step 3 multiprocessor operation/coordinators
6-9 system manual c79000-g8576-c199-07 action reaction switch the supply voltage on. 1. the red stop leds flash rapidly on all cpus to indicate: overall reset requested. 2. if the test mode is not set at the coordinator (see section 6.3) and the mode switch is not at the test setting : the red basp (output inhibit) led is permanently lit to indicate: digital outputs are inhibited. symptom: on some cpus the stop led is not lit; the other cpus are requesting overall reset. all cpus are emitting the basp (output inhibit) signal. remedy: check the setting for the number of occupied cpu slots on the coordinator. are the cpus inserted at suitable slots? executing an overall reset on all cpus: ensure that the mode switch on the coordinator is set to stop. (precondition: steps 3 and 4 have been fully executed. action reaction execute the overall reset for each individual cpu: hold the operating mode switch in the overall reset setting; simultaneously set the mode switch from stop to run and back to stop. the red stop leds on the cpus at which the overall reset was executed, light up continuously. each cpu additionally emits the output inhibit signal (basp led continuously lit). step 4 possible faults step 5 multiprocessor operation/coordinators
6-10 system manual c79000-g8576-c199-07 loading step 5 user programs in all cpus:  recommended precondition: the programs of the individual cpus have already been tested in single-processor operation. for details of loading step 5 blocks and using the different types of memory, please consult the relevant programming guides of the cpus and your pg manual. prerequisites what? where? data block db 1 must be present for i/o allocation. in all cpus 1) data block dx 0 must additionally be present at cpu 948. the mode for a process interrupts via ib 0 = off o must be set in dx 0. only in cpu 948 to start multiprocessor operation immediately with all cpu programs, you must now load your programs into the individual cpus. after completing these steps, however, you can load individual programs into certain cpus. into the desired cpu 1) 1. you must only load the blocks for cpus with ram operations; for eprom operation, the inserted eproms must contain your user program with db 1 (dx 0). data blocks which you have provided for dynamic data storage must be copied after a reset by program into the ram. reaction there is no change in the reactions of step 4 (each cpu still emits the output inhibit signal: the basp led is continuously lit). step 6 multiprocessor operation/coordinators
6-11 system manual c79000-g8576-c199-07 executing a reset at all cpus: action reaction execute a reset at each individual cpu: hold the mc 1) mode switch at the reset setting; simultaneously set the mode switch from stop to run. the red stop led on each cpu is continuously lit; each cpu emits the output inhibit signal. the cpus are in the wait state. 1) mc: momentary-contact symptom 1: the stop led of one cpu flashes slowly. when the control bits of this cpu are read out with the programmer, adb 1 erroro is marked in addition to the usual information. there is no output of an istack. remedy: check whether data block db1 in the cpu was correctly loaded and programmed. symptom 2: after execution of a reset: undefined states or faults occur at the cpus (for example, after a restart at cpu 922, it goes to the run state although the other cpus are still at stop). remedy: verify the following points:  is the coordinator inserted?  are all modules correctly inserted (engaged)?  are all modules at the correct slots? step 7 possible faults multiprocessor operation/coordinators
6-12 system manual c79000-g8576-c199-07 setting the coordinator mode switch to run or test: if ... then ... reaction you do not wish to work in the test mode 1) set the coordinator mode switch from stop to run. the green run leds of all cpus are continuously lit. all cpus simultaneously go into the cycle. the output inhibit signal is not emitted (basp led = off). you wish to work in the test mode (it must be enabled on the coordinator) 1) set the coordinator mode switch from stop to test. set the coordinator mode switch from stop to test. 1) test mode and setting: see section 6.3 symptom: all cpus remain in the stop state. remedy: check whether the mode switches of all cpus are set to run. a subsequent start of individual cpus is not possible. switch the coordinator back to stop. execute a reset at all cpus and then switch the coordinator to run again. note during the starting phase (processing of the start obs) the stop and run leds remain off at all cpus. the run led only lights up continuously when the cpus go over to cyclic program processing.  when the coordinator is switched from stop to test, only the cpus whose switches are at the run setting will operate in the test mode.  if the 923c coordinator is used and the pg interface on the front plate is not connected to the pg and switched online, the if fault led lights up on the 923c coordinator. the indicator can be ignored in this case. step 8 possible faults notes relating to multiprocessor start multiprocessor operation/coordinators
6-13 system manual c79000-g8576-c199-07 6.3 coordinator modes if, when the supply voltage is switched on, the coordinator mode switch is at stop or another stop request is pending, the cpus remain in the stop state. automatic reset or automatic restart if, when the supply voltage is switched on, the coordinator mode switch is at run, an automatic reset or automatic restart (depending on dx 0 setting) will take place as long as the mode switches of the cpus are also at run and the plc was previously in cyclic operation. manual start when you set the coordinator mode switch from stop to run, the cpus will execute a start if this was already prepared at all cpus by appropriate switch actuation, i.e. the cpus are in the wait state. as required by the user, the type of start can be the same for all cpus or arbitrarily different. after the start synchronization by the system programs, the cpus simultaneously go to run (cyclic operation). the transition of individual cpus is synchronized - as long as the preset astart synchronizationo in the relevant cpus has not been changed by dx 0 programming - i.e. only when each cpu has ended its start do all cpus jointly go to cyclic program processing. if the coordinator mode switch is at the run setting and one cpu goes to the stop state, all the other cpus also go to the stop state. the red stop led(s) on the cpu(s) causing the stop state flash slowly; the stop leds of the other cpus are continuously lit. apart from any indication with fault leds on the cpu which is the cause, all cpus emit the basp (output inhibit) signal. the stop state startup normal operation and stop in the event of faults multiprocessor operation/coordinators
6-14 system manual c79000-g8576-c199-07 ! warning since, in the test mode, no cpu can emit a basp (output inhibit) in the event of a fault, the test mode must be switched to the inactive state without fail after completion of startup to avoid a critical or even hazardous system state. before you can go into the test mode with the test switch, you have to enable it on the module. this is achieved differently with the 923a and 923c coordinators. insert jumper 3 - 14 on coding socket ep 45 as shown in the following sketch. 14 16 8 9 13 ep 45 923a coordinator set dil switch s1.3 from off to on (the following table shows the dil switches as delivered; see also figure 6-2). dil s. on off effect s1.1 s1.2 s1.3 s1.4 s1.5 s1.6 x x x x x x test mode no. of occupied cpu slots = 2 no. of occupied cpu slots = 3 no. of occupied cpu slots = 4 when the coordinator mode switch is set from stop to test, the cpus can be started individually. there is therefore no synchronized transition to cyclic program processing. the output of signal basp is suppressed on all cpus, even if there is an error. if an error occurs with a cpu switched to run, only this one goes to the stop state in the test mode. the error is indicated by slow flashing of the cpu's stop led. the error at this cpu does not affect other cpus. if the test mode is not activated, a changeover from stop to test does not result in any reaction of the cpus. test mode enabling the test mode with the 923a enabling the test mode with the 923c reaction of the cpus multiprocessor operation/coordinators
6-15 system manual c79000-g8576-c199-07 6.4 923a coordinator module (is no longer supplied) 6.4.1 technical description this section contains information on the application, design and principle of operation of the 923a coordinator. the 923a coordinator module is intended for operation in the s5-135u/155u plc. it is required in multiprocessor operation and has the following functions:  bus arbitration to coordinate multiprocessor operation, i.e. the simultaneous use of two to four cpus (cpu 928b, cpu 928 or cpu 922).  communication memory for the interchange of data between cpus via communication flags. note the 923a coordinator module cannot be used in multiprocessor operation if a cpu 948 is fitted in the 135u/155u plc . if you execute global memory access in multiprocessor operation (i/o area with addresses 0000h-efffh) with the cpu 928b and/or the cpu 928, you must use the cor 923c as the coordinator. the cor 923a is designed as a plug-in pcb of double eurocard format. two 48-way series 2 blade connectors serve to connect the pcb to the s5 bus in the subrack. the front plate width is 1 1/3 standard plug-in stations. a three-position mode switch is fitted in the front plate for operator functions. application design multiprocessor operation/coordinators
6-16 system manual c79000-g8576-c199-07 bus arbitration the cor 923a cyclically allocates a bus enable signal to each of the two to four cpus in the s5-135u/155u plc. only during this time can the relevant cpu utilize the common s5 bus. the assignment of bus enable signals takes place in time-division multiplex operation. on the cor 923a, you set the number of cpus with jumpers. the enable time for access to the s5 bus is preset at 2 ms for all cpus. if the bus enable signal has been emitted by the coordinator for a cpu, this cpu can extend the enable time with the bus lock signal. however, the user has no influence on this. the bus enable assignment sequence begins with cpu 1 after the reset signal is removed by the power supply, and enables the cpus in the following order according to the preset number of cpus: cpu 1, cpu 2, cpu 3, cpu 4, cpu 1, cpu 2 etc. (see figure 6-5) cpus in operation cpu1 cpu2 cpu3 cpu4 bus lock reset bus enable for: time bus lock 2 m s 2 m s + figure 6-5 timing sequences of the bus signals communication memory the communication memory comprises a central battery-backed ram in the plc. it has two areas: the communication flags and the semaphores. the communication flags on the cor 923a allow the cyclic interchange of data between the cpus. the semaphores are mainly used to coordinate the exchange of data in the i/o area. please consult the programming guides of the cpus to program these functions. principle of operation multiprocessor operation/coordinators
6-17 system manual c79000-g8576-c199-07 6.4.2 settings on the coordinator a three-stage mode switch on the front plate serves for user control; it has the settings run, stop and test. the functions of the mode switch and its use are explained in sections 6.2 and 6.3. mode switch for run, stop and test figure 6-6 front plate of the cor 923 a user control multiprocessor operation/coordinators
6-18 system manual c79000-g8576-c199-07 6.5 923c coordinator module 6.5.1 technical description this section contains information on the application, design and principle of operation of the 923c coordinator. the 923c coordinator module can be used in the s5-135u/155u programmable controller and in the eu s5-185u expansion unit. there are three main task areas which are, to some extent, independent:  bus arbitration (only in the central controller) to coordinate multiprocessor operation, i.e. the simultaneous use of two to four cpus (cpu 948, cpu 928b, cpu 928, cpu 922).  communication memory (only in the central controller) for the interchange of data between cpus via communication flags and data blocks.  central programmer connection (pg mux) for the programming and startup of up to 8 modules via one pg connection. to program a programmable controller via the sinec h1 or sinec l1/l2 bus, connect the sinec cp to the pg connection of the cor c using the 725 cable (aswingo cable). application multiprocessor operation/coordinators
6-19 system manual c79000-g8576-c199-07 the cor 923c is designed as a plug-in pcb in double eurocard format. two 48-way series 2 blade connectors serve to connect the module to the s5 bus in the subrack. the front plate width is 1 1/3 standard plug-in stations. a mode switch with three settings is fitted in the front plate for other operator functions. faults are indicated by five small red leds. there is a recess with cover in the upper third of the front plate. by removing the cover, you can operate the dil switches to set parameters for the module. you can connect the cor 923c via a 15-pin front connector to a programmer, op, operator control panel or the cp 530 and cp 143. the cor 923c cyclically allocates a bus enable signal to each of the two to four cpus in the s5-135u/155u plc. only during this time can the relevant cpu utilize the common s5 bus. the assignment of bus enable signals takes place in time-division multiplex operation. on the cor 923c, you set the number of cpus with dil switches. the enable time for access to the s5 bus is preset at 2 ms for all cpus. if the bus enable signal has been emitted by the coordinator for a cpu, this cpu can extend the enable time with the bus lock signal. however, the user has no influence on this. the bus enable assignment sequence begins with cpu 1 after the reset signal is removed by the power supply, and enables the cpus in the following order according to the preset number of cpus: cpu 1, cpu 2, cpu 3, cpu 4, cpu 1, cpu 2 etc. (see figure 6-7) design principle of operation multiprocessor operation/coordinators
6-20 system manual c79000-g8576-c199-07 cpus in operation cpu1 cpu2 cpu3 cpu4 bus lock reset bus enable for: time bus lock 2 m s 2 m s + figure 6-7 timing sequences of the bus control signals monitoring for continuous bus assignment the bus lock signal can only be emitted by the cpu which has already received a bus enable signal from the cor 923c. the bus enable time is extended by the duration of the bus lock signal for the cpu (see figure 6-7). the factory setting for monitoring of the bus lock signal is 2 ms. if the signal remains active for a longer duration, the cor 923c emits a signal which results in a stop of all cpus. the cpu which emitted the bus lock signal for too long a duration, is marked by the cpu in a readable register under address feffh (fault register, see figure 6-8). the assigned bus fault led in the front plate of the cor 923c lights up. the register is cleared and the led goes off again when the signal which led to the stop state becomes inactive. communication memory the communication memory comprises a central battery-backed ram in the plc. it has three areas: 1) the communication flags (256 bytes), 2) the semaphores (32), and 3) four memory pages. the communication flags are located in memory area f200h to f2ffh. the communication flags enable the cyclic interchange of small volumes of data between the cpus in the s5-135u/155u plc. the four memory pages serve for the exchange of data blocks between cpus. please consult the programming guides of the cpus to program these two functions. multiprocessor operation/coordinators
6-21 system manual c79000-g8576-c199-07 the semaphores are used to coordinate the cpus for access to the same i/o address (see programming guides, operations ses and sef). page memory for data blocks vector register for page selection, fault register synchronization area for operating systems communication flags feffh f7ffh f400h f300h f200h page no. 253 page no. 254 page no. 255 page no. 252 figure 6-8 areas of the communication memory on the s5 bus addressing method for the page memory (vector register) the vector register serves to form subaddresses of several memories in a common address area. the register is an 8-bit register which is written to under address feffh. it cannot be read out. the page memory contains four pages of 1 kbyte. an identification number is assigned to each page. these are the numbers 252, 253, 254 and 255. these numbers are permanently set on the cor 923c and cannot be changed. you must not use these numbers on other modules (cp, ip) in the same plc otherwise double addressing will occur. when the supply voltage is switched on, the vector register is cleared. the vector register then has the number 0h. the transfer of data to and from this memory is implemented with special functions of the cpu. you can find these functions in the appropriate programming guides. the pg interface of the cor 923c can be switched over to eight different serial interfaces via the path selection of the pg software. the multiplex interfaces have ttl level and are wired to the other modules via the backplane connector and backplane. pg multiplexer multiprocessor operation/coordinators
6-22 system manual c79000-g8576-c199-07 station numbers are assigned to all the modules to be served by the multiplexer in the unit. these numbers must be within the range 1 to 31 (decimal). you set the lowest of these numbers, the base address, with dil switch s2 in binary code. the maximum of eight numbers are allocated to the slots of the plc (see following table). all eight numbers or slots are assigned to switch s3: the lowest number to switch s3.1, and the highest number to switch s3.8. the setting of station numbers and the base address are described in more detail in section 6.5.2. switch slot station no. s3.1 s3.2 s3.3 s3.4 s3.5 s3.6 s3.7 s3.8 11 27 43 59 75 83 91 99 base address base address + 1 base address + 2 base address + 3 base address + 4 base address + 5 base address + 6 base address + 7 if slots are not occupied or if you wish to operate modules via their own front connectors, you must delete the numbers assigned to the corresponding slots with switch s3. note for a module operated via the multiplexer, the front connector of the pg interface of the cpu must not be plugged in. with cpus 948 and 928b, this only applies to the integrated pg interface si 1. selection method for the serial interfaces multiprocessor operation/coordinators
6-23 system manual c79000-g8576-c199-07 6.5.2 settings on the coordinator shown in figure 6-9 are all the indicators and controls on the front plate of the cor 923c. setting the pg multiplexer: s1.3 to enable/lock out the atesto mode s1.4 to s1.6 to set the number of cpus setting the coordination section: s2.2 to s2.6: base address s3.1 to s3.8: activating the slots to be served by the cor923c mode switch for run, stop and test pg interface, 15-pin aif faulto led indicates fault at the serial interface. if the interface is not in use, the led is permanently lit. abus faulto leds these are allocated to the relevant cpus and light up when the max. value of monitored bus access time is exceeded. figure 6-9 front plate of the cor 923c the mode switch on the front plate can be set to run, stop and test. please refer to sections 6.2 and 6.3 for its functions and use. note ensure that all the switches are operated clearly (meaning past the latching point). indicators and controls mode switch multiprocessor operation/coordinators
6-24 system manual c79000-g8576-c199-07 note on switch s1, the on position is on the left; on switches s2 and s3, however, it is on the right (see figure 6-10). on off on on off off figure 6-10 dil switches on the cor 923c (settings when delivered) you set the number of cpus present in the plc with the 3 dil switches s1.4 to s1.6. you may only set one switch. the factory setting is anumber of cpus = 2o (see below). factory setting: switch setting meaning on off s1.1 x s1.2 x s1.3 x test mode (see also sec. 6.3) s1.4 x number of cpus = 2 s1.5 x number of cpus = 3 s1.6 x number of cpus = 4 setting the dil switches coordination section (number of cpus) multiprocessor operation/coordinators
6-25 system manual c79000-g8576-c199-07 you set a base address from 1 to 31 with dil switch s2. you can reference the modules selected by the multiplexer under this address and the following seven addresses. the base address results from the sum of binary significances activated by the on setting of the switch. factory setting: switch setting meaning off on '0' '1' s2.1 x s2.2 x significance 16 s2.3 x significance 8 s2.4 x significance 4 s2.5 x significance 2 s2.6 x significance 1 (base address = 1) you use switch s3 to activate the numbers and slots to be reached via the cor 923c. factory setting: switch setting meaning slot no. in the s5 135u/155u off on s5-135u/155u s3.1 x base address + 0 11 s3.2 x base address + 1 27 s3.3 x base address + 2 43 s3.4 x base address + 3 59 s3.5 x base address + 4 75 s3.6 x base address + 5 83 s3.7 x base address + 6 91 s3.8 x base address + 7 99 an example for setting the pg multiplexer is given on the following page. pg multiplexer: base address pg multiplexer: activating addesses multiprocessor operation/coordinators
6-26 system manual c79000-g8576-c199-07 you wish to reference modules at slots 11, 59, 75 and 99 in the s5-135u/155u plc via the cor 923c, from base address 10. setting the base address: switch setting meaning off on base address: s2.1 x s2.2 x significance 16 s2.3 x significance 8 8 s2.4 x significance 4 s2.5 x significance 2 +2 s2.6 x significance 1 = 10 activating the required slots for the s5-135u/155u plc: switch setting meaning slot no. in the s5-135u/155u operable slots end address off on s3.1 x base address + 0 11 11 10 s3.2 x base address + 1 27 s3.3 x base address + 2 43 s3.4 x base address + 3 59 59 13 s3.5 x base address + 4 75 75 14 s3.6 x base address + 5 83 s3.7 x base address + 6 91 s3.8 x base address + 7 99 99 17 example of address activation multiprocessor operation/coordinators
6-27 system manual c79000-g8576-c199-07 all the output signals required for coordination (arbitration) can be interrupted by removing a jumper plug. this is necessary to operate the cor 923c as a pg multiplexer in the eu s5-185u. coordination section in operation out of operation all jumpers of ep 61 closed all jumpers of ep 61 open 1 8 ep 61 9 16 when the unit is delivered, all jumpers are closed. the fault register is an 8-bit register and is readable by the cpu under address feffh. the register is written to by the bus monitor in the event of a bus error. each cpu is assigned one bit of the fault register which is set to 1 in the event of an error. the register is cleared each time the stop signal becomes inactive. fault register feffh bit = 1: bus error from cpu 1 bit = 2: bus error from cpu 2 bit = 3: bus error from cpu 3 bit = 4: bus error from cpu 4 7 4 3210 not assigned the fault register can be read by all cpus, allowing central functions to be initiated. note the fault register and the page register are at address feffh (ffeffh with the cpu 948). the page register is addressed by writing to feffh, and the fault register is addressed by reading out feffh. jumpers to switch off the coordination signals fault register multiprocessor operation/coordinators
6-28 system manual c79000-g8576-c199-07 6.6 technical specifications of the coordinators important for the usa and canada the following approvals have been obtained:  ul listing mark underwriters laboratories (ul) to standard ul 508, report e 85972  csa certification mark canadian standard association (csa) to standard c 22.2 no. 142, report lr 63533 923a coordinator 923c coordinator degree of protection ip 00 operating temperature 0 to +55  c transportation and storage temperature 40 to +70  c relative humidity 95% max. at +25  c, no condensation operating altitude 3500 m max. above sea level supply voltage 5 v  5% 5 v  5% 24 v +25%/ -15% current consumption at 5 v 0.5 a typical 1.1 a typical current consumption at 24 v 60 ma minimum backup voltage 2.7 v backup current 100 na typical 2  a typical acknowledgement time for access to communication memory via s5 bus 320 ns typical transmission rate of the serial interface 9600 bps transmission cable shielded 4-wire line, pg connecting cable transmission range 1 km max. at 9600 bps weight approx. 0.3 kg dimensions (w x h x d) 20.32 x 233.4 x 160 mm multiprocessor operation/coordinators
7-1 system manual c79000-g8576-c199-07 interface modules various interface modules (ims) are available for communication between a central controller and expansion units, and between expansion units. interface modules in the central controller are known as eu interface modules; those inserted in an eu are known as cc interface modules. this chapter describes the eu interface modules:  im 300-3, im 300-5, im 301-3, im 301-5 and im 304 as well as the cc interface modules:  im 312-3, im 312-5, im 310 and im 314 other ims such as the im 307-im 317 and the im 308-im 318 are described in separate manuals (see catalog st 54.1). the im 306 cc interface module is described in the s5-115u plc manual. a general overview of the applications of individual ims can be found in chapter 2: acentralized and distributed configuration of a programmable controller.o section description page 7.1 the 300 and 312 interface modules 7-2 7.2 the 301 and 310 interface modules 7-10 7.3 the 304 and 314 interface modules 7-14 7.4 technical specifications 7-21 chapter overview 7
7-2 system manual c79000-g8576-c199-07 7.1 the 300 and 312 interface modules the 300 and 312 interface modules are used for centralized connection of i/o modules and signal preprocessing modules (ips) to a cc via the following expansion units (allowing for possible configurations):  eu 183u  eu 184u  eu 185u (only input/output modules)  eu 187u  er 701-1 additionally, you can utilize these ims for secondary communication, i.e. additional eus can be connected in a centralized arrangement to an eu 183u or eu 185u in distributed configuration. up to four im 300s can be used in one cc, up to two of which may be im 300-5s. you can use one im 300 in an eu 183u or eu 185u. an im 300 eu interface module is complemented by an im 312 or im 306 cc interface module. use the following ims, depending on the connected eu: eu interface module eu type cc interface module im 300-5 c (6es5 300-5ca11) eu 184u, eu 187u im 312-5 im 300-3 (6es5 300-3ab11) eu 183u eu 185u (only i/o modules) im 312-3 im 300-5 l (6es5 300-5lb11) er 701-1 im 306 there are two versions of im 312-3 and im 312-5. they differ in the length of permanently connected cable: order no. cable length 6es5 312-5ca1x 6es5 312-5ca2x 0.5 m 1.5 m 6es5 312-3ab1x 6es5 312-3ab3x 0.5 m 0.95 m application of the im 300 and im 312 interface modules
7-3 system manual c79000-g8576-c199-07 for one im 300-5, you can connect up to three eus to a cc or eu in distributed arrangement (see figures 7-5 and 7-6). the eus are supplied with operating voltage via the ims. any free connections on the im 300-5 and the last im 312-5 require no terminator. note the maximum permissible current over each connection of the im 300-5ca11 is 5 a. you can connect up to four eus to each im 300-3. the last im 312-3 requires a terminator. you can connect up to three ers to each im 300-5l (-5lb11). the ers are supplied with operating voltage via the ims. note the maximum permissible current over each connection of the im 300-5lb11 is 2 a. the connection of central controller and expansion unit to the im 300-5lb11 is provided exclusively by the 705-0 connecting cable. it is available in two lengths: 0.5 m and 1.5 m (refer to the ordering information for order numbers). when the im 300s are used in the s5-135u/155u plc, the input/output modules can be addressed in the normal (p) and extended (o) areas. you may only set module addresses in the eu which are not used in the cc. this applies to both areas. connecting the eu 184u and eu 187u connecting the eu 183u, eu 185u connecting the er 701-1 addressing interface modules
7-4 system manual c79000-g8576-c199-07 7.1.1 indicators and controls im 300-3 : i/o module failure led this led lights up if the supply of power to the connected eus has failed and/or the connecting cable is open-circuit. im 300-5 (-5ca11): i/o module failure leds leds ld1 and/or ld2 light up if a module inserted in the eu no longer responds to an access by the cpu. the im 312 has no indicators or controls. 50 34 18 33 17 1 im312 fault 50 34 18 33 17 1 50 33 17 34 18 1 im300-5 fault i/o module fault 50 34 18 33 17 1 im300-3 failure i/o module failure figure 7-1 front plates of the im 300 and im 312 interface modules
7-5 system manual c79000-g8576-c199-07 7.1.2 modes/jumper assignments of the im 300 im 300-3 up to version 10 x1 x2 12 16 9 8 1 j1 x3 led 1 o area figure 7-2 location of jumpers on the im 300-3 (as delivered) you must insert an additional jumper 4-13 at location 12 for address setting in the extended i/o area (o area). jumper 1 is open and has no function for operation in the s5-135u/155u plc. jumper assignments purpose of the jumpers interface modules
7-6 system manual c79000-g8576-c199-07 im 300-5 (-5ca11) up to version 06 x1 x2 4 16 9 8 1 j2 j1 j3 j8 x3 x4 led1 led2 o area figure 7-3 location of jumpers on the im 300-5 (-5lb11) (as delivered) you must insert jumper 8-9 at location 4 for address setting in the extended i/o area (o area). all other jumpers must remain in their factory settings. jumper assignments interface modules
7-7 system manual c79000-g8576-c199-07 im 300-3ab11 from version 11 im 300-5ca11 from version 07 the single switch s1 is used to specify the address on the p area or on the o area. the other single switches must remain in the state of delivery (off). x1 x2 x3 x4 led1 led2 (im 300-5) 6 5 4 3 2 1 s1 (im 300-5) si for p area off on 65 4 32 1 si for o area off on 65 4 32 1 note ensure that all the switches are operated clearly (meaning past the latching point). jumper assignment interface modules
7-8 system manual c79000-g8576-c199-07 im 300-5 (-lb11) x1 x2 x3 x4 m1 p1 q1 q2 q3 q4 q5 figure 7-4 location of jumpers on the im 300-5 (-5lb11) (as delivered) you must insert jumpers q1 to q4 for addressing in the normal (p) area. if you insert jumper q5, the ai/os not readyo message will be relayed to the cpu. all other jumpers must remain in their factory settings. shown in the following figures is the centralized communication between central controller and expansion units, with and without supply of power via the im 300 and im 312. jumper assignments interface modules
7-9 system manual c79000-g8576-c199-07 im 300-3 eu183u im 312-3 eu183u im 312-3 eu183u im 312-3 eu183u im 312-3 s5-135u/155u cc terminator total length of lines 2 m max. figure 7-5 centralized communication between central controller and expansion units with a power supply unit im300-5 s5-135u/155u cc im312-5 im312-5 im312-5 (1.5m) im 312-5 eu 184u eu 187u eu 184u eu 187u eu 184u eu 187u eu 184u eu 187u eu 184u eu 187u im 312-5 (0.5m) with this arrangement, the two cabinets must be electrically interconnected. 5 a max. 5 a max. total length of lines 2 m max. figure 7-6 centralized communication between central controller and expansion units without a power supply unit the eu with the highest current consumption should be positioned as closely as possible to the cc. interface modules
7-10 system manual c79000-g8576-c199-07 7.2 the 301 and 310 interface modules the im 301 is used to connect i/o modules and signal preprocessing modules (ips) to a cc in a distributed arrangement (allowing for possible configurations) via an  eu 183u  eu 185u (only input/output modules) expansion unit. you can connect up to four eus to a cc in distributed arrangement via the im 301. if you use the 721 connecting cable, the total cable length from the cc to the last eu may be up to 200 m. the distributed connection is made via the lower front connector of the module. use the im 310 interface module in the eu to be connected in a distributed arrangement: eu interface module eu type cc interface module im 301 eu 183u, eu 185u (only i/o modules) im 310 apart from the distributed eus, you can connect the following expansion units in a centralized arrangement:  eu 183u  eu 184u  eu 187u the centralized connection is made via the upper front connector of the module. use the following interface modules, according to the eu to be connected in a centralized arrangement: eu interface module eu type cc interface module im 301-5 eu 184u, eu 187u im 312-5 im 301-3 eu 183u im 312-3 unused centralized connections of the im 301-3 and unused distributed connections of the im 301-3 and im 301-5 must be terminated with terminators. the same applies to the last im 310. you may only set module addresses in the eu which you are not yet using in the cc. this applies to the normal (p) and extended (o) areas. interface modules
7-11 system manual c79000-g8576-c199-07 7.2.1 indicators and controls im 301: fault leds when the cpu is restarted, the red led 1 and/or led 2 lights up if the internal supply voltage (5 v dc) or external load voltage (24 v dc) fails. the im 310 has no indicators or controls. fault fault 50 34 18 33 17 1 50 33 17 34 18 1 50 34 18 33 17 1 50 33 17 34 18 1 im 301 im 310 fault centralized connection distributed connection figure 7-7 front plate of the im 301 and im 310 interface modules
7-12 system manual c79000-g8576-c199-07 7.2.2 modes/jumper assignments of the im 301 x1 x2 7 16 9 8 1 j3 j1 x3 x4 led1 led2 27 16 9 8 1 j4 *) *) not on the im 301-5 figure 7-8 location of jumpers on the im 301 (as delivered) you must insert jumper 8-9 at location 7 for address setting on the extended i/o area (o area). all other jumpers must remain in the factory settings. jumper assignments interface modules
7-13 system manual c79000-g8576-c199-07 the following figures show distributed communication between central controller and expansion units via the im 301 and im 310. terminator 760-0ab11 im301-3 eu 183u cc s5-135u/155u to additional expansion cabinets (up to 4 per im 301) iim312-3 200m max. eu183u eu 183u iim312-3 im300-3 im 310 eu 184u eu 183u im 312-5 im 300-5 im 310 eu 187u all 721 connecting cables additional eu 184u, eu 187u (centralized) additional eu 183u (centralized) 760-0aa11 terminator figure 7-9 connection of eu 183us to the central controller via the im-301-3 im 301-5 eu 184u cc s5-135u/155u im 312-5 eu 187u additional eu 184u, eu 187u (centralized) to additional expansion cabinets (up to 4 per im 301) 760-0aa11 terminator eu 183u eu 183u im 312-3 im 300-3 im 310 eu 184u eu 183u im 312-5 im 300-5 im 310 eu 187u all 721 connecting cables additional eu 184u, eu187u (centralized) 760-0aa11 terminator figure 7-10 connection of eu 184/eu 187 u to the central controller via the m 301-5 interface modules
7-14 system manual c79000-g8576-c199-07 7.3 the 304 and 314 interface modules the im 304 and im 314 are used to connect i/o modules, signal preprocessing modules (ips) and communication processors (cps) to a cc in a distributed arrangement via the  eu 185u  er 701-3 expansion units. you can also use the im 304 and im 314 to connect i/o modules to a cc in a distributed arrangement via the  eu 183u  er 701-2 expansion units. you can connect up to two-times four eus in a distributed arrangement via one im 304. if you utilize the 721 connecting cable, the total line length from the cc to the last eu may be 600 m per run. you can connect additional eus in a centralized arrangement to the distributed eus. you can insert up to four im 304s in one cc. the im 304 eu interface module is complemented by the im 314 cc interface module. in fault-tolerant systems, you must use the im 314r cc interface module together with the im 304 (refer to the s5-155h manual). eu type eu interface module cc interface module eu 183u eu 185u er 701-2 er 701-3 im 304 im 314 you may only set module addresses in the eu which you do not use in the cc. this also applies when the eu is addressed in the extended (o) area, im3 area or im4 area. line length interface modules
7-15 system manual c79000-g8576-c199-07 7.3.1 indicators and controls fault leds a fault led lights up  if the power supply fails in an expansion unit;  if there is no terminator at the last im 314;  in the event of a cable open-circuit or wrong setting of dil switch s3 for the im 304;  or if an eu which is ready and operational is connected to an interface which is switched off. interface (x3) interface(x4) interface (x4) faulty fault signal: interface (x3) faulty fault signal: fault fault 50 34 18 33 17 1 50 33 17 34 18 1 50 34 18 33 17 1 50 33 17 34 18 1 im 304 im 314 figure 7-11 front plates of the im 304 and im 314 interface modules
7-16 system manual c79000-g8576-c199-07 7.3.2 modes/jumper assignments of the im 304 you must match the im 304 to the cable length with jumper x11. cable length 10 m max. 100 m max. 100 to 250 m 250 to 450 m 450 to 600 m jumper location jumper plug x11 9 7 5 3 1 10 8 6 4 2 *) 9 7 5 3 1 10 8 6 4 2 9 7 5 3 1 10 8 6 4 2 9 7 5 3 1 10 8 6 4 2 9 7 5 3 1 10 8 6 4 2 *) this setting is only permissible for im 304 - im 324r communication in the s5-155h plc. the longest communication path, i.e. the sum of cable lengths at interface of x3 or x4, is governed by the location of jumper x11. x3 x4 x1 x2 led2 led1 s3 x14 x15 x12 x11 x13 x21 x22 on off on off jumper x21/x22 set to off if no expansion unit is connected. 1 2 3 1 2 3 3 2 1 1 2 3 4 5 6 7 8 9 10 on off figure 7-12 location of jumpers on the im 304 (as delivered) note ensure that all the switches are operated clearly (meaning past the latching point). jumper assignments interface modules
7-17 system manual c79000-g8576-c199-07 function jumper settings interface x3/x4 - switched on - switched off 1) x22/x21 at aono x22/x21 at aoffo on off on off ai/os not readyo message relayed - no - yes x15 no jumpers x15 jumper 1-2 1 2 3 1 2 3 ai/os not readyo message when - 1 interface not ready - 2 interfaces not ready x14 jumper 1-2 x14 jumper 2-3 1 2 3 1 2 3 set cable length between 304 / 314 - 0 to 100 m - 100 to 250 m - 250 to 450 m - 450 to 600 m x11 jumper 3-4 jumper 5-6 jumper 7-8 jumper 9-10 9 7 5 3 1 10 8 6 4 2 1) jumper x22 is assigned to interface x3. jumper x21 is assigned to interface x4 all other jumpers and switches must remain at the factory settings. purpose of the jumpers interface modules
7-18 system manual c79000-g8576-c199-07 7.3.3 modes/jumper assignments of the im 314 set the jumpers according to the expansion unit in use. x3 x4 x1 x2 1 2 3 1 2 1 2 3 j1 j2 j3 operation in the eu 183u x3 x4 x1 x2 1 2 3 1 2 1 2 3 j1 j2 j3 operation in the eu 185u x3 x4 x1 x2 1 2 3 1 2 1 2 3 j1 j2 j3 operation in the er 701-2, er 701-3 (s5-115u plc) off s1 on off s1 on off s1 on 4 3 4 4 4 3 4 4 3 4 4 4 up to version 04 j1 has 2 poles, j2 and j3 3 poles figure 7-13 location of jumpers in the im 314 jumper assignments interface modules
7-19 system manual c79000-g8576-c199-07 i/o area address switch setting 0 = off, 1 = on p area: f000 - f0ff s1: 0000 *) o area: f100 - f1ff 0001 off irrelevant im3 area: fc00 - fcff 1100 off on im4 area: fd00 - fdff 1101 *) factory setting the i/o area address is set on the im 314. this setting applies only to the digital and analog i/o modules. address areas p, o, im3 and im4 are available. to address the digital and analog i/o modules in these areas, set the switches by depressing the individual rockers. in the step 5 standard operation set, you only address the p and o areas. module addresses used in the cc cannot be used in the eu in the p area, o area, im3 area and im4 area. if you do not insert i/o modules in the central controller, an address space of 256 bytes is available in each i/o area for input/output addresses. the following figure shows communication between the central controller and expansion units via the im 304 and im 314. note ensure that all the switches are set clearly (meaning past the latching point). setting the addresses interface modules
7-20 system manual c79000-g8576-c199-07 (up to 4 per im 304) 600m max. im304 to additional expansion cabinets (distributed) eu 183u eu 183u im 312-3 im 300-3 im314 eu 184u eu 183u im 312-5 im 300-5 im 314 eu 187u all 721 connecting cables 760-1aa11 terminator cc s5-135u/155u eu 185u eu 185u im 300-3 im 312-3 eu 183u im 312-3 im 300-3 eu 184u eu 183u im 312-5 im 300-5 im 314 eu 187u additional eu 184u, eu 187u (centralized) 760-1aa11 terminator eu 183u eu 183u eu 183u eu 185u eu 185u eu 185u im 314 iim 314 all 721 connecting cables figure 7-14 communication between central controller and expansion units via the im 304/im 314 interface modules
7-21 system manual c79000-g8576-c199-07 7.4 technical specifications important for the usa and canada the following approvals have been obtained:  ul listing mark underwriters laboratories (ul) to standard ul 508, report e85972 and e116536 for the im 300-5lb11  csa certification mark canadian standard association (csa) to standard c 22.2 no. 142, report lr 63533c and lr 48323 for the im 300-5lb11 given in the following are the technical specifications of the ims and pin assignments of the connecting cable and terminator. general specifications degree of protection ip 20 insulation class c to vde 0160 operating temperature 0 to 55 o c transportation and storage temperature - 40 to 70 o c relative humidity 95 % max. at 25 o c, no condensation mechanical requirements see description of central controllers supply voltage (internal) 5 v + 5 % specifications for specific ims interface module im 300 im 300 (-5ca) im 300 (-5lb) im 301 (-5ca) im 301 (-3ab) im 304 im 310 im 312 im 314 max. current consumption 0.2 a 0.2 a 50 ma 0.75 a 0.75 a 1.2 a 0.7 a 0.2 a 1.0 a max. current per interface - 5 a 2 a 5 a - - - - - weight, approx. 0.25 kg 0.30 kg 0.25 kg 0.3 kg 0.3 kg 0.35 kg 0.3 kg 0.35 kg 0.3 kg 7.4.1 6es5 721 connecting cable the 6es5 721-xxx connecting cable is intended for interconnection of the cc/eus. refer to the catalog for the simatic length codes. interface modules
7-22 system manual c79000-g8576-c199-07 . 34 . 1 50 . 17 . 1 . 34 . . 17 . 50 shield 6 rd 5wh 4wh 3wh 2gn 1rd red no. 16 green no. 17 yellow no.18 brown no.19 black no.20 blue no.21 connector 50-pin terminal bundle id sheath id foil 20 21 4 5 18 19 2 3 24 25 8 9 22 23 6 7 26 27 10 11 42 43 44 45 28 29 12 13 46 47 30 31 34 35 36 37 38 39 40 41 48 49 14 15 32 33 connector 50-pin terminal core color wh br gn ye gr pk bl rd wh br gn ye gr pk bl rd wh br gn ye gr pk bl rd wh br gn ye gr pk bl rd wh br gn ye gr pk bl rd wh br gn ye gr pk 21 4 5 18 19 2 3 24 25 8 9 22 23 6 7 26 27 10 11 42 43 44 45 28 29 12 13 46 47 30 31 34 35 36 37 38 39 40 41 48 49 14 15 32 33 20 - - figure 7-15 conductor assignments of the 721 connecting cable interface modules
7-23 system manual c79000-g8576-c199-07 7.4.2 6es5 7602 terminator the im 314 of the last expansion unit of each run is terminated with the 6es5 760-1aa11 terminator. the im 312 and im 301-3 (with a free centralized connection) is terminated with the 6es5 760-0ab11 terminator. the im 301-3 (with a free distributed connection) is terminated with the 6es5 760-0aa11 terminator. 117 34 50 6 22 5 12 6es5 760-0ab11 6es5 760-0aa11 connector pin 8 9 6 7 4 5 2 3 24 25 22 23 20 21 18 19 12 13 10 11 30 31 180-ohm resistor or jumper 28 29 26 27 46 47 44 45 42 43 38 39 34 35 36 37 40 41 14 / 48 16 50 15 / 49 6es5 760-1aa11 8 9 6 7 4 5 2 3 24 25 22 23 20 21 18 19 12 13 10 11 30 31 28 29 26 27 46 47 44 45 42 43 38 39 34 35 36 37 40 41 48 49 15 16 14 50 1) 1) 1) 1) 2) 1)100 ohm 2)200 ohm connector pin connector pin connector pin 180-ohm resistor or jumper connector pin 180-ohm-resistor or jumper connector pin figure 7-16 pin assignments of the 760 terminator interface modules
7-24 system manual c79000-g8576-c199-07 interface modules
8-1 system manual c79000-g8576-c199-07 digital input/output modules described in this chapter are the installation, wiring and operation of digital input modules and digital output modules. the 432 digital input module and the 482 digital input/output module have special features. these are discussed in separate sections. the technical specifications and front connector assignments for the individual modules are shown at the end of this chapter. section description page 8.1 technical description 8-2 8.2 installation and startup 8-14 8.3 common technical specifications 8-28 8.4 specification sheets for the modules 8-30 chapter overview 8
8-2 system manual c79000-g8576-c199-07 8.1 technical description the description below applies to the following modules: type of modules inputs/outputs input/output ct isolation/ groups *) number rated voltage current digital input modules 6es5 420-4ua13/14 6es5 430-4ua13/14 6es5 431-4ua12 6es5 432-4ua12 6es5 434-4ua12 6es5 435-4ua12 6es5 436-4ua12 6es5 436-4ub12 32 32 16 32 32 16 16 8 24 v dc 24 v dc 24 to 60 v dc 24 v dc/alarm 5 to 15 v dc 24 to 60 v ac 115 to 230 v ac 115 to 230 v ac 8.5 ma 7.0 ma 4.5 to 7.5 ma 8.5 ma 1.3 ma 15 to 25 ma 15 to 25 ma 15 to 25 ma no yes yes yes yes yes yes yes - 1 16 4 1 2 2 8 digital output modules 6es5 441-4ua13/14 6es5 451-4ua13/14 6es5 453-4ua12 6es5 454-4ua13/14 6es5 455-4ua12 6es5 456-4ua12 6es5 456-4ub12 6es5 457-4ua12 6es5 458-4ua12 6es5 458-4uc11 32 32 16 16 16 16 8 16 16 16 24 v dc 24 v dc 24 v dc 24 v dc 24 to 60 v ac 115 to 230 v ac 115 to 230 v ac 24 to 60 v dc 60 v relay 250 v ac relay 0.5 a 0.5 a 2.0 a 2.0 a 2.0 a 2.0 a 2.0 a 0.5 a 0.5 a 5 a no yes yes yes yes yes yes yes yes yes - 1 16 1 2 2 8 16 16 2 digital input/output modules 6es5 482-4ua11 6es5-482-4ua20 16 inputs and 16 outputs or 24 inputs and 8 outputs 24 v dc 8.5 ma (inputs) 0.5 a (outputs) yes 1 *) all inputs and outputs having a common 0 v ground form a group. technical specifications which are common to all modules are given in section 8.3. the special technical specifications for all modules can be found in section 8.4. digital input and digital output modules are i/o modules which allow the processing of widely differing process signals with the s5-135u/155u programmable controller. they can also be used via an adapter casing in the s5-115u plc. i/o modules di g ital input/output modules
8-3 system manual c79000-g8576-c199-07 a digital input module converts the process signals to the internal signal level in the module. interference is suppressed by the input circuitry, and the logic states at the inputs are indicated with leds on the front strip of the module. with most digital input modules (except the 420), the signals are isolated from the central ground point when received. inputs relating to the same group are isolated from inputs of another group, but not from each other. the control signals processed in the plc are output via digital output modules at a signal level suitable for the actuator, for example contactor, solenoid valve, etc. for the voltages and currents required in the process, modules with appropriate output circuitry are available. with most digital output modules (except the 441), the signals are isolated from the central ground point when relayed to the outputs. outputs relating to the same group are isolated from outputs of another group, but not from each other. if a digital output module receives a acommand output inhibito (basp, cf. programming guide and chapter 4) from the cpu, the outputs are set to zero. when the supply voltage of the central controller or expansion unit has been switched on or when the cpu is at stop, the outputs are set to zero. signal output h+ on digital output modules for direct voltage emits a signal when a short-circuit to ground (l-) or overcurrent has been detected at one or more outputs currently at logic 1. only short-circuits which are effective for more than 0.5 to 1 s are detected. short-circuits are only detected at connected outputs. the signal outputs are decoupled by diodes. up to 16 outputs can be connected in parallel. ensure that isolation is not defeated by the parallel connection of outputs. to ensure functioning of the signal output, you must connect terminal 1l+ to 24 v on the 441, 451 and 454 modules. on the 453 and 457 modules, the floating signal output must be powered separately. digital input modules digital output modules basp signal output, short-circuit detection di g ital input/output modules
8-4 system manual c79000-g8576-c199-07 8.1.1 design the modules are designed as plug-in pcbs for central controllers and expansion units with backplane connector and with a blade connector to accept a plug-in front connector. the front connector has screw or crimp terminals and is available separately; you can connect the process signal lines to it directly. fitted to each module is a strip with green leds to indicate the logic states of inputs or outputs. the leds are arranged in bytes and marked bit 0 to 7. output modules for direct voltage additionally have red leds to indicate short-circuits between output lines and ground (l-) within a group. output modules for alternating voltage have red leds to indicate a fuse failure. fitted on each module is an addressing switch with six, seven or eight rockers to set the module address. the modules are protected on both sides by covers. front connector leds blade connector addressing switch figure 8-1 digital input module led indicators addressing switch di g ital input/output modules
8-5 system manual c79000-g8576-c199-07 8.1.2 function of the enable inputs the digital input/output modules have an enable circuit. you can use the enable inputs to implement electrical interlocks for certain modules or switch off individual modules, whilst the plc is in operation. this means that:  the module can no longer be addressed by the user program.  all outputs of digital output modules are set to zero. modules which are switched off can be removed or inserted during operation. if this is not necessary, operate the module with the enable input switched off. on digital input/output modules with dc voltage inputs or outputs, the enable circuit requires that enable inputs f+ and f- be wired in the front connector. enabling is achieved by applying an external voltage to inputs f+/f-. modules for ac voltage have a wire jumper in the front connector. when the front connector is swivelled away from the front strip of the module, the supply of power to the enable input is interrupted, i.e. the wire jumper in the front connector is removed; the module is switched off and can no longer be addressed by the user program. when the front connector is swivelled away, i.e. the voltage is removed from the enable inputs, a timeout (qvz) occurs at the cpu (see the programming guide for the particular cpu). apart from the 6es5 458-4uc11 digital output module, all digital input/output modules additionally offer the facility for changing the enable mode. the modules have a jumper accessible from above in the vicinity of the addressing switch (see figure 8-2). enable jumper figure 8-2 location of the enable jumper jumper inserted: enable input (f+/f-) active (factory setting) jumper open: enable input (f+/f-) switched off with an active enable input di g ital input/output modules
8-6 system manual c79000-g8576-c199-07 if removal and insertion of modules during operation is not required, you must remove the plug-in jumper for changeover of the enable mode. wiring of the enable inputs (f+/f-) can then be dispensed with. almost power-free shutdown of individual subprocesses, i.e. outputs of various modules can be operated from a common load supply and yet activated separately. the load voltage of each individual module can be monitored without additional circuitry. any reactions to failure of the load voltage can be programmed in the qvz (timeout) organization block. you must observe the following when configuring systems: switching on at the latest 100 ms after power-up of the plc, the voltage must be present at the enable inputs of the i/o modules. switching off when the plc has been switched off, the voltage at the enable inputs of the i/o modules must still be present as long as voltage is applied to the cc/eu. you should observe the following instructions for switching off plcs and equipment for supplying power to the enable inputs: 24 v supply for cc/eu and i/os f+ l+ i/o modules 24 v dc b) a) cc/eu l+ battery 24v power supply enable supply from: a) battery b) terminals for 24 v on the front plate of the power supply with enable input switched off examples of functioning of the enable inputs di g ital input/output modules
8-7 system manual c79000-g8576-c199-07 when there is a need to switch off the load power supply separately without affecting the enabling of modules, there are the following possibilities for producing the enable voltage. these exist even when the power supply is used without an additional capacitor and common shutdown. 230 v ac supply for cc/eu and load power supply f+ l+ i/o modules 230v ac cc/eu -951 a) c) b) battery l+ power supply load power supply 24v enable supply from: a) 6es5 951-4lb11 load power supply b) battery c) terminals for 24 v on the front plate of the power supply proper functioning is ensured if the 24 v load power supply has an output capacitance of at least 4700  f per 10 a of load current. other units (load power supply for 20 or 40 a) which do not meet this condition can be adapted to this requirement by connecting a 10000  f/40 v capacitor in parallel. 10000 m f/ 40v cc/eu f+ l+ 230v ac i/o modules load power supply 24v power supply separate or common shutdown of the cc/eu and load power supply common shutdown of the cc/eu and load power supply with a 230 v ac supply di g ital input/output modules
8-8 system manual c79000-g8576-c199-07 8.1.3 special features of the 432 digital input module the 432 digital input module accepts 32 process signals and emits a process alarm if the logic state at one of its inputs changes. you can operate the module in the following modes:  without process alarm (anormalo digital input module)  with initiation of a process alarm via interrupt  with initiation of a process alarm via ib 0 (only in conjunction with cpu 948) to operate the module with process alarm via ib 0, you must address it in the normal (p) area from byte 128 because  the automatic updating of the process image might acknowledge a process alarm without the system program having detected and interpreted this alarm;  only modules addressed in the normal (p) area can initiate a process alarm via ib 0. the time for reaction of the module to a process alarm is mainly determined by the input circuitry. you can set the reaction time to one of the values 0.3 ms, 1 ms or 3 ms with switch s5. note that the filtering effect decreases with shorter reaction times, and interference may be received as useful signals (effect of the line length, see the technical specifications). to operate the module without process alarm, you can insert it at any slot for i/o modules and address it in the entire i/o area. if you address it in the area pb/py 0 to pb/py 124, it will be within the automatic updating of the process image. make the following settings on the module to operate it without process alarm: step action 1 open jumpers x3 and x4 2 set switch rows s1 and s2 to off s1 3 3 bit 3 ir-d 4 4 bit 4 ir-e 5 5 bit 5 ir-f 6 6 bit 6 ir-g 7 7 bit 7 int 0 0 bit 0 ir-a 1 1 bit 1 ir-b 2 2 bit 2 ir-c :off :on s2 figure 8-3 switch settings for operation without process alarm the setting for switch row s3 is arbitrary in this mode. modes reaction time operation without process alarm settings on the module di g ital input/output modules
8-9 system manual c79000-g8576-c199-07 to operate the 432 digital input module with process alarm via an interrupt, you must either operate it in the cc where only certain slots have interrupt lines (see chapter 4), or in an interrupt-capable eu connected to the cc with im 307 - im 317 interfacing (see also the im 307 - im 317 manual). in the cc, you may only operate the module in this mode at slots with an interrupt line (interrupt source). so that the module can initiate a process alarm for a change of logic state, the alarm must be processed by an alarm routine (alarm ob) in the user program, with automatic acknowledgement of the alarm. to avoid loss of an alarm, it must not be possible for the alarm ob to be interrupted by process alarms. the cpu must process the process alarms with level triggering (see programming guide of the cpu). example: program the following operations in the corresponding alarm ob: l pw132 (load i/o word) t fw10 (transfer flag word) l pw134 etc. t fw12 only the flag word may be accessed during the cyclic program. accessing the i/o bytes in the process image will result in alarm loss. addressing of the module must therefore be above address 127. double accessing of i/o bytes, even from different cpus, is not permissible (alarm loss). the four i/o bytes of a module must be scanned successively and in ascending order. the scanning of byte n inhibits all input circuits of the module, and the scanning of byte (n + 3) enables them again. make the following settings on the module to operate it with a process alarm via interrupt: step action 1 open jumper x4 and close jumper x3. 2 set the interrupt line at switch row s1: the switch relating to the desired interrupt line should be set to on. set all other switches to off. you can set the same interrupt line on several modules. 3 set switch row s2 to off. 4 set switch row s3 to choose whether the interrupt is to be initiated with a positive-going (leading) or negative-going (trailing) edge. the setting of a pair of switches applies to an entire byte. operation with process alarm via interrupt scanning the process inputs settings on the module di g ital input/output modules
8-10 system manual c79000-g8576-c199-07 s1 3 3 3 bit 3 ir-d 4 4 4 bit 4 ir-e 5 5 5 bit 5 ir-f 6 6 6 bit 6 ir-g 7 7 7 bit 7 int 0 0 0 bit 0 ir-a 1 1 1 bit 1 ir-b 2 2 2 bit 2 ir-c process interrupt via ir-c byte 0: positive-going edge byte 1: negative-going edge byte 2: both edges byte 3: no process interrupt byte 0 byte 1 byte 2 byte 3 s2 s3 } } } } : off : on figure 8-4 switch settings for operation with process alarm via interrupt (example) in this mode, a process alarm is initiated via input byte ib 0. this mode is only possible in conjunction with a cpu 948 in single-processor operation. to operate the 432 digital input module with process alarm via ib 0, you can insert it at any i/o slot. when you use the module in the cc, you must not set any other input module to address 0 (i.e. neither in the normal (p) nor in the extended (o) area). if you use the module in an eu which is addressed in the normal area, you must not set any other input module in the eu to address 0 in the normal area. so that the module can initiate a process alarm for a change of logic state, the alarm must be processed by an alarm routine (alarm ob) in the user program, with automatic acknowledgement of the alarm. to avoid loss of an alarm, it must not be possible for the alarm ob to be interrupted by process alarms. the cpu must process the process alarms with level triggering (see programming guide of the cpu). example: program the following in the alarm ob which you have preset with byte ib 0 and switch s2: l pw128 (load i/o word) t fw0 (transfer flag word) l pw130 etc. t fw2 operation with process alarm via ib 0 scanning the process inputs di g ital input/output modules
8-11 system manual c79000-g8576-c199-07 only the flag word (fw) may be accessed during the cyclic program. accessing the i/o bytes in the process image will result in alarm loss. addressing of the module must therefore be above address 127. double accessing of i/o bytes, even from different cpus, is not permissible (alarm loss). the four i/o bytes of a module must be scanned successively and in ascending order. the scanning of byte n inhibits the input circuit of the module, and the scanning of byte (n + 3) enables them again. make the following settings on the module to operate it with a process alarm via ib 0: step action 1 insert jumpers x3 and x4 2 set switch row s1 to off. 3 set bit 0 on switch row s2 to on, and all other switches to off. 4 set switch row s3 to choose whether the interrupt is to be i nitiated with a positive-going (leading) or negative-going (trailing) edge. the setting of a pair of switches applies to an entire byte. s1 3 3 3 bit 3 ir-d 4 4 4 bit 4 ir-e 5 5 5 bit 5 ir-f 6 6 6 bit 6 ir-g 7 7 7 bit 7 int 0 0 0 bit 0 ir-a 1 1 1 bit 1 ir-b 2 2 2 bit 2 ir-c s2 s3 byte 0 byte 1 byte 2 byte 3 } } } } :off :on byte 0: positive-going edge byte 1: negative-going edge byte 2: both edges byte 3: no process interrupt figure 8-5 switch settings for operation with process alarm via ib 0 (example) settings on the module di g ital input/output modules
8-12 system manual c79000-g8576-c199-07 you can use up to eight 432 digital input modules with process alarm via ib 0 in one plc. the modules must all be inserted in the cc or in the same eu for error-free acknowledgement of address 0. each module reserves one bit in ib 0. you must set one module to bit 0 on switch row s2; on the other modules you must remove jumper x3 and set one of the other bits 2 to 8. the module you have set to bit 0 is known as the master, and the other modules are slaves. on the master module, you must additionally set the number of slave modules on switch row s2. refer to the labeling on the module cover. you can also use the 432 digital input module with process alarm together with other alarm-generating modules. to operate the module with process alarm via interrupt, you must observe the following:  if a process alarm is generated via an interrupt, the i/o words of all 432 digital input modules involved in this process alarm must be read in the alarm-processing ob; with ips, the process alarms must be acknowledged (refer to the manuals of the ips).  the modules must be inserted at interrupt-capable slots (see chapter 4). to operate the module with process alarm via ib 0, you must observe the following:  you may use up to eight alarm-generating modules.  the modules must all be inserted in the cc or all in the same eu.  you must operate the 432 module as the master. if you use two or more 432 digital input modules with other alarm-generating modules, you must operate one 432 as the master and all others as slaves. 8.1.4 special features of the di/dq 482 the di/dq 482 digital input/output module (6es5482-4ua11) is a process signal i/o module which allows the processing of process signals in conjunction with the ip 257, with the s5-135u/155u plc and the eu 185u (see the ip 257 manual). the di/dq 482 (6es5482-4ua20) has an identical functionality, but not an interface which allows a connection to the ip257. the following section describes the operation of the di/dq 482 without ip 257 . the di/dq 482 has 32 channels which are jointly isolated, i.e. there is no subdivision into groups in the module. channels 0.0 to 0.7 are digital outputs, channels 2.0 to 3.7 are digital inputs; channels 1.0 to 1.7 can be optionally and individually operated as inputs or outputs. using two or more 432 digital input modules with process alarm via ib 0 using the 432 digital input module with other alarm- generating modules di g ital input/output modules
8-13 system manual c79000-g8576-c199-07 the operation of channels 1.0 to 1.7 as inputs or outputs merely depends on the user program. you define the byte as an input with a read access to the di/dq; you define the byte as an output with a write access. the double-function of the byte also allows the output byte to be read out. unused channels should not be wired nor addressed by program. when these channels are used as inputs, it should be noted that the corresponding bits in the output register remain at logic 0. this resetting of output registers is executed automatically after power-up of the plc or eu. note when at least one of channels 1.0 to 1.7 is operated as an input, the connected sensors and the 1l+ terminal must have the same power supply. if this is not the case, the input voltage acts on the 1l+ terminal. the resultant supply to the output amplifiers of channels 0.0 to 1.7 causes currents to be drawn via the wired input terminal; these currents may assume different values, depending on the control states of the outputs. with the di/dq 482 (6es5482-4ua11) you must set slide switch s2 to setting 1 for operation without the ip 257. local bus interface slide switch s2 figure 8-6 slide switch s2 on the di/dq 482 changeover of the i/o byte di g ital input/output modules
8-14 system manual c79000-g8576-c199-07 8.2 installation and startup this section describes how to prepare digital input/output modules for installation, and how to install and wire them. 8.2.1 setting the module address you set the module address on the addressing switch. this also establishes the necessary assignments between user program and process connection. the address of the digital input modules (input bytes ib 0 to 255 or 252 for the di/dq 482) and digital output modules (output bytes qb 0 to 255 or 252 for the di/dq 482) is the sum of the binary significances established by depressing the individual rockers in the on setting (  ). the modules are addressed by the step 5 program under their parameters (byte address). you can affix the adhesive label with the desired module address on a labeling field under the addressing switch. suitable labels are supplied with the cc. the switch rockers with which the module address (ib n or qb n) is specified as a decimal number, are marked by dots on the label. do not use a pencil to set the addressing switch. labeling field di g ital input/output modules
8-15 system manual c79000-g8576-c199-07 on setting (switch pressed) addressing switch address bit binary significance of the address bit labeling field for the module address and marked switch settings address (decimal) 128 64 32 16 8 4 2 1 adb7 adb6 adb5 adb4 adb3 adb2 adb1 adb0 figure 8-7 labeling of the addressing switch (extract from module labeling) the address byte under which the module is referenced by the step 5 program is independent of the slot. for modules with 16 or 32 inputs or outputs, i.e. 2 or 4 bytes, only the lowest address (start address) is set for the first byte. the addresses of the following bytes of the same module are decoded on the module. if, for example, the address 20 is set for a 16-bit module (2 bytes), the following address 21 is decoded internally and is no longer available. the next free address would be 22. for a 32-bit module (4 bytes) with start address 20, addresses 21, 22 and 23 would be decoded internally. the next free address would be 24. addresses already assigned must not be set again. however, digital input and output modules may be given the same address because they are referenced by different commands in the user program. start address di g ital input/output modules
8-16 system manual c79000-g8576-c199-07 example digital input module with 8 inputs (ib 23) or digital output module with 8 outputs (qb 23). the address is the sum of binary significances set with the individual coding switches: 23 = 1 + 2 + 4 + 16 = 2 0 + 2 1 + 2 2 + 2 4 on setting (switch pressed) ib 23 (or qb 23) 128 64 32 16 8 4 2 1 adb7 adb6 adb5 adb4 adb3 adb2 adb1 adb0 example digital input module with 32 inputs (ib 80) or digital output module with 32 outputs (qb 80). the address is the sum of binary significances set with the individual coding switches: 80 = 16 + 64 = 2 4 + 2 6 on setting (switch pressed) 128 64 32 16 8 4 2 1 adb7 adb6 adb5 adb4 adb3 adb2 adb1 adb0 ib 80 (or qb 80) di g ital input/output modules
8-17 system manual c79000-g8576-c199-07 the following table is an overview of settings for addressing digital input/output modules. significance byte address 8 channels xxxxxxxxxxxxxxxx xxxxxxxx xxxx 1 2 4 8 1) 128 64 32 16 16 32 48 64 80 96 112 128 144 160 176 192 208 224 01 17 33 49 65 81 97 113 129 145 161 177 193 209 225 241 240 2 18 34 50 66 82 98 114 130 146 162 178 194 210 226 242 3 19 35 51 67 83 99 115 131 147 163 179 195 211 227 243 4 20 36 52 68 84 100 116 132 148 164 180 196 212 228 244 5 21 37 53 69 85 101 117 133 149 165 181 197 213 229 245 6 22 38 54 70 86 102 118 134 150 166 182 198 214 230 246 7 23 39 55 71 87 103 119 135 151 167 183 199 215 231 247 8 24 40 56 72 88 104 120 136 152 168 184 200 216 232 248 9 25 41 57 73 89 105 121 137 153 169 185 201 217 233 249 10 26 42 58 74 90 106 122 138 154 170 186 202 218 234 250 11 27 43 59 75 91 107 123 139 155 171 187 203 219 235 251 12 28 44 60 76 92 108 124 140 156 172 188 204 220 236 252 13 29 45 61 77 93 109 125 141 157 173 189 205 221 237 253 14 30 46 62 78 94 110 126 142 158 174 190 206 222 238 254 15 31 47 63 79 95 111 127 143 159 175 191 207 223 239 255 1) address range for digital input and digital output modules whose signals are not routed via the process image. switch setting on significance 128 64 32 16 8 4 2 1 16 channels 32 channels di g ital input/output modules
8-18 system manual c79000-g8576-c199-07 8.2.2 removing and inserting modules ! warning when removing and inserting the front connector during operation, hazardous voltages of more than 25 v ac or 60 v dc may be present at the module pins. when this is the case at the front connector, live modules may only be replaced by electrical specialists or trained personnel in such a way that the module pins are not touched. during operation, the front connector and module must not be removed or inserted without the enable jumper or active enable circuit. install a digital input/output module as follows: step action 1 release the upper locking bar on the subrack and swivel it upwards and out. 2 insert the module at the desired slot in the subrack and push it back in the guides. 3 latch the module by rotating the locking pin by 90 5 at the lower end of the module. 4 engage the front connector on the support pin of the module and swivel it up. the width of the support pin also provides keying to prevent front connectors from being fitted to the wrong modules (for example 230 v ac front connector on 24 v dc modules). 5 tighten the screw in the upper part of the front connector. di g ital input/output modules
8-19 system manual c79000-g8576-c199-07 remove a digital input/output module as follows: step action 1 release the upper locking bar on the subrack and swivel it upwards and out. 2 slacken the screw in the upper part of the front connector. this causes the front connector to be pressed out of the female connector of the module. contacts f+ and f- of the enable input at the upper end of the front connector are thus opened first. 3 swing the front connector out and lift it away from the support pin of the module. 4 release the module, if necessary, by rotating the locking pin by 90 o . you can pull the module out of the subrack with a grip which swivels outwards. 1 2 3 5 6 4 module front connector support mount support pin figure 8-8 module with front connector 1 screw 2 locking pin 3 support mount 4 support pin 5 grip 6 backplane connector comply with vde specifications 0100 and 0160 to carry out the wiring of the supply and signal lines which are to be connected to the programmable controllers and front connectors of the modules. detailed information on the supply of power, cabinet assembly, cabinet ventilation, cabinet wiring and protective measures can be found in chapter 3. wiring di g ital input/output modules
8-20 system manual c79000-g8576-c199-07 8.2.3 marking of modules for the marking of modules and front connectors, a set of labels is supplied with the modules for the labeling, and a set of labels with the addresses is supplied with the central controller. figure 8-9 shows the locations of the labels. the self-adhesive address label is preprinted. you can mark the strips to identify the signal line terminals. 5 1 13 4 2 figure 8-9 marking and labeling of modules 1 address label with the module address (output byte qb n or input byte ib n) under which the module is addressed by the step 5 program (address labels are supplied with the plc), and for marking the addressing switch settings 2 labeling strip with the product designation which is color-coded to distinguish between the various module types, as well as fields to mark the version and for user-related labeling of channels. color codes: digital inputs for dc voltage blue digital inputs for ac voltage red digital outputs for dc voltage green digital outputs for ac voltage orange update the version when replacing modules! 3 label with module address and marking of the required settings for the addressing switch 4 labeling strip for terminal designations or connection diagrams for the front connector 5 name plate di g ital input/output modules
8-21 system manual c79000-g8576-c199-07 8.2.4 connecting the signal lines the modules have 20 or 42-pin blade connectors with contact blades measuring 2.4 x 0.8 mm. front connectors for 20 and 40 mm mounting width with crimp connection and 40 mm mounting width with screw connection are provided to connect the signal lines (screwdriver blade width: 3.5 mm, maximum torque: 0.8 nm). use stranded conductors to facilitate handling of the front connector. when the crimp contact is inserted in the plastic body of the front connector, a click can clearly be heard. this indicates that the contact is engaged. for jumpering or to correct the wiring, you can remove the contacts with a releasing tool (see ordering information) without having to pull out the front connector. ferrules are not required for screw connections, because the screw terminals are provided with wire protection. you can use ferrules of 7 mm in length according to din 46228. the maximum terminal area is 2 x 2.5 mm 2 . terminal type connector type 6es5 max. no of cross-sec. of signal or connector for rated voltage front connector module 6es5- t ype t ype 6es5 497- n o. o f contacts si gna l or supply r a t e d v o lt age c onnec t or width for operation 497 contacts supply conductor w dth with fan without fan crimp connection 4ua12 42 0.5 to 1.5 mm 2 5 to 60 v dc 20 mm 420. 430. 431, 432. 434, 441, 451, 454-14, 458 - 4ua22 42 0.5 to 1.5 mm 2 5 to 60 v dc 40 mm 453, 454, 457 420. 430. 431, 432. 434, 441, 451, 453, 454, 457, 458 4ua42 20 0.5 to 1.5 mm 2 24 to 230 v ac 40 mm 435, 436, 455, 456 screw connection 4ub12 4ub32 42 0.5 to 2 x 2.5 mm 2 5 to 60 v dc 40 mm 20 mm 420. 430. 431, 432. 434, 441, 451, 453, 454, 457, 458 4ub22 25 0.5 to 2 x 2.5 mm 2 5 to 60 v dc 40 mm 454 4ub42 20 0.5 to 2 x 2.5 mm 2 24 to 230 v ac 40 mm 435, 436, 455, 456 di g ital input/output modules
8-22 system manual c79000-g8576-c199-07 ! caution only extra-low voltage  60 v dc with safety separation from system voltage may be used for the 24 v dc supply and for the 24 v dc input signals. safety separation can be implemented to the requirements of, amongst other sources, vde 0100 part 410/hd 384-4-41/iec 60364-4-41 (as functional extra-low voltage with safety separation) or vde 0805/en 60950/iec 60950 (as safety extra-low voltage selv) or vde 0106 part 101. 8.2.5 connection of outputs in parallel and switching on the load via a contact ! caution the parallel connection of outputs to increase the load is not permissible. outputs of modules with the same load voltage supply may be connected in parallel without additional circuitry. an external diode must be fitted to the output lines of modules fed from different load voltage supplies (exception: 453, 457). in the case of different logic states of the two outputs, the maximum permissible output current corresponds to that of the lower stage. the contact (for ex. for manual operation) is connected to one of the two l+. 2l+ output 2 2l- load manual a1 a2 1l+ 1l- output 1 figure 8-10 parallel connection of outputs for dc voltage outputs outputs can be connected in parallel without increasing the load if they are connected to the same phase (l) and the same neutral conductor (n). the load must be at least 50 ma per output to keep to the permissible residual voltage at logic 0. the maximum switching current of 2 a per load must not be exceeded. digital output modules for dc voltage digital output modules for ac voltage di g ital input/output modules
8-23 system manual c79000-g8576-c199-07 the load can also be switched via a contact. output 1 output 2 elr phase (l) load neutral (n) elr = electronic load relay elr manual figure 8-11 parallel connection of outputs for ac voltage outputs given here are two examples of the feeding of inputs and outputs of different modules from two power supply units. with non-floating input/output modules, the negative terminals (l-) of the power supply units are connected to reference potential (pe) because the inputs of the 420 module are referred to chassis ground. reference potential + + dq e.g. 441 0 v + + dq e.g. 441 0 v 0 v e.g. 420 di 0 v e.g. 420 di 2l+ 1l+ ii ii iii ii ac 230v dc 24v + _ + _ ac 230v dc 24v l _ q lql qq qq lqq l central ground point or rack or the cc/eu and connection to protective conductor (pe) figure 8-12 feeding of non-floating input/output modules from two power supply units connection of input/output modules to two power supply units di g ital input/output modules
8-24 system manual c79000-g8576-c199-07 with isolated input/output modules the supply voltage is applied separately to the individual modules. dq e.g.453 0 v dq e.g.451 0 v 0 v e.g.430 di 0 v e.g.431 di 1l+ l + l _ ii i ii i i l _ l _ l _ l _ l _ 1l _ 2l+ 2l _ q qq q l + q l + l _ q lq lq lq l ++ ++ ac 230v dc 24v ac 230v dc 24v + _ + _ reference potential and connection to protective conductor (pe) figure 8-13 feeding of isolated input/output modules from two power supply units with isolated modules, the inputs or outputs can be fed from two separate power supply units in isolation groups created by the internal distribution in the module. note that when inputs or outputs from two isolated groups are connected to one power supply unit, isolation between the groups is defeated. 8.2.6 short-circuit protection and fusing with digital output modules for dc voltage, fuses are provided on the module, in addition to the electronic short-circuit protection, for the wiring cables and to protect the module. the fuses also provide protection against reversal of supply voltage connections and can only be replaced at the factory. the electronic short-circuit protection guaranteed in the technical specifications applies to a resistance which is lower than the specified, maximum permissible line resistance. in the event of a short-circuit, two to three-times the rated output current flows briefly at the output before the switched electronic short-circuit protection becomes effective. when selecting the load power supply units, therefore, allow for the increased short-circuit current as well as all connected output loads (observe the coincidence factor). with unregulated load power supplies, this overcurrent is generally ensured. with regulated load power supplies, especially at low output power levels (up to 20 a), you must allow for a corresponding overcurrent. di g ital input/output modules
8-25 system manual c79000-g8576-c199-07 8.2.7 quenching for inductive loads note digital output modules have integrated circuits on the module to quench inductive loads (refer to the technical specifications of the output modules). exception : the 458 digital output module allows the switching of inductive loads with contact protection submodules. the integrated circuits on the modules for quenching inductive loads are disabled if the load circuits are interrupted, either  operationally by contacts and switches,  or by fuses in the event of a fault. this can result in excessive, inductive breaking voltages which put fault-free operation at risk. you can prevent this with additional, external quenching circuitry for the inductive loads. l- n digital output digital output ac voltage dc voltage l+ l contact, switch contactor, solenoid valve, etc. quenching device (diode, zener diode, r/c network or varistor) elr elr elr figure 8-14 quenching of inductive loads when the load circuit is opened di g ital input/output modules
8-26 system manual c79000-g8576-c199-07 external quenching circuitry is needed when  the switching frequency of an output is greater than that specified in the technical specifications (thermal stress of the integrated circuit for quenching inductive loads);  disconnection of output lines can be expected;  disconnection of the supply line can be expected. when selecting or designing the quenching circuitry, the technical specifications for the digital output should be taken into account. these are:  the permissible overvoltage for the supply voltage (see section 8.3 acommon technical specificationso)  inductive breaking voltage of the output (see section 8.4 adescription of individual moduleso) an external quenching circuit only provides thermal relief if its quenching voltage is lower than the breaking voltage specified for the module, allowing for unfavorable supply voltage conditions. example: 453 digital output inductive breaking voltage l+ - 47 v (tech. specifications) max. supply voltage l+ = 30 v quenching voltage referred to l- (0 v ground) is - 17 v the quenching device must be rated at approximately 15 v and the switched load current, for example, 1 a. a quenching device rated for the induced breaking current must be provided at the load (see figure 8-14). the quenching voltage at the load is independent of the module. the quenching devices must also ensure that the overvoltages at the switch and in the wiring do not exceed the disturbance voltage and voltage hazard limits permissible to vde/iec. the following applies to digital outputs for dc voltage: in general, load power supplies should be switched on the primary side to utilize the low-resistance secondary winding and smoothing capacitors of the power supply for energy compensation in the dropping of inductive loads. the load power supply switch should only be considered as a circuit breaker. with switched-through digital outputs and disconnection of the supply line l+, the output current is maintained during the quenching time by capacitors and the reverse voltage protection diode on the module. this severe electrical stress of the module should be avoided during operations, because it can result in a fault in the long term. external quenching circuitry switching frequency of the output is higher than the permissible value disconnecting the load circuit disconnecting the supply line l+ and l switched-through outputs di g ital input/output modules
8-27 system manual c79000-g8576-c199-07 with two-wire switches and ac voltage outputs: disconnection of the supply voltage during operation is not permissible without additional protective circuitry. quenching of the inductive load is achieved here via the load power supply unit or system. since, as two-wire switches, the outputs have no l-/n (0 v ground) terminal, the inductive load cannot be quenched on the module when the supply line is disconnected. with the 453 and 457 modules using two-wire switches, the overvoltages can result in destruction of the module. if the load voltage must be switched for safety reasons, you must provide external quenching circuitry at each inductive load (see figure 8-15). instead, with the 453 and 457 modules using two-wire switches, you can insert a quenching device (diode) with adequate ratings after contact k from the l+ line to l-. digital output dc voltage digital output ac voltage l+ l n l- contact, switch contactor, solenoid valve, etc. quenching device (diode, zener diode, r/c network or varistor) common diode only on 453/457 elr elr elr figure 8-15 quenching of inductive loads when switching the supply line l+ and l two-wire switches di g ital input/output modules
8-28 system manual c79000-g8576-c199-07 8.3 common technical specifications important for the usa and canada the following approvals have been obtained for all the modules listed in this chapter:  ul listing mark underwriters laboratories (ul) to standard ul 508, report e 85972  csa certification mark canadian standard association (csa) to standard c 22.2 no. 142, report lr 63533 valid safety specifications vde 0160 class of protection i degree of protection ip 20 to iec 60529/din 40050 when empty slots are covered by dummy front plates climatic ambient conditions operation in equipment with fan 0 to 55 c operation in equipment without fan (module clearance: 40 mm) 0 to 55 c supply air measured at lower inlet of power supply; for a cabinet assembly, note that the removable power dissipation depends on the cabinet design, its ambient temperature and arrangement of equipment. transportation and storage temperature -40 to 70 c temperature variation in operation transportation and storage 10 k/h max. 20 k/h max. (when delivered under 0 o c, allow 3 h min. settling time on account of possible condensation) relative humidity in operation transportation and storage 95 % max. at 25 o c, no condensation 95 % max. at 25 o c, no condensation site altitude in operation transportation and storage -1000 m to +1500 m -1000 m to +3500 m pollutants s0 2 h 2 s 0.5 ppm max. (rel. humidity under 60 %) 0.1 ppm max. (rel. humidity under 60 %) mechanical ambient conditions vibration in operation 10 to 58 hz (const. amplitude 0.15 mm) 58 to 500 hz (const. acceleration 2 g) mechanical requirements installation in stationary equipment which is not free from vibrations; installation on ships and vehicles, allowing for special installation specifications, but not on the engine operand identifiers for inputs i = input for outputs q = output parameters 0.0 to 255.7 di g ital input/output modules
8-29 system manual c79000-g8576-c199-07 terminals rated dc voltage of module l+ reference potential for dc voltage l- rated ac voltage of module l reference potential for ac voltage n permissible line length for digital output modules allow for the line resistance and tolerance of the supply voltage for the relevant output current. enable inputs f+ f- (enable voltage according to the rated voltage of the module) short-circuit signaling output (only when the short- circuited output is at logic 1) h+ (supply for 1l+, referred to l- of the module) max. permissible supply voltage for rated voltage 24 v dc (l+/l-) 1) for rated voltage 60 v dc (l+/l-) 1) for rated voltage 115 v/230 v ac (l/n) 36 v dc for 100 ms 90 v dc for 100 ms 276 v ac for 100 ms supply voltage ripple v pp referred to rated dc voltage 15 % max. 2) interference suppression at digital inputs  1.5 ms 3) interference pulse length at digital outputs  1.5 ms 3) 4) circuitry for inductive loads: protective devices to limit the breaking voltage are provided on the digital output modules. additional protective circuitry for the load is only required in exceptional cases. exception : 458 digital output module switching of capacitive loads: 50 nf max. at full load 1) supply and signal voltages must be produced as functional voltage with safety separation. 2) the supply voltage range values are limit values. they include ripple. 3) if not otherwise specified 4) must be bridged by the signal receiver di g ital input/output modules
8-30 system manual c79000-g8576-c199-07 8.4 specification sheets for the modules the common technical specifications are given in section 8.3. 8.4.1 6es5 420-4ua13/4ua14 digital input module -4ua13 -4ua14 rated input voltage 24 v dc number of inputs 32 isolation no input voltage for logic 0 for logic 1 -33 to 5 v 13 to 33 v rated input current 8.5 ma input frequency 100 hz max. delay time 3 ms typical (1.4 to 5 ms) input resistance 2.8 kohm typical coincidence factor (total load capability) 100 % permissible line length 600 m max., unshielded; 1000 m max., shielded power supply digital section from system bus 5 v, 80 ma typical 5 v, 30 ma typical supply voltage for 2-wire bero 22 to 33 v power dissipation (rated operation) 7.0 w enable input (f+/f-) rated input voltage 24 v dc input voltage for logic 0 for logic 1 -33 to 5 v 13 to 33 v rated input current 5 ma permissible line length 200 m max. mechanical specifications dimensions (w x h x d) 20 mm x 255 mm x 195 mm weight approx. 0.4 kg di g ital input/output modules
8-31 system manual c79000-g8576-c199-07 1i0.0 1i0.1 1i0.3 1i0.4 1i0.5 1i0.6 1i0.7 1i0.2 1i1.0 1i1.1 1i1.2 1i1.3 1i1.4 1i1.5 1i1.6 1i1.7 1i2.0 1i2.1 1i2.2 1i2.3 1i2.4 1i2.5 1i2.6 1i2.7 1i3.0 1i3.1 1i3.2 1i3.3 1i3.4 1i3.5 1i3.6 1i3.7 f+ 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g t 2) 2) 2) 2) 2) 2) 2) 2) t t t g t t t t t t (l-) data memory and s5 bus control 1) x20 m ext. m ext. front strip led pin l+ connection of process signal lines example of connection designation for an input: input 5 (5th bit); 0 to 7 possible address of input byte (1st byte); 0 to 255 possible i = input 1st group (not specified in the address) (1) i 1.5 block diagram of module inputs l- g = green led (status indicator) f+ = enable input connect l- of the power supply unit to the reference potential (pe). 1) changeover of enable mode with jumper x20: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. 2) the terminal is not connected internally. even when this terminal is connected to input voltages, the clearances in air and leakage paths remain adequate to ul, csa and vde. di g ital input/output modules
8-32 system manual c79000-g8576-c199-07 8.4.2 6es5 430-4ua13/4ua14 digital input module -4ua13 -4ua14 rated input voltage 24 v dc number of inputs 32 isolation yes, 1 group with 32 inputs input voltage for logic 0 for logic 1 1) -3 to 7 v 13 to 33 v -33 to 7 v 13 to 33 v rated input current 7.0 ma input frequency 100 hz max. delay time 4 ms typical (2.5 to 6.5 ms) 3 ms typical (1.4 to 5.0 ms) input resistance 3.3 kohm typical coincidence factor (total load capability) 100 % permissible line length 600 m max., unshielded; 1000 m max., shielded power supply digital section from system bus 5 v, 100 ma typical 5 v, 30 ma typical supply voltage for 2-wire bero 22 to 33 v supply voltage l+/l- 24 v (20 to 30 v) l+ to terminal 3 not required current consumption from l+/l- approx. 100 ma l+ not required power dissipation (rated operation) 8.3 w 5.6 w enable input (f+/f-) rated input voltage 24 v dc input voltage for logic 0 for logic 1 -33 to 5 v 13 to 33 v rated input current 5 ma permissible line length 200 m max. voltage test to vde 0160 between group and ground point: 500 v ac mechanical specifications dimensions (w x h x d) 20 mm x 255 mm x 195 mm weight approx. 0.4 kg 1) polarity reversal for up to 8 inputs per module is permissible. di g ital input/output modules
8-33 system manual c79000-g8576-c199-07 1i0.0 1i0.1 1i0.3 1i0.4 1i0.5 1i0.6 1i0.7 1i0.2 1i1.0 1i1.1 1i1.2 1i1.3 1i1.4 1i1.5 1i1.6 1i1.7 1i2.0 1i2.1 1i2.2 1i2.3 1i2.4 1i2.5 1i2.6 1i2.7 1i3.0 1i3.1 1i3.2 1i3.3 1i3.4 1i3.5 1i3.6 1i3.7 l+ f+ l+ l- l+ f- l- l- 3) 4) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g t 2) 2) 2) 2) 2) t t g t t t t t t l- 1) led pin l- x20 shield isolation l+ (1) i 3.5 front strip connection of process signal lines example of connection designation for an input: input 5 (5th bit); 0 to 7 possible address of input byte (3rd byte); 0 to 255 possible i = input 1st group (not specified in the address) block diagram of module inputs data memory and s5 bus control g = green led (status indicator) f+/f- = enable input 1) changeover of enable mode with jumper x20: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. 2) the terminal is not connected internally. even when this terminal is connected to input voltages, the clearances in air and leakage paths remain adequate to ul, csa and vde. 3) by connecting l- to pin 42, a leading and trailing connection to ground is established on the module when it is plugged in and removed. 4) l+ to terminal 3 is not required for -4ua14. di g ital input/output modules
8-34 system manual c79000-g8576-c199-07 8.4.3 6es5 431-4ua12 digital input module rated input voltage 24 to 60 v dc number of inputs 16 isolation yes, 16 inputs input voltage for logic 0 for logic 1 -33 to 8 v 13 to 72 v rated input current 4.5 to 7.5 ma (24 to 60 v dc) input frequency 100 hz max. delay time 3 ms typical (1.4 to 5 ms) coincidence factor (total load capability) 100 % permissible line length 400 m max. unshielded; 1000 m max. shielded power supply digital section from system bus 5 v, 90 ma typical supply voltage for 2-wire bero 22 to 72 v power dissipation (rated operation) 2.2 to 7.7 w (24 to 60 v) enable input (f+/f-) rated input voltage 24 to 60 v dc input voltage for logic 0 for logic 1 -72 to 8 v 13 to 72 v rated input current 5 ma (at 48 v dc) permissible line length 200 m max. voltage test to vde 0160 between two groups: 1250 v ac between group and ground point: 1250 v ac mechanical specifications dimensions (w x h x d) 20 mm x 255 mm x 195 mm weight approx. 0.4 kg di g ital input/output modules
8-35 system manual c79000-g8576-c199-07 f+ 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 g g g g g g g g g g g g g g g g led pin 1l+ 1l- 2l+ 2l- 3l+ 3l- 4l+ 4l- 5l+ 5l- 6l+ 6l- 7l+ 7l- 8l+ 8l- 9l+ 9l- 10l+ 10l- 11l+ 11l- 12l+ 12l- 13l+ 13l- 14l+ 14l- 15l+ 15l- 16l+ 16l- f- l+ l- 2) t 2) 2) 2) 3) 3) 2) 2) t t t t t t t t 1) shield x20 1i0.0 1i0.0 2i0.1 3i0.2 3i0.2 4i0.3 4i0.3 2i0.1 5i0.4 5l0.4 6i0.5 6i0.5 7i0.6 7i0.6 8i0.7 8i0.7 9i1.0 9i1.0 10i1.1 10i1.1 11i1.2 11i1.2 12i1.3 12i1.3 13i1.4 13i1.4 14i1.5 14i1.5 15i1.6 15i1.6 16i1.7 16i1.7 + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - (8) i 0.7 front strip connection of process signal lines example of connection designation for an input: input 7 (7th bit); 0 to 7 possible address of input byte (byte 0); 0 to 255 possible i = input 8th group (not specified in the address) block diagram of module inputs data memory and s5 bus control g = green led (status indicator) f+/f- = enable input 1) changeover of enable mode with jumper x20: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. 2) the terminal is not connected internally. when this terminal is connected to the input voltages, the clearances in air and leakage paths are no longer adequate to ul and csa, but comply with vde. 3) the terminal is not connected internally. when this terminal is connected to the input voltages, the clearances in the air and leakage paths remain adequate to ul, csa and vde. di g ital input/output modules
8-36 system manual c79000-g8576-c199-07 8.4.4 6es5 432-4ua12 digital input module rated input voltage 24 v dc number of inputs 32 isolation yes, 4 groups of 8 inputs input voltage for logic 0 for logic 1 -33 to 5 v 13 to 33 v rated input current 8.5 ma input frequency 100 hz / 300 hz / 1 khz max. delay time 1) 3 ms / 1 ms / 0.3 ms typical (1.5 to 4.8 ms/0.5 to 1.6 ms/0.15 to 0.48 ms) input resistance 2.8 kohm typical coincidence factor (total load capability) 100 % permissible line length 600 m max. unshielded (3 ms); 200 m max. unshielded (1 ms); 50 m max. unshielded (0.3 ms) power supply digital section from system bus 5 v, 130 ma typical supply voltage for 2-wire bero 22 to 33 v power dissipation (rated operation) 7.5 w enable input (f+/f-) rated input voltage 24 v dc input voltage for logic 0 for logic 1 -33 to 5 v 13 to 33 v rated input current 5 ma permissible line length 200 m max. voltage test to vde 0160 between two groups: 500 v ac between group and ground point: 500 v ac mechanical specifications dimensions (w x h x d) 20 mm x 255 mm x 195 mm weight approx. 0.4 kg 1) selectable in bytes with switch s5 di g ital input/output modules
8-37 system manual c79000-g8576-c199-07 1i0.0 1i0.1 1i0.3 1i0.4 1i0.5 1i0.6 1i0.7 1i0.2 2i1.0 2i1.1 2i1.2 2i1.3 2i1.4 2i1.5 2i1.6 2i1.7 3i2.0 3i2.1 3i2.2 3i2.3 3i2.4 3i2.5 3i2.6 3i2.7 4i3.0 4i3.1 4i3.2 4i3.3 4i3.4 4i3.5 4i3.6 4i3.7 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g 3) 3) 4) 3) g led pin f+ l+ f- l- 1l+ 1l- 2l+ 2l- 3l+ 3l- 4l+ 4l- t t t t t t t t t 1) x20 shield (4) i 3.5 front strip connection of process signal lines example of connection designation for an input: input 5 (5th bit); 0 to 7 possible address of input byte (3rd byte); 0 to 255 possible i = input 4th group (not specified in the address) block diagram of module inputs data memory and s5 bus control g = green led (status indicator) f+/f- = enable input 1) changeover of enable mode with jumper x20: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. 2) only 128 to 255 permissible with group signal and interrupt. 3) the terminal is not connected internally. when this terminal is connected to the input voltages, the clearances in air and leakage paths are no longer adequate to ul and csa, but comply with vde. 4) the terminal is not connected internally. when this terminal is connected to the input voltages, the clearances in air and leakage paths remain adequate to ul, csa and vde. di g ital input/output modules
8-38 system manual c79000-g8576-c199-07 labeling for module cover: mark the switch settings in the free fields. x3 master (on) slave (off) delay-time x4 byte 3 ms 1 ms 0.3 ms s5 group signal 3    active (on) 3    inactive (off) 2    2    1 ? ? ? 1    0 ? ? ? 0    edge trigger s3  3 ?    s1 interrupt 3     ira 2     irb 2     irc 1     ird 1     ire 0     irf 0     irg byte int group signal master submodule (jumper x3 on) slave submodule (jumper x3 off) data bit without slave 1 slave 2 slave 3 slave 4 slave 5 slave 6 slave 7 slave 1.slave o.1 2.slave 0.2 3.slave 0.3 4.slave 0.4 5.slave 0.5 6.slave 0.6 7.slave 0.7 s2 0                1                2                3                4                5                6                7                di g ital input/output modules
8-39 system manual c79000-g8576-c199-07 8.4.5 6es5 434-4ua12 digital input module rated input voltage (lh+) dc 5 to 15 v rated input voltage (l+) dc 12 to 24 v (namur) 1) number of inputs 32 isolation yes, 1 group of 32 inputs input voltage ttl: for logic 0 for logic 1 cmos: for logic 0 for logic 1 0 to 0.8 v 2.4 to 5.0 v 0 v to 0.3 x lh+ 0.7 v x lh+ to 1 x lh+ rated input current ttl: for logic 0 for logic 1 cmos: for logic 0 for logic 1 namur: for logic 0 for logic 1 -1 ma 0.1 ma or open input -1 to -3 ma (5 to 15 v) 0.1 to 0.3 ma (5 to 15 v)  1.2 ma  2.1 ma internal resistance 1 kohm typical line resistance 50 ohm max. input frequency 100 hz max. delay time for positive-going edge for negative-going edge 3 ms typical (1.4 to 5 ms) 3 ms typical (1.4 to 5 ms) coincidence factor (total load capability) 100 % permissible line length ttl/cmos namur 200 m max. unshielded 600 m max. unshielded power supply digital section from system bus 5 v, 80 ma typical supply voltage l+/l- 24 v (20 to 30 v) current consumption at l+/l- 100 ma each current consumption at lh+/lh- 150 ma each at 15 v input voltage current output from lh+/lh- 120 ma each at 8.5 v sensor supply (namur) 2) power dissipation (rated operation) 5.5 w enable input (f+/f-) rated input voltage 5/ 15/ 24 v dc input voltage for logic 0 for logic 1 -15 to 2 v 4 to 33 v rated input current 5 ma permissible line length 100 m max. voltage test to vde 0160 between group and ground point: 500 v ac mechanical specifications dimensions (w x h x d) 20 mm x 255 mm x 195 mm weight approx. 0.45 kg 1) namur = sensor with current output to en 50227, standards committee for measurement and control. however, the module is not intrinsically safe. 2) the current consumption from l+/l- increases accordingly. di g ital input/output modules
8-40 system manual c79000-g8576-c199-07 connection for supply voltage, jumpers and sensor supply in groups of 2 bytes (16 inputs each) byte 0 + 1 byte 2 + 3 1l+ terminal 3 2l+ terminal 24 1lh+ terminal 12 2lh+ terminal 33 1lh- terminal 22 2lh- terminal 23 y type of sensor namur connect to l+ (24 v supply) output for sensor supply jumper to l- terminal 21 cmos open connect to 5 to 15 v supply open ttl open connect to 5 v supply open the types of sensor can be arbitrarily mixed in groups of 16 inputs. with cmos ttl sensors, open inputs are at logic 1 (led is lit). di g ital input/output modules
8-41 system manual c79000-g8576-c199-07 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g t t t g t t t t t t l- 1) front strip led pin l- x20 shield isolation 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 . . . . . . . . . . . lh+ l- l- ttl/cmos . . . . . . . . . . . 1lh+ q q q q q q q q ttl/cmos lh+ lh+ sensors with ttl- and/or cmos outputs sensor supply +/- l- = 0v ttl lh+ = 5v : cmos : lh+ = 5...15v l- = 0v + _ + _ + _ + _ + _ + _ + _ + _ l- 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 l+ l- l+ l- namur l- 1lh- 2lh- 1i0.0 1i0.1 1i0.3 1i0.4 1i0.5 1i0.6 1i0.7 1i0.2 1i1.0 1i1.1 1i1.2 1i1.3 1i1.4 1i1.5 1i1.6 1i1.7 f+ f- 1l+ 1lh+ sensor supply lh+ from l+ = 24v 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 namur 2l+ 1i2.0 1i2.1 1i2.2 1i2.3 1i2.4 1i2.5 1i2.6 1i2.7 1i3.0 1i3.1 1i3.2 1i3.3 1i3.4 1i3.5 1i3.6 1i3.7 2lh+ l- l+ namur- and til/cmos sensors (can be connected . . . . . . . . . . . . . . . . . . . . . . connection of namur sensors in groups of 16) data memory and s5 bus control 1i2.0 1i2.1 1i2.2 1i2.3 1i2.4 1i2.5 1i2.6 1i2.7 1i3.0 1i3.1 1i3.2 1i3.3 1i3.4 1i3.5 1i3.6 1i3.7 2lh+ l- 1i0.0 1i0.1 1i0.3 1i0.4 1i0.5 1i0.6 1i0.7 1i0.2 1i1.0 1i1.1 1i1.2 1i1.3 1i1.4 1i1.5 1i1.6 1i1.7 f+ f- (1) i 3.5 g = green led (status indicator) f+/f- = enable input 1) changeover of enable mode with jumper x20: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. connection of process signal lines block diagram of module inputs connection of process signal lines example of connection designation for an input: input 5 (5th bit); 0 to 7 possible address of input byte (1st byte); 0 to 255 possible i = input 1st group (not specified in the address) di g ital input/output modules
8-42 system manual c79000-g8576-c199-07 8.4.6 6es5 435-4ua12 digital input module rated input voltage 24 to 60 v ac (47 to 63 hz) number of inputs 16 isolation yes, 2 groups of 8 inputs input voltage for logic 0 for logic 1 0 to 15 v ac 20 to 72 v ac rated input current bei ac 48 v bei ac 60 v 15 ma typical 20 ma typical input current for 2-wire bero for logic 0 for logic 1  5 ma  10 ma input frequency 20 hz max. as pulse train delay time for positive-going edge for negative-going edge 5 ms typical (2 to 15 ms) 20 ms typical (10 to 25 ms) input resistance 3 kohm typical coincidence factor (total load capability) ventilated not ventilated 100 % 75 % at 60 v; 100 % at 35 o c; 100 % at 30 v permissible line length 600 m max. unshielded 1000 m max. shielded power supply digital section from system bus 5 v, 100 ma typical power dissipation (rated operation) 3.5 w at 24 v, 18.0 w at 60 v enable input (f+/f-) jumper in front connector voltage test to vde 0160 between two groups: 2000 v ac; between group and ground point: 1500 v ac mechanical specifications dimensions (w x h x d) 40 mm x 255 mm x 195 mm weight approx. 0.55 kg di g ital input/output modules
8-43 system manual c79000-g8576-c199-07 1n 1i0.1 1i0.2 1i0.0 1i0.4 1i0.5 1i0.6 1i0.7 2n 2i1.0 2i1.1 2i1.2 2i1.4 2i1.5 2i1.6 2i1.7 2l f+ f- 1 2 4 6 8 10 12 14 16 18 20 25 27 29 31 33 35 37 39 41 g g g g g g g g g g g g g g g g led pin shield 1n 1i0.3 2i1.3 2n t t t t t t t t t t t t t t t t isolation isolation 1) x20 t +5v (2) i 1.2 front strip connection of process signal lines example of connection designation for an input: input 2 (2nd bit); 0 to 7 possible address of input byte (1st byte); 0 to 255 possible i = input 2nd group (not specified in the address) block diagram of module inputs data memory and s5 bus control g = green led (status indicator) f+/f- = enable input (jumper in front connector) 1) changeover of enable mode with jumper x20: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. di g ital input/output modules
8-44 system manual c79000-g8576-c199-07 8.4.7 6es5 436-4ua12 digital input module rated input voltage 115 to 230 v ac (47 to 63 hz) number of inputs 16 isolation yes, 2 groups of 8 inputs input voltage for logic 0 for logic 1 0 to 60 v ac 90 to 264 v ac rated input current at 115 v ac at 230 v ac 15 ma typical 25 ma typical (2-wire-bero can be connected) input frequency 20 hz max. as pulse train delay time for positive-going edge for negative-going edge 5 ms typical (2 to 15 ms) 20 ms typical (10 to 25 ms) input resistance 10 kohm typical coincidence factor (total load capability) ventilated not ventilated 100 % 75 % at 230 v ac; 100 % at 35 o c; 100 % at 115 v ac permissible line length 600 m max. unshielded 1000 m max. shielded power supply digital section from system bus 5 v, 100 ma typical power dissipation (rated operation) 3.5 w at 115 v, 17.0 w at 230 v enable input (f+/f-) jumper in front connector voltage test to vde 0160 between two groups: 2000 v ac; between group and ground point: 1500 v ac mechanical specifications dimensions (w x h x d) 40 mm x 255 mm x 195 mm weight approx. 0.55 kg di g ital input/output modules
8-45 system manual c79000-g8576-c199-07 1n 1i0.1 1i0.2 1i0.0 1i0.4 1i0.5 1i0.6 1i0.7 2n 2i1.0 2i1.1 2i1.2 2i1.4 2i1.5 2i1.6 2i1.7 1l f+ f- 1 2 4 6 8 10 shield 1n 1i0.3 2i1.3 2n t t t t t t t 12 14 16 18 20 25 27 29 31 33 35 37 39 41 g g g g g g g g g g g g g g g g led pin t t t t t t t t t isolation isolation 1) x20 t +5v 2l (1) i 0.4 front strip connection of process signal lines example of connection designation for an input: input 4 (4th bit); 0 to 7 possible address of input byte (byte 0); 0 to 255 possible i = input 1st group (not specified in the address) block diagram of module inputs data memory and s5 bus control g = green led (status indicator) f+/f- = enable input (jumper in front connector) 1) changeover of enable mode with jumper x20: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. di g ital input/output modules
8-46 system manual c79000-g8576-c199-07 8.4.8 6es5 436-4ub12 digital input module rated input voltage 115 to 230 v ac (47 to 63 hz) number of inputs 8 isolation yes, 8 inputs input voltage for logic 0 for logic 1 0 to 60 v ac 90 to 264 v ac rated input current at 115 v ac at 230 v ac 15 ma typical 25 ma typical (2-wire-bero can be connected) input frequency 20 hz max. as pulse train delay time for positive-going edge for negative-going edge 5 ms typical (2 to 15 ms) 20 ms typical (10 to 25 ms) input resistance 10 kohm typical coincidence factor (total load capability) 100 % permissible line length 600 m max. unshielded 1000 m max. shielded power supply digital section from system bus 5 v, 80 ma typical power dissipation (rated operation) 2.0 w at 115 v, 8.5 w at 230 v enable input (f+/f-) jumper in front connector voltage test to vde 0160 between two groups: 2000 v ac; between group and ground point: 1500 v ac mechanical specifications dimensions (w x h x d) 40 mm x 255 mm x 195 mm weight approx. 0.5 kg di g ital input/output modules
8-47 system manual c79000-g8576-c199-07 f+ f- 1 2 4 6 8 10 12 14 16 18 20 25 27 29 31 33 35 37 39 41 g g g g g g g g led pin shield t t t t t t t t t +5v 1n 1n 2n 2n 3n 3n 4n 4n 1i0.0 1l 2i0.1 2l 3i0.2 3l 4i0.3 4l 1) x20 2) 5n 5n 6n 6n 7n 7n 8n 8n 5i0.4 5l 6i0.5 6l 7i0.6 7l 8i0.7 8l 2) (6) i 0.5 front strip connection of process signal lines example of connection designation for an input: input 5 (5th bit); 0 to 7 possible address of input byte (byte 0); 0 to 255 possible i = input 6th group (not specified in the address) block diagram of module inputs data memory and s5 bus control g = green led (status indicator) f+/f- = enable input (jumper in front connector) 1) changeover of enable mode with jumper x20: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. 2) the terminal is not connected internally. when this terminal is connected to input voltages, the clearances in air and leakage paths remain adequate to ul, csa and vde. di g ital input/output modules
8-48 system manual c79000-g8576-c199-07 8.4.9 6es5 441-4ua13/4ua14 digital output module -4ua13 -4ua14 rated supply voltage l+ 24 v dc number of outputs 32, short-circuit protected 1) isolation no range for supply voltage 20 to 30 v dc fusing 6.3 a slow, 1 fuse per 8 outputs 7 a, fast, 1 fuse per 8 outputs output voltage for logic 1 for logic 0 l+ -1.5 v min. 3 v max. switching current (resistive, inductive load) 5 ma to 0.5 a residual current at logic 0 0.5 ma max. switching current for lamps 0.22 a max. (5 w) switching frequency with resistive load with inductive load 100 hz max. 2 hz max. at 0.3 a, 0.5 hz max. at 0.5 a breaking voltage (inductive) limited to l+ - 47 v limited to l+ -55 v total switching current 4 a max. per 8 outputs coincidence factor (total load capability) ventilated not ventilated (in relation to the total switching current) 100 % 50 %; 100 % up to 35 o c permissible line length 400 m max. unshielded power supply digital section from system bus 5 v, 80 ma typical current consumption from l+/l- 24 v, 150 ma typical 24 v, 200 ma typical power dissipation (rated operation) 17.0 w 6.4 w enable input (f+/f-) rated input voltage 24 v dc input voltage for logic 1 for logic 0 13 to 33 v - 33 to 5 v rated input current 5 ma permissible line length 200 m max. short-circuit monitoring short-circuit display red led for 8 outputs signaling output (h+) common for all outputs. the signal a1o is generated when a short circuit occurs at an output. output voltage referred to l- (with feed at 1l+) for logic 1 for logic 0 1l+ - 5 v min. 3 v max. 1l+ -1.5 v min. 3 v max. switching current 10 ma max., limited mechanical specifications dimensions (w x h x d) 20 mm x 255 mm x 195 mm weight approx. 0.45 kg 1) short-circuit protection responds with line resistance  15 ohms, irrelevant for the -4ua14 . di g ital input/output modules
8-49 system manual c79000-g8576-c199-07 (2) q 2.6 1q0.0 1q0.1 1q0.3 1q0.4 1q0.5 1q0.6 1q0.7 1q0.2 1q1.0 1q1.1 1q1.2 1q1.3 1q1.4 1q1.5 1q1.6 1q1.7 2q2.0 2q2.1 2q2.2 2q2.3 2q2.4 2q2.5 2q2.6 2q2.7 2q3.0 2q3.1 2q3.2 2q3.3 2q3.4 2q3.5 2q3.6 2q3.7 f+ 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g 2) 2) 2) 2) 2) g 1) x20 m ext. led pin l- l+ l+ 1l+ r h- h+ l+ 2l+ r r r t short- circuit f1 f2 f3 f4 data memory and s5 bus control front strip connection of process signal lines example of connection designation for an output: output 6 (6th bit); 0 to 7 possible address of output byte (2nd byte); 0 to 255 possible q = output 2nd terminal l+ (not specified in the address) block diagram of module inputs g = green led (status indicator) r = red led (short-circuit indicator) f+ = enable input, referred to 0 v ground connect l- of the power supply unit to the reference potential (pe). 1) changeover of enable mode with jumper x20: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. 2) the terminal is not connected internally. when this terminal is connected to the output voltages, the clearances in air and leakage paths are no longer adequate to ul and csa, but comply with vde. di g ital input/output modules
8-50 system manual c79000-g8576-c199-07 8.4.10 6es5 451-4ua13/4ua14 digital output module -4ua13 -4ua14 rated supply voltage l+ 24 v dc number of outputs 32, short-circuit protected 1) isolation yes, 1 group of 32 outputs range for supply voltage 20 to 30 v dc fusing 6.3 a slow 1 fuse per 8 outputs 7 a fast 1 fuse per 8 outputs output voltage for logic 1 for logic 0 l+ - 1,5 v min. 3 v max. switching current (resistive, inductive load) 5 ma to 0.5 a residual current at logic 0 0.5 ma max. switching current for lamps 0.22 a max. (5 w) switching frequency with resistive load with inductive load 100 hz max. 2 hz max. at 0.3 a; 0.5 hz max. at 0.5 a breaking voltage (inductive) limited to l+ - 47 v limited to l+ -55 v total switching current 4 a max. per 8 outputs coincidence factor (total load capability) ventilated not ventilated (in relation to the total switching current) 100 % 50 %; 100 % up to 35 o c permissible line length 400 m max. unshielded power supply digital section from system bus 5 v, 80 ma typical current consumption from l+/l- 24 v, 150 ma typical 24 v, 200 ma typical power dissipation (rated operation) 17.0 w 6.4 w enable input (f+/f-), rated input voltage 24 v dc input voltage for logic 1 for logic 0 13 to 33 v - 33 to 5 v rated input current 5 ma permissible line length 200 m max. short-circuit monitoring short-circuit display red led for 8 outputs signaling output (h+) common for all outputs. the signal a1o is generated when a short circuit occurs at an output. output voltage referred to l- (with feed at 1l+) for logic 1 for logic 0 1l+ - 5 v min. 3 v max. 1l+ -1,5 v min. 3 v max. switching current 10 ma max. limited voltage test to vde 0160 between group and ground point: 500 v ac mechanical specifications dimensions (w x h x d) 20 mm x 255 mm x 195 mm weight approx. 0.45 kg 1) short-circuit protection responds with line resistance  15 ohms, irrelevant for the -4ua14 . di g ital input/output modules
8-51 system manual c79000-g8576-c199-07 x20 1q0.0 1q0.1 1q0.3 1q0.4 1q0.5 1q0.6 1q0.7 1q0.2 1q1.0 1q1.1 1q1.2 1q1.3 1q1.4 1q1.5 1q1.6 1q1.7 2q2.0 2q2.1 2q2.2 2q2.3 2q2.4 2q2.5 2q2.6 2q2.7 2q3.0 2q3.1 2q3.2 2q3.3 2q3.4 2q3.5 2q3.6 2q3.7 f+ 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g 2) 2) 2) g led pin l+ l+ 1l+ r h- h+ l+ 2l+ r r r t f1 f2 f3 f4 f- l- l- l- 3) l- l- 1) shield isolation (1) q 1.6 short- circuit data memory and s5 bus control front strip connection of process signal lines example of connection designation for an output: output 6 (6th bit); 0 to 7 possible address of output byte (1st byte); 0 to 255 possible q = output 1st terminal l+ (not specified in the address) block diagram of module inputs g = green led (status indicator) r = red led (short-circuit indicator) f+/f- = enable input 1) changeover of enable mode with jumper x20: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. 2) the terminal is not connected internally. when this terminal is connected to the output voltages, the clearances in air and leakage paths are no longer adequate to ul and csa, but comply with vde. 3) by connecting l- to pin 42, a leading and trailing connection to 0 v ground is created on the module when it is inserted and removed. di g ital input/output modules
8-52 system manual c79000-g8576-c199-07 8.4.11 6es5 453-4ua12 digital output module rated supply voltage l+ 24 v dc number of outputs (decoupled via diodes) 16, short-circuit protected 1) isolation yes, 16 outputs range for supply voltage 20 to 30 v dc fusing 16 x 2.5 a, slow output voltage for logic 1: (l+)-switch (l-)-switch for logic 0: (l+)-switch (l-)-switch l+ - 2.5 v min. 2.5 v max. 3 v max. l+ - 3 v min. switching current (resistive, inductive load) 10 ma to 2.0 a 2) residual current at logic 0 1 ma max. switching current for lamps 0.45 a max. (10 w) switching frequency with resistive load with inductive load 100 hz max. 0.2 hz max. at 1 a; 0.1 hz at 2 a breaking voltage (inductive) limited to l+ - 47 v total switching current 4 a max. 8 outputs coincidence factor (total load capability) ventilated not ventilated 100 % 25 %; 50 % to 20 o c permissible line length 400 m max., unshielded power supply digital section from system bus 5 v, 120 ma typical power dissipation (rated operation) 49.0 w enable input (f+/f-) rated input voltage 24 v dc input voltage for logic 1 for logic 0 13 to 33 v - 33 to 5 v rated input current 5 ma permissible line length 200 m max. short-circuit monitoring short-circuit indication red led for 16 outputs signaling output (h+, h-), floating common for all outputs. the signal o1o is generated when a short-circuit occurs at an output. output voltage as l+ switch for logic 1 for logic 0 l+ - 5 v min. 3 v max. switching current 10 ma max., short-circuit protected voltage test to vde 0160 between two groups: 1250 v ac between group and ground point: 1250 v ac mechanical specifications dimensions (w x h x d) 40 mm x 255 mm x 195 mm weight approx. 0.6 kg 1) short-circuit protection responds with line resistance  3.6 ohm. 2) one digital input is permissible as minimum load. di g ital input/output modules
8-53 system manual c79000-g8576-c199-07 f+ 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 g g g g g g g g g g g g g g g g 2) l+ r h f- l- h + - 13l+ f1 2) f5 2) 2) f9 2) f13 2) short-circuit t 1l+ 1l- 2l+ 2l- 3l+ 3l- 4l+ 4l- 5l+ 5l- 6l+ 6l- 7l+ 7l- 8l+ 8l- 9l+ 9l- 10l+ 10l- 11l+ 11l- 12l+ 12l- 14l+ 14l- 15l+ 15l- 16l+ 16l- 13l- + - + - + - + - 1q0.0 1q0.0 2q0.1 3q0.2 3q0.2 4q0.3 4q0.3 2q0.1 + - + - + - + - 5q0.4 5q0.4 6q0.5 6q0.5 7q0.6 7q0.6 8q0.7 8q0.7 9q1.0 9q1.0 10q1.1 10q1.1 11q1.2 11q1.2 12q1.3 12q1.3 + - + - + - + - 14q1.5 14q1.5 15q1.6 15q1.6 16q1.7 16q1.7 + - + - + - 13q1.4 + 13q1.4 - 1) x20 shield led pin (7) q 0.6 data memory and s5 bus control front strip connection of process signal lines example of connection designation for an output: output 6 (6th bit); 0 to 7 possible address of output byte (byte 0); 0 to 255 possible q = output 7th terminal l+ (not specified in the address) block diagram of module inputs g = green led (status indicator) r = red led (short-circuit indicator) f+/f- = enable input 1) changeover of enable mode with jumper x20: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. 2) the terminal is not connected internally. when this terminal is connected to the output voltages, the clearances in air and leakage paths are no longer adequate to ul and csa, but comply with vde. di g ital input/output modules
8-54 system manual c79000-g8576-c199-07 8.4.12 6es5 454-4ua13/4ua14 digital output module -4ua13 -4ua14 rated supply voltage l+ 24 v dc number of outputs 16, short-circuit protected 1) isolation yes, 1 group of 16 outputs range for supply voltage 20 to 30 v dc fusing 6.3 a, slow 1 fuse per 4 outputs 7 a, fast 1 fuse per 4 outputs output voltage for logic 1 for logic 0 l+ - 2 v min. 3 v max. switching current (resistive, inductive load) 10 ma to 2 a 2) residual current at logic 0 1 ma max. switching current for lamps 0.45 a max. (10 w) switching frequency with resistive load with inductive load 100 hz max. 0.2 hz max. at 1 a; 0.1 hz at 2 a breaking voltage (inductive) limited to l+ - 47 v limited to l+ -55 v total switching current 4 a max. per 4 outputs coincidence factor (total load capability) 50 % (in relation to the total switching current) permissible line length 400 m max., unshielded power supply digital section from system bus 5 v, 100 ma typical current consumption from l+/l- 24 v, 100 ma typical 24 v, 120 ma typical power dissipation (rated operation) 17.5 w 10 w enable input (f+/f-) rated input voltage 24 v dc input voltage for logic 1 for logic 0 13 to 33 v - 33 to 5 v rated input current 5 ma permissible line length 200 m max. short-circuit monitoring short-circuit display red led for 4 outputs signaling output (h+) common for all outputs. the signal a1o is generated when a short circuit occurs at an output. output voltage , referred to l- (with feed at 1l+) for logic 1 for logic 0 1l+ - 5 v min. 3 v max. 1l+ -1,5 v min. switching current 10 ma max., limited voltage test to vde 0160 between group and ground point: 1250 v ac mechanical specifications dimensions (w x h x d) 40 mm x 255 mm x 195 mm 20 mm x 255 mm x 195 mm weight approx. 0.55 kg 1) short-circuit protection responds with line resistance  4,75 ohm, irrelevant for the -4ua14. 2) one digital input is permissible as minimum load. di g ital input/output modules
8-55 system manual c79000-g8576-c199-07 x20 1q0.0 1q0.2 1q0.3 1q0.1 2q0.4 2q0.5 2q0.6 2q0.7 2l+ 3q1.0 3q1.1 3q1.2 3q1.3 4q1.4 4q1.5 4q1.6 4q1.7 4l+ f+ 1 2 3 4 5 6 7 8 9 10 block diagram of module inputs 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 g g g g g g g g g g g g g g g g 2) 2) 2) 2) front strip led pin l+ l+ 1l+ r h- h+ l+ 3l+ r r r f- l- l- 1) data memory and s5 bus control shield isolation l+ l- l- l+ 2) 2) 2) 2) 2) 2) f1 f2 f3 short- circuit 2) 2) 2) 2) 2) 2) 2) 2) f4 t connection of process signal lines example of connection designation for an output output 6 (6th bit); 0 to 7 possible address of the output byte (1st byte); 0 to 255 possible q = output 4th terminal l+ (not specified in the address) (4) q 1.6 g = green led (status indicator) r = red led (short-circuit indicator) f+/f- = enable input 1) changeover of enable mode with jumper x20: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. 2) the terminal is not connected internally. when this terminal is connected to the output voltages, the clearances in air and leakage paths are no longer adequate to ul and csa, but comply with vde. di g ital input/output modules
8-56 system manual c79000-g8576-c199-07 8.4.13 6es5 455-4ua12 digital output module rated supply voltage l 24 to 60 v ac (47 to 63 hz) number of outputs 16, conditional short-circuit protection 1) isolation yes, 2 groups of per 8 outputs range for supply voltage 20 to 72 v ac fusing 6.3 a, fast; 1 fuse per 4 outputs output voltage for logic 1 for logic 0 l- 1.5 v min. 7.5 v max. residual current at logic 0 5 ma max. switching current (resistive, inductive load) ventilated not ventilated 40 ma to 2 a; 6 a max. per 4 outputs 40 ma to 1 a; 4 a max. per 4 outputs switching current for lamps ventilated not ventilated 40 ma to 2 a; 2.5 a max. per 4 outputs 40 ma to 1 a; 2.5 a max. per 4 outputs max. inrush current for 3 3 ms 3 20 ms 3 50 ms 25 a/group 15 a/group 13 a/group permissible line length 300 m max. unshielded power supply digital section from system bus 5 v, 100 ma typical power dissipation (rated operation) 39.0 w enable input (f+/f-) jumper in front connector voltage test to vde 0160 between two groups: 2000 v ac between group and ground point: 1500 v ac mechanical specifications dimensions (w x h x d) 40 mm x 255 mm x 195 mm weight approx. 0.7 kg 1) protected by a fuse. di g ital input/output modules
8-57 system manual c79000-g8576-c199-07 1l 1q0.1 1q0.2 1q0.0 1q0.4 1q0.5 1q0.6 1q0.7 2l 2q1.0 2q1.1 2q1.2 2q1.4 2q1.5 2q1.6 2q1.7 1n f+ f- 1 2 4 6 8 10 12 14 16 18 20 25 27 29 31 33 35 37 39 41 g g g g g g g r g g g g g g g g g led pin shield 1l 1q0.3 2q1.3 2l isolation isolation 1) x20 t +5v 2n f2 f1 f4 f3 r r r (2) q 1.2 front strip connection of process signal lines example of connection designation for an output: output 2 (2nd bit); 0 to 7 possible address of output byte (1st byte); 0 to 255 possible q = output 2nd terminal l+ (not specified in the address) block diagram of module inputs data memory and s5 bus control g = green led (status indicator) r = red led (short-circuit indicator) f+/f- = enable input 1) changeover of enable mode with jumper x20: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. di g ital input/output modules
8-58 system manual c79000-g8576-c199-07 8.4.14 6es5 456-4ua12 digital output module rated supply voltage l 115 to 230 v ac (47 to 63 hz) number of outputs 16, conditional short-circuit protection 1) isolation yes, 2 groups of 8 outputs range for supply voltage 88 to 264 v ac fusing 6.3 a fast; 1 fuse per 4 outputs output voltage for logic 1 for logic 0 l- 1.5 v min. 30 v max. residual current at logic 0 5 ma max. switching current (resistive, inductive load) ventilated not ventilated 40 ma to 2 a; 2) 6 a max. per 4 outputs 40 ma to 1 a; 2) 4 a max. per 4 outputs switching current for lamps ventilated not ventilated 40 ma to 2 a; 2.5 a max. per 4 outputs 40 ma to 1 a; 2.5 a max. per 4 outputs contactor size per fuse group for all outputs 0 (type 3tb40) to 14 (type 3tb58) at 230 v ac; 00 (type 3tj ..) to 10 (type 3tb54) at 115 v ac; 0 (type 3tb40) to 8 (type 3tb52) at 230 v ac; 00 (type 3tj ..) to 4 (type 3tb48) at 115 v ac; max. inrush current for 3 3 ms 3 20 ms 3 50 ms 25 a/fuse group 15 a/fuse group 13 a/fuse group permissible line length 300 m max. unshielded power supply digital section from system bus 5 v, 100 ma typical power dissipation (rated operation) 39.0 w enable input (f+/f-) jumper in front connector voltage test to vde 0160 between two groups: 2000 v ac between group and ground point: 1500 v ac mechanical specifications dimensions (w x h x d) 40 mm x 255 mm x 195 mm weight approx. 0.7 kg 1) protected by a fuse 2) contactors of series 3tj can only be operated at 115 v ac. di g ital input/output modules
8-59 system manual c79000-g8576-c199-07 1l 1q0.1 1q0.2 1q0.0 1q0.4 1q0.5 1q0.6 1q0.7 2l 2q1.0 2q1.1 2q1.2 2q1.4 2q1.5 2q1.6 2q1.7 1n f+ f- 1 2 4 6 8 10 12 14 16 18 20 25 27 29 31 33 35 37 39 41 g g g g g g g g g g g g g g g g led pin shield 1l 1q0.3 2q1.3 2l isolation isolation 1) x20 t +5v 2n f2 f1 f4 f3 r r r r (2) q 1.6 data memory and s5 bus control front strip connection of process signal lines example of connection designation for an output: output 6 (6th bit); 0 to 7 possible address of output byte (1st byte); 0 to 255 possible q = output 2nd terminal l+ (not specified in the address) block diagram of module inputs g = green led (status indicator) r = red led (short-circuit indicator) f+/f- = enable input 1) changeover of enable mode with jumper x20: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. di g ital input/output modules
8-60 system manual c79000-g8576-c199-07 8.4.15 6es5 456-4ub12 digital output module rated supply voltage l 115 to 230 v ac (47 to 63 hz) number of outputs 8, conditional short-circuit protection 1) isolation yes, 8 outputs range for supply voltage 88 to 264 v ac fusing 3.5 a fast; 1 fuse per output output voltage for logic 1 for logic 0 l- 1.5 v min. 30 v max. residual current at logic 0 5 ma max. switching current (resistive, inductive load) ventilated not ventilated 40 ma to 2 a; 2) 40 ma to 1 a; 2) switching current for lamps ventilated not ventilated 40 ma to 2 a; 40 ma to 1 a; contactor size 0 (type 3tb40) to 14 (type 3tb58) at 230 v ac; 00 (type 3tj ..) to 8 (type 3tb52) at 115 v ac; max. inrush current for 3 3 ms 3 20 ms 3 50 ms 16 a 8 a 6.5 a switching capacity per module for ul for csa 1440 va max. 2000 va max. permissible line length 300 m max. unshielded power supply digital section from system bus 5 v, 100 ma typical power dissipation (rated operation) 18.0 w enable input (f+/f-) jumper in front connector voltage test to vde 0160 between two groups: 2000 v ac between group and ground point: 1500 v ac mechanical specifications dimensions (w x h x d) 40 mm x 255 mm x 195 mm weight approx. 0.6 kg 1) protected by a fuse. 2) contactors of series 3tj can only be operated at 115 v ac. di g ital input/output modules
8-61 system manual c79000-g8576-c199-07 f+ f- 1 2 4 6 8 10 12 14 16 18 20 25 27 29 31 33 35 37 39 41 g g g g g g g g led pin shield t +5v 1l 1l 2l 2l 3l 3l 4l 4l 1q0.0 1n 2q0.1 2n 3q0.2 3n 4q0.3 4n 1) x20 2) 5l 5l 6l 6l 7l 7l 8l 8l 5q0.4 5n 6q0.5 6n 7q0.6 7n 8q0.7 8n 2) r r r r r r r r f1 f5 f8 (3) q 0.2 data memory and s5 bus control front strip connection of process signal lines example of connection designation for an output: output 2 (2nd bit); 0 to 7 possible address of output byte (byte 0); 0 to 255 possible q = output 3rd terminal l+ (not specified in the address) block diagram of module inputs g = green led (status indicator) r = red led (short-circuit indicator) f+/f- = enable input (jumper in front connector) 1) changeover of enable mode with jumper x20: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. 2) the terminal is not connected internally. if this terminal is connected to the output voltage, the clearances in air and leakage paths remain adequate to ul, csa and vde. di g ital input/output modules
8-62 system manual c79000-g8576-c199-07 8.4.16 6es5 457-4ua12 digital output module rated supply voltage l+ 24 to 60 v dc number of outputs (decoupled via diodes) 16, short-circuit protected 1) isolation yes, 16 outputs range for supply voltage 20 to 72 v dc fusing 16 x 1 a, slow output voltage for logic 1: (l+)-switch (l-)-switch for logic 0: (l+)-switch (l-)-switch l+ - 2.5 v min. 2.5 v max. 3 v max. l+ - 3 v min. switching current (resistive, inductive load) 5 ma to 0.5 a 2) residual current at logic 0 1 ma max. switching current for lamps 0.22 a max. (5 w) switching frequency with resistive load with inductive load 100 hz max. 2 hz max. at 0.5 a breaking voltage (inductive) limited to l+ - 75 v 3) coincidence factor (total load capability) ventilated not ventilated (in relation to the total switching current) 100 % 50 %; 100 % up to 35 o c permissible line length 400 m max. unshielded power supply digital section from system bus 5 v, 120 ma typical power dissipation (rated operation) 13.0 w enable input (f+/f-) rated input voltage 24 to 60 v dc input voltage for logic 1 for logic 0 13 to 72 v - 72 to 8 v rated input current at 24 v dc at 48 v dc at 60 v dc 2.5 ma 5 ma 6.5 ma permissible line length 200 m max. short-circuit monitoring short-circuit display red led for 16 outputs signaling output (h+, h-) common for all outputs. the signal o1o is generated if a short-circuit occurs at an output. output voltage as l+ switch for logic 1 for logic 0 l+ - 5 v min. 3 v max. switching current 10 ma max., short-circuit protected voltage test to vde 0160 between two groups: 1250 v ac; between group and ground point: 1250 v ac mechanical specifications dimensions (w x h x d) 40 mm x 255 mm x 195 mm weight approx. 0.6 kg 1) short-circuit protection responds with line resistance 9 ohm at 24 v dc, 30 ohm at 60 v dc. 2) one digital input is permissible as minimum load. 3) at l+ voltages of more than 72 v, the logic 0 of the output can rise to 13 v. a digital input follower will interpret this sign al as a logic 1 (possible fault). di g ital input/output modules
8-63 system manual c79000-g8576-c199-07 f+ 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 g g g g g g g g g g g g g g g g 2) l+ r h f- l- h + - 13l+ f1 2) f5 2) 2) f9 2) f13 2) short-circuit t 1l+ 1l- 2l+ 2l- 3l+ 3l- 4l+ 4l- 5l+ 5l- 6l+ 6l- 7l+ 7l- 8l+ 8l- 9l+ 9l- 10l+ 10l- 11l+ 11l- 12l+ 12l- 14l+ 14l- 15l+ 15l- 16l+ 16l- 13l- + - + - + - + - 1q0.0 1q0.0 2q0.1 3q0.2 3q0.2 4q0.3 4q0.3 2q0.1 + - + - + - + - 5q0.4 5q0.4 6q0.5 6q0.5 7q0.6 7q0.6 8q0.7 8q0.7 9q1.0 9q1.0 10q1.1 10q1.1 11q1.2 11q1.2 12q1.3 12q1.3 + - + - + - + - 14q1.5 14q1.5 15q1.6 15q1.6 16q1.7 16q1.7 + - + - + - 13q1.4 + 13q1.4 - 1) x20 shield led pin (7) q 0.6 data memory and s5 bus control front strip connection of process signal lines example of connection designation for an output: output 6 (6th bit); 0 to 7 possible address of output byte (byte 0); 0 to 255 possible q = output 7th terminal l+ (not specified in the address) block diagram of module inputs g = green led (status indicator) r = red led (short-circuit indicator) f+ = enable input) 1) changeover of enable mode with jumper x20: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. 2) the terminal is not connected internally. when this terminal is connected to the output voltages, the clearances in air and leakage paths are no longer adequate to ul and csa, but comply with vde. di g ital input/output modules
8-64 system manual c79000-g8576-c199-07 8.4.17 6es5 458-4ua12 digital output module rated supply voltage l 24 v dc number of outputs 16 isolation yes, 16 outputs range for supply voltage 20 to 30 v dc fusing 16 x 1 a, slow 1) output relay contacts service life of contacts 10 8 cycles switching capacity with resistive load with rc element module without rc element module 60 v dc/48 v ac, 0.5 a 2) 60 v dc/48 v ac, 70 ma switching current with inductive load with rc element module and external suppressor circuit 0.5 a max. switching current for lamps 0.1 a max. with rc element module switching frequency with resistive load with inductive load 100 hz max. (pick-up 1 ms, drop-out 1 ms) 10 hz max. up to 50 ma, 2 hz max. up to 0.3 a, 0.5 hz max. up to 0.5 a coincidence factor (total load capability) 100 % permissible line length 400 m max., unshielded power supply digital section from system bus 5 v, 80 ma typical current consumption from l+/l- 200 ma typical power dissipation (rated operation) 5.2 w enable input (f+/f-) rated input voltage 24 v dc input voltage for logic 1 for logic 0 13 to 33 v -33 to 5 v rated input current 5 ma permissible line length 200 m max. voltage test to vde 0160 between two groups: 500 v ac between group and ground point: ac 500 v mechanical specifications dimensions (w x h x d) 20 mm x 255 mm x 195 mm weight approx. 0.45 kg 1) the fuse does not protect the contacts. the relay must be replaced after an overload. 2) 50 v/0.5 a max. resistive load for ul di g ital input/output modules
8-65 system manual c79000-g8576-c199-07 shield isolation 1) x35 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 g g g g g g g g g g g g g g g g led pin f- l- 1l 1l 2l 2l 3l 3l 4l 4l 5l 5l 6l 6l 7l 7l 8l 8l 9l 9l 10l 10l 11l 11l 12l 12l 14l 14l 15l 15l 16l 16l 13l 13l f2 2) f6 2) 2) f10 2) f14 2) f1 l- l- 3) f+ l+ l+ l+ 498 498 498 498 + - + - + - + - + - + - + - + - + - + - + - + - + + - + - + - - 14q1.5 14q1.5 15q1.6 15q1.6 16q1.7 16q1.7 13q1.4 13q1.4 5q0.4 5q0.4 6q0.5 6q0.5 7q0.6 7q0.6 8q0.7 8q0.7 1q0.0 1q0.0 2q0.1 3q0.2 3q0.2 4q0.3 4q0.3 2q0.1 9q1.0 9q1.0 10q1.1 10q1.1 11q1.2 11q1.2 12q1.3 12q1.3 r c 47r 47nf f 498 4x t (7) q 0.6 data memory and s5 bus control front strip connection of process signal lines example of connection designation for an output: output 6 (6th bit); 0 to 7 possible address of output byte (byte 0); 0 to 255 possible q = output 7th terminal l+ (not specified in the address) block diagram of module inputs g = green led (status indicator) r = red led (short-circuit indicator) f+ = enable input 1) changeover of enable mode with jumper x35: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. 2) the terminal is not connected internally. when this terminal is connected to the output voltages, the clearances in air and leakage paths are no longer adequate to ul and csa, but comply with vde. 3) the terminal is not connected internally. if this terminal is connected to the output voltages, the clearances in air and leakage paths remain adequate to ul, csa and vde. di g ital input/output modules
8-66 system manual c79000-g8576-c199-07 load 60v dc max. front strip for dc voltage: current sinking switching to p for ac voltage: 498 load load l+ l- z. diode 82v, 5w 60 v dc max. 48 v ms max. l+ l- l n diode  100v,1a 498-1ab11 rc element module diode  100v,1a external suppressor circuitry for inductive load di g ital input/output modules
8-67 system manual c79000-g8576-c199-07 8.4.18 6es5 458-4uc11 digital output module rated supply voltage l 24 v dc (pins 22, 23) number of outputs 16 isolation yes, 2 groups of 8 outputs range for supply voltage of the relays 20 to 30 v dc ausgang relay contacts service life of contacts approx. 10 5 cycles at 230 v ac/5a approx. 10 7 cycles mechanical switching capacity of the contacts with resistive load with inductive load 5.0 a at 250 v ac 5.0 a at 30 v dc 0.3 a at 115 v dc 1.5 a at 250 v ac 1.0 a at 30 v dc 0.08 a at 115 v dc max. rating per group p0/p1 8.0 a switching frequency with resistive load with inductive load 10 hz max. 2 hz max. permissible line length 400 m max., unshielded power supply digital section from system bus 5 v, 120 ma typical (all outputs active) current consumption from l+/l- 250 ma typical (all outputs active) power dissipation (rated operation) 6.6 w enable input (f+/f-) rated input voltage 24 v dc input voltage for logic 1 for logic 0 13 to 33 v -33 to 5 v rated input current 5 ma permissible line length 200 m max. voltage test to vde 0160 between two groups: 2000 v ac between group and ground point: 1500 v ac mechanical specifications dimensions (w x h x d) 20 mm x 255 mm x 195 mm weight approx. 0.7 kg di g ital input/output modules
8-68 system manual c79000-g8576-c199-07 1q0.0 1q0.2 1q0.3 1q0.1 1q0.4 1q0.5 1q0.6 1q0.7 f+ 1 2 4 6 8 10 12 14 16 18 20 22 23 25 27 29 31 33 35 37 39 41 g g g g g g g g g g g g g g g g led pin l+ f- t l- p0 m0 2q1.2 2q1.3 2q1.1 2q1.4 2q1.5 2q1.6 2q1.7 m1 l+ l- l+ l- p1 2q1.0 f1 shield isolation 1) x2 3 2 1 (2) q 1.6 data memory and s5 bus control front strip connection of process signal lines example of connection designation for an output: output 6 (6th bit); 0 to 7 possible address of output byte (1st byte); 0 to 255 possible q = output 2nd terminal l+ (not specified in the address) block diagram of module inputs g = green led (status indicator) f+/f- = enable input p0/m0 = group of 8/load supply voltage (1st group) p1/m1 = group of 8/load supply voltage (2nd group) l+/l- = relay supply voltage (24 v dc) 1) changeover of enable mode with jumper x2: 1 - 2 jumper inserted = enable input active (factory setting) jumper open = enable input inactive. di g ital input/output modules
8-69 system manual c79000-g8576-c199-07 8.4.19 6es5 482-4ua11 digital input/output module - 4ua11 - 4ua20 inputs rated input voltage 24 v dc number of inputs 16 min., 24 max. isolation yes, 1 group of 32 inputs/outputs input voltage for logic 0 for logic 1 -33 to 5 v 13 to 33 v -33 to 7 v 13 to 33 v rated input current 8.5 ma typical 7 ma typical delay time 0.3 ms typical 0.3 ms typical (0.15 to 0.5ms) input resistance 2.8 kohm typical 3.3 kohm typical coincidence factor (total load capability) 100 % permissible line length 50 m max. unshielded supply voltage for 2-wire bero 22 v to 33 v outputs number of outputs 8 min., 16 max., short-circuit protected 1) isolation ye s fusing 6.3 a, slow; 1 fuse per 8 outputs 7 a, fast; 1 fuse per 8 outputs output voltage for logic 1 for logic 0 l+ - 1.5 v min. 3 v max. switching current (resistive, inductive load) 5 ma to 0.5 a switching frequency with resistive load 120 hz max. 100 hz max. with inductive load 2 hz max. at 0.3 a; 0.5 hz max. at 0.5 a breaking voltage (inductive) limited to l+ and - 27 v limited to l+ and l+ -55 v total switching current 4 a max. per 8 outputs coincidence factor ventilated not ventilated (in relation to the total switching current) 100 % 50 %; 100 % up to 35 o c permissible line length 400 m max. unshielded power supply rated supply voltage l+ 24 v dc digital part of system bus 5 v, 80 ma typical 5 v, 80 ma typical current consumption from l+/l- 24 v, 150 ma typical 24 v, 220 ma typical power loss (nominal operation) 13.6 w 8 w short-circuit monitoring short-circuit display red led for 8 outputs signal output (h+) common for all outputs. the signal a1o is generated when a short-circuit occurs at an output di g ital input/output modules
8-70 system manual c79000-g8576-c199-07 output voltage referred to l- (with supply at 1l+) for logic 1 for logic 0 1l+ - 5 v min. 3 v max. 1l+ -1.5 v max. 3 v max. switching current 10 ma max. current limiting enable input (f+/f-) jumper in front connector voltage test to vde 0160 between group and ground point: 1250 v ac between group and ground point: ac 500 v mechanical specifications dimensions (w x h x d) 20 mm x 255 mm x 195 mm weight approx. 0.4 kg 1) short-circuit protection responds at line resistance  15 ohm di g ital input/output modules
8-71 system manual c79000-g8576-c199-07 1q0.0 1q0.1 1q0.3 1q0.4 1q0.5 1q0.6 1q0.7 1q0.2 1q1.0 1q1.1 1q1.2 1q1.3 1q1.4 1q1.5 1q1.6 1q1.7 synin synout 2) 1i2.0 1i2.1 1i2.2 1i2.3 1i2.4 1i2.5 1i2.6 1i2.7 1i3.0 1i3.1 1i3.2 1i3.3 1i3.4 1i3.5 1i3.6 1i3.7 f+ 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 pin l+ l+ h+ f- l- l+ l- connection of process signal lines 1) x20 (1) q 1.6 example of connection designation for an output: output 6 (6th bit); 0 to 7 possible address of output byte (1st byte); 0 to 255 possible q = output 1st terminal l+ (not specified in the address) h- l- 1) changeover of enable mode with jumper x20: jumper inserted = enable input active (factory setting) jumper open = enable input inactive. 2) sysnin, synout only relevant for operation with the ip 257 (6es5 482-4ua11) f+/f- = enable input switch s2 must be at setting 1. di g ital input/output modules
8-72 system manual c79000-g8576-c199-07 di g ital input/output modules
9-1 syste m manual c79000-g8576-c199-07 analog input/output modules described in this chapter are the installation, wiring and operation of analog input modules and analog output modules. the individual modules have special features. these are discussed in separate sections. section description page 9.1 t echnica l description 9-2 9.2 common t echnica l specifications 9-3 9.3 the 460 analog input module 9 -4 9.4 the 463 analog input module 9-35 9.5 the 465 analog input module 9-50 9.6 the 466 analog input module 9-77 9.7 the 470 analog output module 9-106 chapter overview 9
9-2 system manual c79000-g8576-c199-07 9.1 technical description the description below applies to the following modules: analog input modules and cards order no. of the module no. of inputs isolation/groups range card (4 channels) order no. of the range card 6es5 460-4ua13 6es5 465-4ua12 6es5 465-4ua13 8 16/8 yes/8 inputs isolated from m, m ext and l+/l- no/none  12.5/50/500 mv/pt 100  50/500 mv/pt 100  1 v  10 v  20 ma 4 to 20 ma/4-wire trans.  5 v 4 to 20 ma/4-wire trans. 6es5 498-1aa11 6es5 498-1aa11 6es5 498-1aa21 6es5 498-1aa31 6es5 498-1aa41 6es5 498-1aa51 6es5 498-1aa61 6es5 498-1aa71 analog input modules order no. of the module no. of inputs isolation/groups measuring range 6es5 463-4ua12 6es5 463-4ub12, 6es5 466-3la11 6es5 466-4ua11 4 16/8 yes/4 inputs isolated from m, m ext and l+/l- ye s 1 v, 10 v, 20 ma, 4 to 20 ma 1.25 v, 2.5 v, 5 v, 10 v 20 ma, 4 to 20 ma analog output modules order no. of the module no. of inputs isolation/groups output range 6es5 470-4ua12 6es5 470-4ua13 6es5 470-4ub12 6es5 470-4ub13 6es5 470-4uc12 6es5 470-4uc13 8 8 8 yes/8 outputs isolated from m, m ext and l+/l- yes/8 outputs isolated from m, m ext and l+/l- yes/8 outputs isolated from m, m ext and l+/l-  10 v/0 to 20 ma  10 v  1 to 5 v/4 to 20 ma analog input and analog output modules are i/o modules for the input/output of widely differing, analog process signals for the s5-135u/155u programmable (logic) controller. these i/o modules allow the creation of control systems which require the processing of analog measured variables or continuous input to actuators. i/o modules analo g input/output modules
9-3 system manual c79000-g8576-c199-07 9.2 common technical specifications important for the usa and canada the following approvals have been issued:  ul listing mark underwriters laboratories (ul) to standard ul 508, report e85972 and e116536 for the 466-3la11/466-4ua11 analog input module  csa certification mark mark canadian standard association (csa) to standard c 22.2 no. 142, report lr 63533c and lr 48323 for the 466-3la11/466-4ua11 analog input module address range 128 to 255 (0 to 255) supply voltage l+ rated value ripple v pp permissible range (including ripple) reference potential 24 v 3.6 v 20 to 30 v l-= m ext = 0 v voltage for the isolated enable inputs (only required when enable jumper is inserted) f+ = + 24 v f- = 0 v line lengths for analog input modules with rated input range of  12.5 m,  50 mv and pt 100 50 m max. for shielded cables laid separately from power system cables (see chapter 3) analog input modules with rated input range of  500 mv /  1 /  5 /  10 v /  20 ma, 4 to 20 ma and pt 100 200 m max., shielded analog output modules 200 m max., shielded temperature range in operation for storage and transportation 0 to 55 o c - 40 to 70 o c relative humidity 95 % max. at 25 o c, no condensation site altitude 3500 m max. above sea level dimensions (w x h x d) 20 x 255 x 195 mm weight approx. 0.4 kg analo g input/output modules
9-4 system manual c79000-g8576-c199-07 9.3 the 460 analog input module 9.3.1 design the modules are designed as plug-in pcbs for central controllers and expansion units with a backplane connector and with a blade connector to accept a plug-in front connector. you can directly connect the process signal lines to the front connector, which is available separately, with screw or crimp terminals. situated on each module is an addressing switch with six rockers to set the module address. analog input modules also have two switches on the side with eight rockers for setting the mode, and receptacles for range cards. the modules are protected by covers on both sides. blade connector addressing switch mode switches range cards front connector figure 9-1 analog input module 9.3.2 function of the enable input the 460 module has an enable circuit. you can use the enable inputs to switch off individual modules whilst the plc is in operation. this means that:  the module can no longer be addressed by the user program. modules which are switched off can be removed or inserted during operation. if this is not necessary, operate the module with the enable input switched off. addressing switch, mode switches analo g input/output modules
9-5 system manual c79000-g8576-c199-07 the enable circuit requires an external 24 v voltage at enable inputs f+/f- in the front connector. if there is no voltage at f+/f-, the modules will not acknowledge. when the front connector is swivelled away from the front strip of the module, the supply of power to the enable input is interrupted, i.e. the module is switched off and can no longer be addressed by the user program: a timeout (qvz) occurs in the cc. the 460 module additionally offers the facility for changing the enable mode. the module has a jumper accessible from above in the vicinity of the addressing switch. when the enable jumper is inserted, you can define the behaviour of the 460 analog input module as follows:  when the enable voltage and load voltage are obtained from the same load supply, a shutdown of the 24 v load voltage will result in a timeout.  when the enable voltage and load voltage are obtained from different load supplies, a shutdown of the 24 v load voltage will not result in a timeout. (with the 460-4ua11/12 modules, a shutdown of the load voltage will result in a timeout.) enable jumper figure 9-2 enable input and enable jumper jumper inserted: enable input (f+/f-) active (factory setting) jumper open: enable input (f+/f-) switched off examples of functioning of the enable inputs:  to switch off individual subprocesses, i.e. outputs of various modules can be operated from a common load supply and yet activated separately.  the load voltage of individual modules can be monitored without additional circuitry. any reactions to failure of the load voltage can be programmed in the qvz (timeout) organization block. enable input switching off the enable input analo g input/output modules
9-6 system manual c79000-g8576-c199-07 you must observe the following when configuring systems: switching on at the latest 100 ms after power-up of the plc, the voltage must be present at the enable inputs of the i/o modules. switching off when the plc has been switched off, the voltage at the enable inputs of the i/o modules must still be present as long as the internal 5 v voltage is present. you should observe the following instructions for switching off ccs and equipment for supplying power to the enable inputs. when there is a need to switch off the load power supply separately without affecting the enabling of modules, there are the following possibilities for producing the enable voltage. these exist even when the load power supply is used without an additional capacitor and common shutdown.  230 v ac supply for cc/eu and load power supply f+ l+ i/o modules 230 v ac cc/eu -951 a) c) b) battery l+ power supply load power supply 24v supply for the enable inputs from: a) 6es5 951-4lb11 load power supply b) battery c) terminals for 24 v on the front plate of the power supply configuring switching off the cc separate or common shutdown of the cc/eu and load power supply analo g input/output modules
9-7 system manual c79000-g8576-c199-07  24 v supply for cc/eu and i/os f+ l+ i/o modules 24 v dc b) a) cc/eu l+ battery power supply 24v supply for the enable inputs from: a) battery b) terminals for 24 v on the front plate of the power supply proper functioning is ensured if the 24 v load power supply has an output capacitance of at least 4700  f per 10 a of load current. other units which do not meet this condition can be adapted to this requirement by connecting a 10000  f / 40 v capacitor in parallel. 10000 m f/ 40v cc/eu f+ l+ 230 v ac i/o modules load power supply 24v power supply common shutdown of the cc/eu and load power supply with a 230 v ac supply analo g input/output modules
9-8 system manual c79000-g8576-c199-07 9.3.3 special features of the 460 analog input module the 460 analog input module executes integrating processing of the digital input signals; periodic system interference is thus suppressed. you can adapt the process signals, according to the application, to the input level of the analog-to-digital converter of the module with plug-in range cards (resistor dividers or shunt resistors). to monitor the sensors connected to the inputs, you can use the 6es5 498-1aa11 range card (through-connection card) to implement the abroken wire detectiono mode. you can activate broken wire detection for 4 or 8 inputs. each time the input value is about to be encoded, a constant current is briefly (1.6 ms) switched to the input terminals and the resultant current is checked for a limit value. if a digital voltmeter is used to measure the signal at the input, these current pulses may appear to indicate fluctuation of the signal. the encoded value, however, is not affected. if these apparent fluctuations of the signal are disturbing, for example, during startup, you can switch the tripping current to the inactive state on the 460 analog input module: apply + 24 v to pin 24 of the front connector, and 0 v to l-. you must additionally set the mode switch to awithout broken wire detection.o in the event of open-circuit of the sensor or its line, the voltage exceeds the limit and a broken wire is indicated (bit 1 in data byte 1). the analog-to-digital converter encodes the value 0. a broken wire signal is only useful when the 6es5 498-1aa11 through-connection card is used. with all other measurement cards, a broken wire signal will result in incorrect reactions. further details relating to the broken wire signal can be found in section 9.3.12. if the measuring range is exceeded, the overflow bit (bit 2 0 of the low byte) is set. you have a choice of the cyclic sampling and selective sampling modes. in the cyclic sampling mode, the module continuously encodes all measured values. the digitized measured values are stored under the channel-related address on the module (the high byte under this address, and the low byte under the next higher address). the measured values can then be read by the module at any time without waiting. when you operate the module in this mode, you can set a module address from 0 to 255. broken wire signal switching the tripping current to the inactive state measuring range exceeded cyclic sampling analo g input/output modules
9-9 system manual c79000-g8576-c199-07 in the selective sampling mode, a measured value is encoded on the central initiative of the cpu. at the start of conversion, the module must be addressed once with a write operation (t pw) by the user program. an active bit (t = 1) is set during encoding. with the transition to t = 0, the measured value becomes valid. with non-constant cycle times, there may be non-periodic measured value aquisition. if you operate the module in this mode, you must set a module address from 128 to 255. you can also use the address range from 0 to 127 for selective sampling after appropriate programming in db 1 of the user program. another method is that of time-controlled program processing. with this method, certain program segments (e.g. fb 13) are automatically inserted into program processing at the 100 ms rate by a time-controlled block (ob 13). a constant timebase is thus achieved. fb 13 sprm-b len=22 abs sheet 1 segment 1 name: selsampl example of selective sampling 0005 : 0006 : 0007 :l pw128 read analog value 0008 :t mw128 in to aux: flag fw 128 0009 :a m 129.2 scan activity =1? 000a :jc = end if = 1, jump to end 000b :t fw10 if = 0, measured value in fw 10 000c :t pb128 initiate sampling 000d end : (1st value invalid after start) 000e 000f : 0010 :be you can read analog values of analog input modules with a function block from the abasic functionso package. the basp signal is not interpreted by the 460 analog input module. selective sampling time-controlled program processing function block basp (output inhibit) analo g input/output modules
9-10 system manual c79000-g8576-c199-07 9.3.4 setting the module address you set the module address on the addressing switch. this also establishes the necessary assignments between user program and process connection. the module address is the sum of the decimal significances of the switch rockers in the on setting ( ). one data word = two data bytes is required to process an input or an output. a module with 16 inputs therefore reserves 32 byte addresses, and a module with 8 inputs or outputs reserves 16 byte addresses. you can affix the adhesive label with the desired module address on a free labeling field under the addressing switch. the switch rockers to be set for the module address specified as a decimal number (address bit adb) are marked by dots on the label. press the individual rockers of the addressing switch downwards with a ballpoint pen or similar object, but not a pencil. note ensure that all the switches are operated properly (meaning pressed past the latching point). on setting (switch pressed) addressing switch address bit decimal signification of the address bit free field for label with module address and marked switch settngs address (decimal) 128 64 32 16 8 4 2 1 adb7 adb6 adb5 adb4 adb3 adb2 adb2 is not connected adb1 adb0 adb0 and adb1 are not assigned figure 9-3 labeling of the addressing switch labeling field analo g input/output modules
9-11 system manual c79000-g8576-c199-07 the address under which the module is referenced by the step 5 program is independent of the slot. for analog input and analog output modules (8 inputs) only the lowest address (start address) is set. other addresses (subaddresses) are decoded on the module. note the start address of the analog module must be a multiple of the double channel number. 4 channels : 0, 8, 16, 24, ... 248 8 channels : 0, 16, 32, 48, ... 240 if one of the inputs or outputs (channel 0 to 7) of a module is to be addressed, the relevant subaddress must be specified in the program. the subaddress of the input or output, based on the start address of the module, is given by: start address + 2 x channel no. = subaddress example: analog input module with 8 inputs the address is the sum of the significances set with the individual coding switches. 160 = 128 + 32 = 2 7 + 2 5 on setting (switch pressed) ib 160 128 64 32 16 8 4 2 1 adb7 adb6 adb5 adb4 adb3 adb2 adb1 adb0 a module with 8 inputs (channel 0 to 7) and start address 160 reserves the address range from 160 to address 160 + 7 x 2 = 174 in this example, the next free address for another module is 176. addresses already assigned must not be set again. start address, subaddress analo g input/output modules
9-12 system manual c79000-g8576-c199-07 however, analog input modules and analog output modules may be given the same address with cyclic sampling because they are distinguished by the user program. this is not possible with selective sampling. for cyclic sampling, you can address the module in the address range from 0 to 255, and for selective sampling from 128 to 255. for selective sampling, you can also use the address range from 0 to 127 after appropriate programming in db 1 of the user program. example: on an analog input module with start address 160 (ib 160 = input byte 160), input channel 3 is to be scanned by the program. step action 1 affix the self-adhesive label with address 160 on the free field under the addressing switch on the module. adb 5 and adb 7 are marked on the label. 2 press the appropriate rockers of the addressing switch down on the side marked by a dot on the module cover. set the other rockers to the opposite setting. this way sets the start address of the module. adb 5 and adb 7 results in 2 5 + 2 7 = 32 + 128 = 160 3 enter the address 160 + 3 x 2 = 166 in the program for input channel 3. addressing for cyclic/selective sampling analo g input/output modules
9-13 system manual c79000-g8576-c199-07 9.3.5 removing and inserting modules ! warning when removing and inserting the front connector during operation, hazardous voltages of more than 25 v ac or 60 v dc may be present at the module pins. when this is the case at the front connector, live modules may only be replaced by electrical specialists or trained personnel in such a way that the module pins are not touched. during operation, the front connector and module must not be removed or inserted without the enable jumper or active enable circuit. install an analog input/output module as follows: step action 1 release the upper locking bar on the subrack and swivel it upwards and out. 2 insert the module at the desired slot in the subrack and push it back in the guides. 3 latch the module by rotating the locking pin by 90 o at the lower end of the module. it must no longer be possible to pull the module forwards. 4 engage the front connector on the support pin of the module. the width of the support pin also provides keying to prevent front connectors from being fitted to the wrong modules (e.g. front connectors with 115/230 v ac wiring cannot be plugged into analog modules). 5 tighten the screw in the upper part of the front connector. analo g input/output modules
9-14 system manual c79000-g8576-c199-07 remove an analog input/output module as follows: step action 1 release the upper locking bar on the subrack and swivel it upwards and out. 2 slacken the screw in the upper part of the front connector. this causes the front connector to be pressed out of the female connector of the module. contacts f+ and f- of the enable input at the upper end of the front connector are thus opened first. if the enable input is active, power is removed from the outputs and the module is isolated from the s5 bus. 3 swing the front connector out and lift it away from the support pin of the module. 4 release the module by rotating the locking pin by 90 o at the lower end of the module. you can pull the module out of the subrack with a grip with swivels outwards. 1 2 3 5 6 4 module front connector support mount support pin figure 9-4 module with front connector 1 screw 2 locking pin 3 support mount 4 support pin 5 grip 6 backplane connector comply with vde specifications 0110 and 0160 to carry out the wiring of supply and signal lines which are to be connected to the programmable controllers and front connectors of the modules. detailed information on cabinet assembly, cabinet ventilation and protective measures can be found in chapter 3. analo g input/output modules
9-15 system manual c79000-g8576-c199-07 9.3.6 marking of modules and front connectors for the marking of modules and front connectors, labels are supplied with the module and central controller; they are affixed as shown in figure 9-5. 1 1 2 3 45 figure 9-5 marking and labeling of modules 1 label with the module address under which the module is referenced by the step 5 program 2 labeling strip with the product designation for the module; space to mark the module version and label the channels 3 label with module address and marking of the required settings for the addressing switch 4 labeling strip for terminal designations or connection diagrams (strip in the cover of the front connector) 5 name plate analo g input/output modules
9-16 system manual c79000-g8576-c199-07 9.3.7 connecting the signal lines for connection of the signal lines, front connectors for 20 and 40 mm mounting width with crimp connection and 40 mm mounting width with screw connection are available (screwdriver blade width: 3.5 mm, maximum torque: 0.8 nm). use stranded conductor to facilitate handling of the front connector. ferrules are not required for screw connections, because the screw terminals are provided with wire protection. when the crimp contact is inserted in the plastic body of the front connector, a click can clearly be heard. this indicates that the contact is engaged. for jumpering or to correct the wiring, you can remove the contacts with a releasing tool (see ordering information) without having to pull out the front connector. ferrules are not required for screw connections, because the screw terminals are provided with wire protection. you can use ferrules of 7 mm in length to din 46228. the maximum terminal area is 2 x 2.5 mm 2 . terminal t connector t max. nf cross-section connector for rtdvlt mounting width fmdl type type 6es 497- no. of contacts signal or supply conductor aux. jumper in connector 1) rated voltage of module crimp connection -4ua12 2) 42 0.5 mm 2 0.5 mm 2 5 to 60 v dc 20 mm operation with fan -4ua22 2) 42 0.5 mm 2 0.5 mm 2 5 to 60 v dc 40 mm oti screw ti -4ub12 42 0.5 to 2.5 mm 2 0.5 to 1.0 mm 2 5 to 60 v dc 40 mm operation without fan connection -4ub31 42 0.5 to 1.5 mm 2 0.5 to 1.0 mm 2 5 to 60 v dc 20 mm without fan 1) to multiply the supply and 0 v ground terminals, and to connect the enable input 2) the crimp contacts must be ordered separately for these types of connector. ! caution only extra-low voltage 60 v dc with safety separation from system voltage may be used for the 24 v dc supply and for the 24 v dc input signals. safety separation can be implemented to the requirements of, amongst other sources, vde 0100 part 410/hd 384-4-41/iec 60364-4-41 (as functional extra-low voltage with safety separation) or vde 0805/en 60950/iec 60950 (as safety extra-low voltage selv) or vde 0106 part 101. analo g input/output modules
9 - 1 7 s y s t e m m a n u a l c 7 9 0 0 0 - g 8 5 7 6 - c 1 9 9 - 0 7 9 . 3 . 8 c o n n e c t i o n o f s e n s o r s o b s e r v e t h e f o l l o w i n g i n f o r m a t i o n w h e n c o n n e c t i n g t h e s e n s o r s . w i t h i s o l a t e d s e n s o r s , i t i s p o s s i b l e f o r t h e m e a s u r i n g c i r c u i t t o d e v e l o p a p o t e n t i a l w i t h r e s p e c t t o g r o u n d w h i c h e x c e e d s t h e p e r m i s s i b l e p o t e n t i a l d i f f e r e n c e u c m ( s e e m a x i m u m v a l u e s o f t h e i n d i v i d u a l m o d u l e s ) . t o p r e v e n t t h i s , y o u m u s t c o n n e c t t h e n e g a t i v e p o t e n t i a l o f t h e s e n s o r t o t h e r e f e r e n c e p o t e n t i a l o f t h e m o d u l e ( 0 v b u s ) . e x a m p l e : t e m p e r a t u r e m e a s u r e m e n t o n a b u s b a r w i t h i n s u l a t e d t h e r m o c o u p l e s i n t h e w o r s t c a s e , t h e m e a s u r i n g c i r c u i t c a n d e v e l o p a n e x c e s s i v e l y h i g h p o t e n t i a l o n a c c o u n t o f a s t a t i c c h a r g e o r c o n t a c t r e s i s t a n c e s . t h i s m u s t b e p r e v e n t e d w i t h a n e q u i p o t e n t i a l b o n d i n g c o n d u c t o r . t h e p e r m i s s i b l e p o t e n t i a l d i f f e r e n c e ( u c m ) b e t w e e n t h e i n p u t s a n d t h e 0 v b u s m u s t n o t b e e x c e e d e d . d e p e n d i n g o n t h e s y s t e m o r t y p e o f s e n s o r , t h e p o t e n t i a l d i f f e r e n c e m u s t b e k e p t i n t h e p e r m i s s i b l e r e g i o n w i t h e p u i p o t e n t i a l b o n d i n g . e q u i p o t e n t i a l b o n d i n g c o n d u c t o r 0 v b u s a d a n a l o g i n p u t m o d u l e s e n s o r , i s o l a t e d m u x m + m - # r a n g e c a r d f o r 4 i n p u t s + - u e f i g u r e 9 - 6 m e a s u r i n g c i r c u i t w i t h e q u i p o t e n t i a l b o n d i n g c o n d u c t o r f o r t h e 4 6 0 a n a l o g i n p u t m o d u l e c o n n e c t i o n o f c u r r e n t o r v o l t a g e s e n s o r s e q u i p o t e n t i a l b o n d i n g a n a l o g i n p u t / o u t p u t m o d u l e s
9-18 system manual c79000-g8576-c199-07 example: (special case) the temperature of the busbar of an electroplating bath is to be measured with an uninsulated thermocouple. + - u e + - u cm a d mux m+ m- u cm # 0 v bus analog input module sensor, not isolated range card for 4 inputs figure 9-7 measuring circuit without equipotential bonding conductor for the 460 analog input module the potential of the busbar with respect to the reference potential of the module is, for example, 24 v dc. a 460 analog input module with isolated input is used (u cm = 60 v ac/75 v dc). an equipotential bonding conductor must not be laid here because it would short-circuit the busbar. analo g input/output modules
9-19 system manual c79000-g8576-c199-07 9.3.9 connecting a compensating box for thermal e.m.f. measurement if the room temperature fluctuations at the reference point (for example, in the terminal box) affect the measurement result and you do not wish to use a thermostat, you can compensate for the effect of temperature on the reference point with a compensating box. between - 10 and + 70 o c, it compensates for the change in thermal e.m.f. caused by temperature deviation (compensating box, see catalog mp 19). ensure that the compensating box has thermal contact with the terminals. if the compensating box is aligned at 20 o c, this must be taken into account in temperature evaluation (20 o c measuring point temperature = 0 mv). pins 22 and 23 are extended on analog input modules as an input for the compensating voltage. you must select a common input loop for all inputs on mode switch 2. the compensating box must be connected in a floating circuit. the power supply unit of the compensating box must have a grounded shield winding to avoid ac system interference being picked up. a separate compensating box with its special power supply unit is required for each analog input module. 23- a d analog input module 460 mux m- 22+ 0 v bus m+ - + power supply for compensating box thermocouple terminal box ~ = # range card for 4 inputs 6es5 498- -1aa11 compensating box figure 9-8 connecting a compensating box analo g input/output modules
9-20 system manual c79000-g8576-c199-07 9.3.10 connecting resistance thermometers in the standard pt 100 range the series-connected resistance thermometers (up to 8 pt 100s) are fed with a current of 2.5 ma (i c+ /i c- ) by a constant current generator. the voltage at the pt 100's is picked off at measurement inputs m+ and m-. in this mode, the whole temperature range of the pt 100 (-200 5 c to +840 5 c) is available. the mode is printed on the cover of the module as follows: aresistance thermometer uncompensated full range.o other voltage sensors can be connected in a floating circuit at the m+/m- inputs of a card which are not assigned to resistance thermometers (voltage range 500 mv). pt 100 - + mux card 1 460 analog input module # d a ch0 ch2 ch1 ch3 m- m + card 2 ch4 0...500 mv u cm 2) 1) ch7 i c- l - l + 0 v bus 2.5 ma const. pt 100 pt 100 pt 100 i c+ u cm 0...500 mv range card for 4 inputs 6es5 498- -1aa11 range card for 4 inputs 6es5 498- -1aa11 figure 9-9 connecting resistance thermometers in the standard pt 100 range 1) if no pt 100 is connected to ch4 to ch7, other voltages and currents can be measured at these channels with cards 6es5 498-1aa21, 6es5 498-1aa31, 6es5 498-1aa41, 6es5 498-1aa51, 6es5 498-1aa61, 6es5 498-1aa71. 2) when cards 6es5 498-1aa41, 6es5 498-1aa51 or 6es5 498-1aa71 are used, a short-circuit jumper is not required. analo g input/output modules
9-21 system manual c79000-g8576-c199-07 9.3.11 connecting resistance thermometers in the extended pt 100 range the series-connected resistance thermometers (up to 8 pt 100s) are fed with a current of 2.5 ma (i c+ /i c- ) by a constant current generator. the voltage at the pt 100s is picked off at measurement inputs m+ and m-. in this mode, the temperature range of approximately -100 5 c to +100 5 c has a more accurate resolution. the mode is printed on the cover of the module as follows: aresistance thermometer compensated low range.o you should only use the 6es5 498-1aa11 range card (  50 mv / 500 mv). unused inputs must be connected in parallel to a wired input. in the following figure, for example, these are the inputs ch4 to ch7. m+ m- ch0 m+ m- ch1 m+ m- ch2 m+ m- ch3 m+ m- ch4 m+ m- ch5 m+ m- ch6 m+ m- ch7 ic- ic+ l+ l- 6es5498- 1aa11 6es5498- 1aa11 24v m24v 2.5ma figure 9-10 connecting resistance thermometers in the extended pt 100 range analo g input/output modules
9-22 system manual c79000-g8576-c199-07 9.3.12 broken wire signal an open-circuit in the lines to a resistance thermometer is indicated as follows: broken wire at module reaction, encoded value error bit e m+ m- pt 100 i c+ i c- 0 0 0 1) 0 0 1 1 1 0 0 1) with the 460 analog input module, the value 0 is also encoded for the intact pt 100 resistances because the auxiliary circuit is interrupted; the error bit will not be set for these channels. if the mode awithout broken wire signalo is selected on the module, an open-circuit of the resistance thermometer is indicated with an overflow. unassigned channels can be used for voltage or current measurement. if a line of the auxiliary circuit (i c+ , i c- ) is interrupted, the anegative range limito is encoded for all inputs and the overflow bit is set to a1.o in the event of a sensor or measuring line open-circuit, the error bit is additionally set to a1o for the relevant channel. broken wire signal in the standard pt 100 range broken wire signal in the extended pt 100 range analo g input/output modules
9-23 system manual c79000-g8576-c199-07 9.3.13 connecting transducers two-wire transducer (short-circuit protected supply voltage via the range card of the analog input module) a d analog input module mux m- 0 v bus m+ + - 4...20 ma l+ l- # range card for 4 inputs 6es5-498- -1aa51 four-wire transducer (with separate supply voltage) a d analog input module mux m- 0 v bus m+ + - +4...20 ma 230 v ac do not exceed max. permissible potential difference! # 6es5-498- -1aa71 range card for 4 inputs four-wire transducer with a two-wire transducer card a d analog input module mux m- 0 v bus m+ + - 0...20 ma 230 v ac l+ l- l- (0 v ext ) # 6es5-498- -1aa71 range card for 4 inputs analo g input/output modules
9-24 system manual c79000-g8576-c199-07 9.3.14 measured-value representation (rated input range  50 mv) units input vlt byte 0 byte 1 voltage in mv 7 2 12 6 2 11 5 2 10 4 2 9 3 2 8 2 2 7 1 2 6 0 2 5 7 2 4 6 2 3 5 2 2 4 2 1 3 2 0 2 a 1 e 0 ov  4096 100.0 0 1 1 1 1 1 1 1 1 1 1 1 1 0/1 0/1 1 overflow 4095 2049 99.976 50.024 0 0 1 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 0/1 0/1 0/1 0/1 0 0 overrange 2048 2047 50.0 49.976 0 0 1 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0/1 0/1 0/1 0/1 0 0 1024 1023 25.0 23.976 0 0 0 0 1 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0/1 0/1 0/1 0/1 0 0 1 0 -1 0.024 0.0 -0.024 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 1 0 1 0/1 0/1 0/1 0/1 0/1 0/1 0 0 0 rated range -1023 -1024 - 24.976 - 25.0 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0/1 0/1 0/1 0/1 0 0 -2047 -2048 - 49.976 - 50.0 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0/1 0/1 0/1 0/1 0 0 -2049 -4095 - 50.024 - 99.976 1 1 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 0/1 0/1 0/1 0/1 0 0 overrange -4096 -100.0 1 0 0 0 0 0 0 0 0 0 0 0 1 0/1 0/1 1 overflow a = active bit e = error bit ov = overflow bit digital measured-value representation as two's complement analo g input/output modules
9-25 system manual c79000-g8576-c199-07 (rated input range  50 mv) units input vlt byte 0 byte 1 voltage in mv 7 s 6 2 11 5 2 10 4 2 9 3 2 8 2 2 7 1 2 6 0 2 5 7 2 4 6 2 3 5 2 2 4 2 1 3 2 0 2 a 1 e 0 ov  4096 100.0 0 1 1 1 1 1 1 1 1 1 1 1 1 0/1 0/1 1 overflow 4095 2049 99.976 50.024 0 0 1 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 0/1 0/1 0/1 0/1 0 0 overrange 2048 2047 50.0 49.976 0 0 1 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0/1 0/1 0/1 0/1 0 0 1024 1023 25.0 23.976 0 0 0 0 1 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0/1 0/1 0/1 0/1 0 0 1 0 -0 -1 0.024 0.0 0.0 -0.024 0 0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0 0 0 0 rated range -1023 -1024 - 24.976 - 25.0 1 1 0 0 0 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 0/1 0/1 0/1 0/1 0 0 -2047 -2048 - 49.976 - 50.0 1 1 0 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 0/1 0/1 0/1 0/1 0 0 -2049 -4095 - 50.024 - 99.976 1 1 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 1 0/1 0/1 0/1 0/1 0 0 overrange -4096 -100.0 1 1 1 1 1 1 1 1 1 1 1 1 1 0/1 0/1 1 overflow a = active bit e = error bit ov = overflow bit bit 2 12 is interpreted as the sign. digital measured-value representation as value and sign analo g input/output modules
9-26 system manual c79000-g8576-c199-07 the resolution with pt 100 resistance thermometers is approximately 0.25 o c. 1 ohm  10 units units resistance in ohm temp. in o c byte 0 byte 1 ohm in o c 7 s 6 2 11 5 2 10 4 2 9 3 2 8 2 2 7 1 2 6 0 2 5 7 2 4 6 2 3 5 2 2 4 2 1 3 2 0 2 a 1 e 0 ov 4096 400.0 - 0 1 1 1 1 1 1 1 1 1 1 1 1 0/1 0/1 1 overflow 4095 2049 399.90 200.98 - 269.1 0 0 1 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 0/1 0/1 0/1 0/1 0 0 overrange 2048 2047 200.0 199.90 266.5 266.0 0 0 1 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0/1 0/1 0/1 0/1 0 0 1024 1023 100.00 99.90 0 -0.2 0 0 0 0 1 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0/1 0/1 0/1 0/1 0 0 rated range 1 0 0.098 0.0 - - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0/1 0/1 0/1 0/1 0 0 a = active bit e = error bit ov = overflow bit s = sign when pt 100 resistance thermometers are connected, the maximum temperature in the rated range is 266 o c. if it can be ensured that the temperature does not exceed 850 o c, the input value may extend into the overrange. the resolution is then 4095 units. unused inputs can be utilized for voltage measurements in the 500 mv range (see front connector assignments). in addition to the standard pt 100 range, there is an extended pt 100 range on the 460 analog input module. you can select this with the mode switch. the following is printed on the cover of the module to set the pt 100 mode: standard range: aresistance thermometer uncompensated full rangeo extended range: aresistance thermometer compensated low rangeo in this range, the basic resistance of the pt 100 at 0 o c (100 ohm) is compensated for on the module. as in the standard range, the pt 100 is fed with a constant current of 2.5 ma. using the overrange (- 100 mv to + 100 mv), this results in a temperature range of approx. -100 5 c to + 100 5 c. this measuring range of 200 5 c is resolved to 8192 units with the correct sign for the temperature. one unit thus corresponds to approximately 0.025 5 c. if you select the extended pt 100 range, you can use all 8 analog inputs in this range only. you should only use the 6es5 498-1aa11 range card (  50 mv/500 mv). measured-value representation for resistance thermometers in the standard pt 100 range extended pt 100 range analo g input/output modules
9-27 system manual c79000-g8576-c199-07 units pt 100/ohm temp. i o c byte 0 byte 1 in o c 7 s 6 2 11 5 2 10 4 2 9 3 2 8 2 2 7 1 2 6 0 2 5 7 2 4 6 2 3 5 2 2 4 2 1 3 2 0 2 a 1 e 0 ov >4095  140.0 0 1 1 1 1 1 1 1 1 1 1 1 1 0 0 1 overflow 4095 2049 139.99 120.01 103.74 51.61 0 0 1 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 0 0 0 0 0 0 overrange 2048 +1 0 -1 -2048 120.0 100.01 100.0 99.99 80 51.58 0.026 0 -0.026 -50.78 0 0 0 1 1 1 0 0 1 1 0 0 0 1 0 0 0 0 1 0 0 0 0 1 0 0 0 0 1 0 0 0 0 1 0 0 0 0 1 0 0 0 0 1 0 0 0 0 1 0 0 0 0 1 0 0 0 0 1 0 0 1 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 rated range -2049 -4095 79.99 60.01 -50.81 -100.60 1 1 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 0 0 0 0 0 0 overrange <-4095  60 1 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1 overflow broken wire -4095 arbitrary arbitrary 1 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1 broken wire ic+/ic- 2) -4095 arbitrary arbitrary 1 0 0 0 0 0 0 0 0 0 0 0 1 0 1 1 broken wire sensor measuring line 1) 1) only with broken wire monitor activated, error bit = 1 only for faulty channel; for sensor broken wire, overflow bit = 1 for all channels 2) on account of the pt 100 series circuit, this bit combination always appears for all channels if the supply line is open-circuit. a = active bit e = error bit ov = overflow bit s = sign measured-value representation in the extended pt 100 measuring range (two's complement) analo g input/output modules
9-28 system manual c79000-g8576-c199-07 measuring range 500 mv; card with 31.25 ohm shunt (6es5 498-1aa51/aa71) the 4 to 20 ma range is resolved to 2048 units at an interval of 512 to 2560. if you require a representation from 0 to 2048, you must subtract 512 units by software. please note the following:  a broken wire signal cannot be emitted.  detection of the overrange can be achieved by scanning bits 2 9 and 2 11 .  a broken wire can be detected with currents < 3 ma.  if you short-circuit the positive and negative terminals of the transducer when using the 6es5 498-1aa51 range card (for a two-wire transducer), the current is limited to about 28 ma. until the thermal current limiting circuit responds in the range card (about 3 s), a short-circuit current of approximately 250 ma flows; this sets the overflow bit for this duration at all channels. units input ct byte 0 byte 1 current in ma 7 s 6 2 11 5 2 10 4 2 9 3 2 8 2 2 7 1 2 6 0 2 5 7 2 4 6 2 3 5 2 2 4 2 1 3 2 0 2 a 1 e 0 ov  4096  32.000 0 1 1 1 1 1 1 1 1 1 1 1 1 0/1 0 1 overflow 4095 3072 3071 2561 31.992 24.0 23.992 20.008 0 0 0 0 1 1 1 1 1 1 0 0 1 0 1 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 0/1 0/1 0/1 0/1 0 0 0 0 0 0 0 0 overrange short-circuit with two- wire transducer 2560 2048 512 20.0 16.0 4.0 0 0 0 1 1 0 0 0 0 1 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0/1 0/1 0/1 0 0 0 0 0 0 rated range 511 384 383 3.992 3.0 2.992 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 0 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 0/1 0/1 0/1 0 0 0 0 0 0 range underflow 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0/1 0 0 broken wire a = active bit e = error bit ov = overflow bit s = sign measured-value representation for current measuring ranges from 4 to 20 ma current limiting analo g input/output modules
9-29 system manual c79000-g8576-c199-07 9.3.15 technical specifications 6es5 460-4ua13 analog input module rated input ranges with cards for every 4 channels - 6es5 498-1aa11 - 6es5 498-1aa21 - 6es5 498-1aa31 - 6es5 498-1aa41 - 6es5 498-1aa51 - 6es5 498-1aa61 - 6es5 498-1aa71  12.5 mv/  50 mv/  500 mv/pt 100  1 v  10 v  5 ma/  20 ma 4 to 20 ma for two-wire transducer  5 v 4 to 20 ma for four-wire transducer number of inputs 8 voltage/current inputs or 8 resistance inputs (pt 100) measured-value representation 13 bits (two's complement) or 12 bits + sign;  2048 units in rated range; 512 to 2560 units for 4 to 20 ma measuring principle integrating isolation yes 8 inputs tested with respect to 0 v at 500 v ac permissible potential difference between reference potentials of sensors and the module (u cm ) and between sensors (channels) 25 v ac/60 v dc max. power supply - digital section from system bus - analog section from load voltage - enabling for module f+/f- - tripping current l+ 5 v  5 %; 130 ma typical 24 v; approx. 50 ma 1) 24 v; approx. 5 ma 24 v; approx. 5 ma constant current source for pt 100 connection i c+ /i c- 2.5 ma; tc =  5 x 10 -5 /k integration time 20 ms at 50 hz; 16 2 / 3 ms at 60 hz encoding time per measured value 60 ms at 50 hz; 50 ms at 60 hz 1) plus 20 ma max. per connected two-wire transducer. analo g input/output modules
9-30 system manual c79000-g8576-c199-07 cycle time for 8 measured values with 2048 units (max. delay time for measured-value acquisition) approx. 0.48 s at 50 hz input resistance (with card) for input ranges:  12.5 mv/  50 mv/  500 mv/pt 100  1 v  5 v/  10 v  5 v/  20 ma 4 to 20 ma  10 m  90 k  50 k  25  31.25  measuring point-related error signal - for overflow - for broken wire ye s yes, configurable (at  12.5 mv,  50 mv  500 mv and pt 100 1) ) max. permissible input voltage without destruction  18 v; 75 v for 1 ms max. and duty ratio 1:20 interference suppression for f = n x (50/60 hz  1 %) - with common-mode interference - with differential-mode interference  100 db  40 db, interference voltage amplitude but 100 % max. of measuring range referred to peak value error referred to rated value - linearity - tolerance at  50 mv at  12.5 mv - polarity reversal error at  50 mv at  12.5 mv - temperature error  1 unit  1 unit  3 units  1 unit  2 units 1 x 10 -4 /k error caused by modules with input range  1 v/  5 v /  10 v  20 ma/4 to 20 ma 2 x 10 -3 ; tc =  10 x 10 -5 /k 10 -3 ; tc =  5 x 10 -5 /k voltage test to vde 0160 between inputs and ground point tested at 500 v ac extended pt 100 measuring range measuring range including overrange resolution basic error at t = 25 o c operational error at t = 0 to 65 o c range card approx. - 100 o c to + 100 o c 0.025 o c per unit  0.2 o c max.  0.5 o c max. 6es5 498-1aa11 environmental specifications see technical specifications of the s5-135u/155u cc 1) in the event of open-circuit of the live i c+ and i c- lines, the digital value 0 is indicated. analo g input/output modules
9-31 system manual c79000-g8576-c199-07 you select the desired mode of the analog input module by setting mode switches i and ii according to the following table. please note that all switch rockers marked with a dot must be set on both mode switches. to set the desired mode, press the rockers downwards on the side marked with a dot in the table. mode mode switch i (digital section) mode switch ii (digital section) without reference point compensation with reference point compensation measuring range extended pt 100 measuring range 500 mv; ma (standard pt 100 measuring range) 50 mv value and sign two's complement gain x 1 (normal setting) gain x4 sampling selective cyclic line frequency 50 hz 60 hz channels 0 to 3 with broken wire signal channels 4 to 7 channels 0 to 3 without broken wire signal channels 4 to 7 x = switch is not assigned; any switch setting. = switch setting setting the mode analo g input/output modules
9-32 system manual c79000-g8576-c199-07 labeling of switches on the module cover: line frequency 50 hz result and sign two`s complement normal mode (gain*1) special mode (gain*4) single scanning mark selected switch positions here mark selected switch positions here broken wire detection channel 0...3 without compensation with compensation resistance thermometer compensated low range 500 mv v...ma resistance thermometer uncompensated full range broken wire detection channel 4...7 without broken wire detection si sii line frequency 60 hz 50mv =press cyclic scanning voltage compens. input range data format gain submodule1 (ch. 0...3) submodule 2 (ch. 4...7) note ensure that all the switches are operated properly (meaning pressed past the latching point). on one 460 analog input module, you can insert two cards to connect four inputs each, and secure them with a srew. there are voltage divider, shunt and through-connection cards for the various ranges. inserting range cards analo g input/output modules
9-33 system manual c79000-g8576-c199-07 circuit of the cards, 4x mode 50 mv + gain x 1 mode 500 mv/ ma pt 100 + gain x 1 -1aa11 -1aa21 -1aa31 -1aa41 -1aa51 -1aa61 -1aa71 m+ m- m+ m- m+ m- m+ m- m+ m- m+ m- m- l+ l- range card type 6es5 498- m+  500 mv pt 100  1 v  10 v  5 v 4...20ma 2-wire transducer  20 ma 4...20ma 4-wire transducer - (  100 mv)  50 mv (  1 v) (  2 ma) (  500 mv) - mode 500 mv/ ma + gain x 4 mode 50 mv + gain x 4 (  125 mv) (  25 mv) (  12.5 mv) (  1.25 v) (  5 ma) (  2.5 v) (  250 mv) - - - - - - - for a defined mode (50 mv or 500 mv) you can insert cards with different ranges for four inputs, e.g. for the 500 mv mode:  4 inputs, range  500 mv; 1 card 6es5 498-1aa11  4 inputs, range  10 v; 1 card 6es5 498-1aa31 analo g input/output modules
9-34 system manual c79000-g8576-c199-07 voltage or current-input resistance thermometer or connection of two-wire transducer i const. 1 2 3 4 6 8 10 13 15 17 19 21 22 23 25 27 29 31 34 36 38 40 41 42 f+ l+ f- l- ch.0 ch.1 ch.2 ch.3 comp.+ comp.- ch.4 ch.5 ch.6 ch.7 data memory and s5 bus control adu t range card 2 range card 1 i c+ c- i l- i trip 24 l+ 3) 4) # front strip pin l- l- l+ i const. connection of process signal lines 1 2 3 4 6 8 10 13 15 17 19 21 22 23 25 27 29 31 34 36 38 40 41 42 f+ l+ 1) f- l- ch.0 1) + - ch.1 1) + - ch.2 1) 4) + - ch.3 comp.+ comp.- i+ c i- c t t t t 1) 1) 1) 1) + - + - 2)ch.4 + - + - + - 2)ch.5 2)ch.6 2)ch.7 adu t range card 2 range card 1 6es5 498-1aa51 i trip l+ 3) 24 # front strip pin connection of process signal lines block diagram of the modules block diagram of the modules data memory and s5 bus control figure 9-11 front connector assignments 1) observe permissible potential difference between sensor ground and reference potential of modules or between sensor grounds. 2) two-wire transducer 3) only required to switch off the tripping current without broken wire detection; 0 v at l-. (refer to section 9.3.3) 4) connect l- to the central ground point (reference potential). front connector assignments analo g input/output modules
9-35 system manual c79000-g8576-c199-07 9.4 the 463 analog input module 9.4.1 design the modules are designed as plug-in pcbs for central controllers and expansion units with a backplane connector and with a blade connector to accept a plug-in front connector. you can directly connect the process signal lines to the front connector, which is available separately, with screw or crimp terminals. situated on each module is an addressing switch with six rockers to set the module address. analog input modules also have two switches on the side with eight rockers for setting the mode, and receptacles for range cards. the modules are protected by covers on both sides. blade connector addressing switch mode switch front connector figure 9-12 analog input module 9.4.2 function of the enable input the 463 module has an enable circuit. you can use the enable inputs to switch off individual modules whilst the plc is in operation. this means that:  the module can no longer be addressed by the user program. modules which are switched off can be removed or inserted during operation. if this is not necessary, operate the module with the enable input switched off. addressing switch, mode switches analo g input/output modules
9-36 system manual c79000-g8576-c199-07 the enable circuit requires an external 24 v voltage at enable inputs f+/f- in the front connector. if there is no voltage at f+/f-, the modules will not acknowledge. when the front connector is swivelled away from the front strip of the module, the supply of power to the enable input is interrupted, i.e. the module is switched off and can no longer be addressed by the user program: a timeout (qvz) occurs in the cc. the -4ux12 type modules additionally offer the facility for changing the enable mode. the modules have a jumper accessible from above in the vicinity of the addressing switch. enable jumper figure 9-13 enable input and enable jumper jumper inserted: enable input (f+/f-) active (factory setting) jumper open: enable input (f+/f-) switched off examples of functioning of the enable inputs:  to switch off individual subprocesses, i.e. outputs of various modules can be operated from a common load supply and yet activated separately.  the load voltage of individual modules can be monitored without additional circuitry. any reactions to failure of the load voltage can be programmed in the qvz (timeout) organization block. enable input switching off the enable input analo g input/output modules
9-37 system manual c79000-g8576-c199-07 you must observe the following when configuring systems: switching on at the latest 100 ms after power-up of the plc, the voltage must be present at the enable inputs of the i/o modules. switching off when the plc has been switched off, the voltage at the enable inputs of the i/o modules must still be present as long as the internal 5 v voltage is present. you should observe the following instructions for switching off ccs and equipment for supplying power to the enable inputs. when there is a need to switch off the load power supply separately without affecting the enabling of modules, there are the following possibilities for producing the enable voltage. these exist even when the load power supply is used without an additional capacitor and common shutdown.  230 v ac supply for cc/eu and load power supply f+ l+ i/o modules 230 v ac cc/eu -951 a) c) b) battery l+ power supply load power supply 24v supply for the enable inputs from: a) 6es5 951-4lb11 load power supply b) battery c) terminals for 24 v on the front plate of the power supply configuring switching off the cc separate or common shutdown of the cc/eu and load power supply analo g input/output modules
9-38 system manual c79000-g8576-c199-07  24 v supply for cc/eu and i/os f+ l+ i/o modules 24 v dc b) a) cc/eu l+ battery power supply 24v supply for the enable inputs from: a) battery b) terminals for 24 v on the front plate of the power supply proper functioning is ensured if the 24 v load power supply has an output capacitance of at least 4700  f per 10 a of load current. other units which do not meet this condition can be adapted to this requirement by connecting a 10000  f /40 v capacitor in parallel. 10000 m f/40v cc/eu f+ l+ 230 v ac i/o modules load power supply 24v power supply common shutdown of the cc/eu and load power supply with a 230 v ac supply analo g input/output modules
9-39 system manual c79000-g8576-c199-07 9.4.3 special features of the 463 analog input module the 463 analog input module executes integrating processing of the digital input signals; periodic system interference is thus suppressed. the module 463-4ua12 is suitable for operation near 50 hz systems, the module 463-4ua12 is suitable for operation near 60 hz systems. in the subsequent module 463-ua13 the system frequency can be set by switch. the measuring range for each channel is adapted by appropriately connecting the sensors and with jumpers in the front connector of the module (see the front connector assignments). note the ohmic resistance of the jumper with which the measuring range is set is also measured. as the resistance of this jumper is not inconsiderable (0.5 to 0.7 ohm in relation to the measuring shunt of 50 ohm) when i/o module cables with integral connectors and subsequent wiring blocks are used, the measurement result may be corrupted accordingly. 9.4.4 setting the module address you set the module address on the addressing switch. this also establishes the necessary assignments between user program and process connection. the module address is the sum of the decimal significances of the switch rockers in the on setting ( ). one data word = two data bytes is required to process an input or an output. a module with 4 inputs therefore reserves 8 byte addresses. you can affix the adhesive label with the desired module address on a free labeling field under the addressing switch. the switch rockers to be set for the module address specified as a decimal number (address bit adb) are marked by dots on the label. the unmarked switches should be switched off. note press the individual rockers of the addressing switch downwards with a ballpoint pen or similar object, but not a pencil. ensure that all the switches are operated properly (meaning pressed past the latching point). adaptation of the measuring range labeling field analo g input/output modules
9-40 system manual c79000-g8576-c199-07 on setting (switch pressed) addressing switch address bit decimal significance of the address bit adresse (dezimal) adb2 is not connected adb0 and adb1 are not assigned 128 64 32 16 8 4 2 1 adb7 adb6 adb5 adb4 adb3 adb2 adb1 adb0 free field for label with module address and marked switch settings figure 9-14 labeling of the addressing switch the address under which the module is referenced by the step 5 program is independent of the slot. for analog input and analog output modules (4 inputs) only the lowest address (start address) is set. other addresses (subaddresses) are decoded on the module. note the start address of the analog module must be a multiple of the double channel number. 4 channels : 0, 8, 16, 24, ... 248 if one of the inputs or outputs (channel 0 to 3) of a module is to be addressed, the relevant subaddress must be specified in the program. the subaddress of the input or output, based on the start address of the module, is given by: start address + 2 x channel no. = subaddress start address, subaddress analo g input/output modules
9-41 system manual c79000-g8576-c199-07 example : analog input module with 4 inputs the address is the sum of the significances set with the individual coding switches. 160 = 128 + 32 = 2 7 + 2 5 ib 160 128 64 32 16 8 4 2 1 adb7 adb6 adb5 adb4 adb3 adb2 adb1 adb0 on setting (switch pressed) a module with 4 inputs (channel 0 to 3) and start address 160 reserves the address range from 160 to address 160 + 3 x 2 = 166 in this example, the next free address for another module is 168. addresses already assigned must not be set again. example : on an analog input module with start address 160 (ib 160 = input byte 160), input channel 3 is to be scanned by the program. step action 1 affix the self-adhesive label with address 160 on the free field under the addressing switch on the module. adb 5 and adb 7 are marked on the label. 2 press the appropriate rockers of the addressing switch down on the side marked by a dot on the module cover. set the other rockers to the opposite setting. this way sets the start address of the module. adb 5 and adb 7 results in 2 5 + 2 7 = 32 + 128 = 160 3 enter the address 160 + 3 x 2 = 166 in the program for input channel 3. analo g input/output modules
9-42 system manual c79000-g8576-c199-07 9.4.5 removing and inserting modules ! warning when removing and inserting the front connector during operation, hazardous voltages of more than 25 v ac or 60 v dc may be present at the module pins. when this is the case at the front connector, live modules may only be replaced by electrical specialists or trained personnel in such a way that the module pins are not touched. during operation, the front connector and module must not be removed or inserted without the enable jumper or active enable circuit. install an analog input/output module as follows: step action 1 release the upper locking bar on the subrack and swivel it upwards and out. 2 insert the module at the desired slot in the subrack and push it back in the guides. 3 latch the module by rotating the locking pin by 90 o at the lower end of the module. it must no longer be possible to pull the module forwards. 4 engage the front connector on the support pin of the module. the width of the support pin also provides keying to prevent front connectors from being fitted to the wrong modules (for example, front connectors with 115/230 v ac wiring cannot be plugged into analog modules). 5 tighten the screw in the upper part of the front connector. analo g input/output modules
9-43 system manual c79000-g8576-c199-07 remove an analog input/output module as follows: step action 1 release the upper locking bar on the subrack and swivel it upwards and out. 2 slacken the screw in the upper part of the front connector. this causes the front connector to be pressed out of the female connector of the module. contacts f+ and f- of the enable input at the upper end of the front connector are thus opened first. if the enable input is active, power is removed from the outputs and the module is isolated from the s5 bus. 3 swing the front connector out and lift it away from the support pin of the module. 4 release the module by rotating the locking pin by 90  at the lower end of the module. you can pull the module out of the subrack with a grip with swivels outwards. 1 2 3 5 6 4 module front connector support mount support pin figure 9-15 module with front connector 1 screw 2 locking pin 3 support mount 4 support pin 5 grip 6 backplane connector comply with vde specifications 0110 and 0160 to carry out the wiring of supply and signal lines which are to be connected to the programmable controllers and front connectors of the modules. detailed information on cabinet assembly, cabinet ventilation and protective measures can be found in chapter 3. analo g input/output modules
9-44 system manual c79000-g8576-c199-07 9.4.6 marking of modules and front connectors for the marking of modules and front connectors, labels are supplied with the module and central controller; they are affixed as shown in figure 9-16. 1 1 2 3 45 figure 9-16 marking and labeling of modules 1 label with the module address under which the module is referenced by the step 5 program 2 labeling strip with the product designation for the module; space to mark the module version and label the channels 3 label with module address and marking of the required settings for the addressing switch 4 labeling strip for terminal designations or connection diagrams (strip in the cover of the front connector) 5 name plate analo g input/output modules
9-45 system manual c79000-g8576-c199-07 9.4.7 connecting the signal lines for connection of the signal lines, front connectors for 20 and 40 mm mounting width with crimp connection and 40 mm mounting width with screw connection are available (screwdriver blade width: 3.5 mm, maximum torque: 0.8 nm). use stranded conductor to facilitate handling of the front connector. ferrules are not required for screw connections, because the screw terminals are provided with wire protection. when the crimp contact is inserted in the plastic body of the front connector, a click can clearly be heard. this indicates that the contact is engaged. for jumpering or to correct the wiring, you can remove the contacts with a releasing tool (see ordering information) without having to pull out the front connector. ferrules are not required for screw connections, because the screw terminals are provided with wire protection. you can use ferrules of 7 mm in length to din 46228. the maximum terminal area is 2 x 2.5 mm 2 . terminal t connector t max. nf cross-section connector for rtdvlt mounting width of mdl type type 6es 497- no. of contacts signal or supply conductor aux. jumper in connector 1) rated voltage module crimp connection -4ua12 2) 42 0.5 mm 2 0.5 mm 2 5 to 60 v dc 20 mm operation with fan -4ua22 2) 42 0.5 mm 2 0.5 mm 2 5 to 60 v dc 40 mm oti screw ti -4ub12 42 0.5 to 2.5 mm 2 0.5 to 1.0 mm 2 5 to 60 v dc 40 mm operation without fan connection -4ub31 42 0.5 to 1.5 mm 2 0.5 to 1.0 mm 2 5 to 60 v dc 20 mm without fan 1) to multiply the supply and 0 v ground terminals, and to connect the enable input. 2) the crimp contacts must be ordered separately for these types of connector. ! caution only extra-low voltage 60 v dc with safety separation from system voltage may be used for the 24 v dc supply and for the 24 v dc input signals. safety separation can be implemented to the requirements of, amongst other sources, vde 0100 part 410/hd 384-4-41/iec 60364-4-41 (as functional extra-low voltage with safety separation) or vde 0805/en 60950/iec 6050 (as safety extra-low voltage selv) or vde 0106 part 101. analo g input/output modules
9-46 system manual c79000-g8576-c199-07 9.4.8 measured-value representation (rated input ranges 0 to 1 v, 0 to 10 v, 0 to 20 ma, 4 to 20 ma) units rated range byte 0 byte 1 0...10 v 0...1 v mv 0... 20 ma 4...20 ma 1) 4...20 ma 2) 7 2 11 6 2 10 5 2 9 4 2 8 3 2 7 2 2 6 1 2 5 0 2 4 7 2 3 6 2 2 5 2 1 4 2 0 3 0 2 0 1 0 0 ov 2047 1536 19.99 15.00 1999 1500 39.98 30.00 35.98 28.00 31.98 24.00 0 0 1 1 1 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 0 0 0 0 0 0 1 1 3) 1535 1280 1025 14.99 10.01 1499 1001 29.98 20.02 27.98 20.02 23.98 20.00 16.02 0 0 0 1 1 1 0 0 0 1 1 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 1 0 0 0 0 0 0 0 0 0 0 0 0 4) 1024 1023 512 511 256 1 0 - 1 - 51 10.00 9.99 5.00 4.99 2.5 0.0098 0 -0.009 8 -0.5 1000 999.02 500.00 499.00 250 0.976 0 0.976 -50 20.00 19.98 10.00 9.98 5.0 0.02 0 -0.02 -1 20.00 19.98 12.00 11.98 8.0 4.0156 4 3.9844 3.184 16.00 15.98 8.00 7.98 4.00 0.0156 0 -0.015 6 -0.816 0 0 0 0 0 0 0 1 1 1 0 0 0 0 0 0 1 1 0 1 1 0 0 0 0 1 1 0 1 0 1 1 0 0 1 1 0 1 0 1 0 0 0 1 1 0 1 0 1 0 0 0 1 1 0 1 0 1 0 0 0 1 0 0 1 0 1 0 0 0 1 0 0 1 0 1 0 0 0 1 1 0 1 0 1 0 0 0 1 1 0 1 0 1 0 0 0 1 0 0 1 0 1 0 1 0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5) 1) with data format setting 0 to 1023 (switch on module) 2) with data format setting 256 to 1279 (switch on module) 3) overflow 4) overrange 5) rated range ov = overflow bit a 50 ohm shunt resistor is used for the 0 to 20 ma range; for 4 to 20 ma, the resistor value is 62.5 ohm. the shunt resistors are permanently fitted to the 463 analog input module. broken wire detection is not possible. for the 4 to 20 ma current measuring range, a broken wire can be detected with currents > 3 ma. if the positive and negative terminals of the transducer are short-circuited when two-wire transducers are used (4 to 20 ma), the current is limited to approximately 28 ma. until the thermal current limiting circuit responds (about 3 s) a short-circuit current of about 250 ma flows. the failure of the load voltage can be detected from the result of encoding (values < -51 units). the module 463-4ua13 does not require 24v voltage. a 24v supply is required when connecting a 2-wire measuring transducer. measured-value representation as value and sign shunt resistor current limiting load voltage analo g input/output modules
9-47 system manual c79000-g8576-c199-07 9.4.9 technical specifications 6es5 463-4ua12/6es5 463-4ub12 and 6es5 463-4ua13 analog input modules rated input ranges (selectable at front connector) - 0.05 to + 1 v - 0.5 to + 10 v -1 to + 20 ma + 4 to 20 ma for 2-wire transducer + 4 to 20 ma for 4-wire transducer number of inputs 4 voltage/current inputs measured value representation 11 bits (two's complement) 1024 units in rated range overrange 50 % (with full accuracy) error signal for overflow yes (upward of 50 % overrange) measuring principle integrating conversion principle voltage-frequency conversion isolation yes, 4 inputs with respect to 0 v and each other permissible potential difference between ref. potentials of sensors and module (u cm ) and between sensors (channels) 25 v ac/60 v dc max. power supply - digital section from system bus - analog section from load voltage - enabling of module f+/f- 5 v  5 %; 150 ma typ. for 463-4ua13 200 ma typ. 24 v; approx. 150 ma. irrelevant for 463-4ua13 24 v; approx. 7 ma integration time - 463-4ua12 - 463-4ub12 - 463-4ua13 20 ms at 50 hz 16 2 / 3 ms at 60 hz 50/60 hz operation can be set by a switch encoding time per measured value - 463-4ua12 - 463-4ub12 - 463-4ua13 20 ms at 50 hz 16 2 / 3 ms at 60 hz 50/60 hz operation can be set by a switch cycle time for 4 measured values (max. delay time of measured value acquisition) - 463-4ua12 - 463-4ub12 - 463-4ua13 20 ms at 50 hz 16 2 / 3 ms at 60 hz 50/60 hz operation can be set by a switch input resistance for input ranges 1 v 10 v 20 ma 4 to 20 ma > 10 m  90 k  50  62.5  max. permissible input voltage without destruction  30 v; 75v for 1 ms max. and duty ratio 1:10 interference suppression - with common-mode interference - with differential-mode interference > 80 db (f = 0 to 50 khz) > 40 db (v noise  0.1 u n ) error, referred to - rated value - linearity - tolerance - temperature error  5 x 10 -4  1 unit  3 units 0.6 x 10 -4 /k voltage test to vde 0160 between inputs and ground point, and between 2 inputs; tested at 500 v ac analo g input/output modules
9-48 system manual c79000-g8576-c199-07 when using the 4 to 20 ma inputs, you can select data representation of 0 to 1023 bits or 256 to 1279 bits by pressing the appropriate switch. you can choose different data formats for all four input channels. when the voltage or 0 to 20 ma inputs are used, the relevant switches remain at the opposite settings. note ensure that all the switches are operated properly (meaning pressed past the latching point). labeling of the switch on the module cover: range 4...20 ma 0...1023 range 4...20 ma 256...1279 otherranges 0...1023 channel 2 channel 0 channel 1 channel 2 channel 3 channel 3 channel 1 channel 0 2) operation mode 50 hz 2) operation mode 60 hz 1) 1) 1) 1) 1) 1) 1) 1) 1) 1) 1) it is advisable to mark the selected switch setting in these fields 2) only for 463-4ua13 transducers are connected to the analog input module via shielded cables of up to 200 m in length. when they are laid separately from power system cables, distances of up to 500 m are possible. an arbitrary mixture of voltage sensor, current sensor, two-wire and four-wire transducers can be connected. for two-wire transducers, there are four short-circuit protected supply terminals at the front connector. ! caution to use two-wire transducers, the reference potential (common input) of these channels must be connected to l-. this defeats the isolation between the channels and the supply voltage l+/l-. note that the bus interface of the module is activated with 24 v via enable lines f+ and f- at the front connector. setting the data format for the 4 to 20 ma range connecting transducers analo g input/output modules
9-49 system manual c79000-g8576-c199-07 f+ l+ f- + - + - + - + - f+ l+ f- f+ l+ f- f+ l+ f- f+ l+ f- 1 2 3 4 6 8 10 13 15 17 19 21 22 23 25 27 29 31 34 36 38 40 41 42 5 7 9 11 12 16 14 18 20 24 28 32 33 26 30 37 35 39 - 7 + - 6 7 + - 5 7 + - 6 7 +4 6 - 16 + - 15 16 + - 14 16 + - 15 16 +13 15 l- l- l- l- l- - 28 +25 27 + - 27 28 + - 26 28 + - 27 28 - 37 +34 36 + - 36 37 + - 35 37 + - 36 37 range 4-20ma range 0-1v range 0-10v range 0-20ma range 4-20ma (2-wiretransd.) (4-wire ransd.) block diagram of the module front strip pin bus control t data memory l- l+ + +10v +1v common common 0-10v 0-20ma 4-20ma +10v +1v common common 0-10v 0-20ma 4-20ma ch.0 ch.1 ch.2 ch.3 4x 15v + - +10v +1v common common 0-10v 0-20ma 4-20ma +10v +1v common common 0-10v 0-20ma 4-20ma 15v + - + + + mu mu mu mu data memory data memory data memory * = not required for 463-4ua13 * ** * ch 0 ch 1 ch 3 ch 4 figure 9-17 front connector assignments, sensor connection, range selection front connector assignments analo g input/output modules
9-50 system manual c79000-g8576-c199-07 9.5 the 465 analog input module 9.5.1 design the modules are designed as plug-in pcbs for central controllers and expansion units with a backplane connector and with a blade connector to accept a plug-in front connector. you can directly connect the process signal lines to the front connector, which is available separately, with screw or crimp terminals. situated on each module is an addressing switch with six rockers to set the module address. analog input modules also have two switches on the side with eight rockers for setting the mode, and receptacles for range cards. the modules are protected by covers on both sides. blade connector addressing switch mode switch front connector figure 9-18 analog input module 9.5.2 function of the enable input the 465 module has an enable circuit. you can use the enable inputs to switch off individual modules whilst the plc is in operation. this means that:  the module can no longer be addressed by the user program. modules which are switched off can be removed or inserted during operation. if this is not necessary, operate the module with the enable input switched off. addressing switch, mode switches analo g input/output modules
9-51 system manual c79000-g8576-c199-07 the enable circuit requires an external 24 v voltage at enable inputs f+/f- in the front connector. if there is no voltage at f+/f-, the modules will not acknowledge. when the front connector is swivelled away from the front strip of the module, the supply of power to the enable input is interrupted, i.e. the module is switched off and can no longer be addressed by the user program: a timeout (qvz) occurs in the cc. the 465 module additionally offers the facility for changing the enable mode. the module has a jumper accessible from above in the vicinity of the addressing switch. enable jumper figure 9-19 enable input and enable jumper jumper inserted: enable input (f+/f-) active (factory setting) jumper open: enable input (f+/f-) switched off examples of functioning of the enable inputs:  to switch off individual subprocesses, i.e. outputs of various modules can be operated from a common load supply and yet activated separately.  the load voltage of individual modules can be monitored without additional circuitry. any reactions to failure of the load voltage can be programmed in the qvz (timeout) organization block. enable input switching off the enable input analo g input/output modules
9-52 system manual c79000-g8576-c199-07 you must observe the following when configuring systems: switching on at the latest 100 ms after power-up of the plc, the voltage must be present at the enable inputs of the i/o modules. switching off when the plc has been switched off, the voltage at the enable inputs of the i/o modules must still be present as long as the internal 5 v voltage is present. you should observe the following instructions for switching off ccs and equipment for supplying power to the enable inputs. when there is a need to switch off the load power supply separately without affecting the enabling of modules, there are the following possibilities for producing the enable voltage. these exist even when the load power supply is used without an additional capacitor and common shutdown.  230 v ac supply for cc/eu and load power supply f+ l+ i/o modules 230 v ac cc/eu -951 a) c) b) battery l+ power supply load power supply 24v supply for the enable inputs from: a) 6es5 951-4lb11 load power supply b) battery c) terminals for 24 v on the front plate of the power supply configuring switching off the cc separate or common shutdown of the cc/eu and load power supply analo g input/output modules
9-53 system manual c79000-g8576-c199-07  24 v supply for cc/eu and i/os f+ l+ i/o modules 24 v dc b) a) cc/eu l+ battery power supply 24v supply for the enable inputs from: a) battery b) terminals for 24 v on the front plate of the power supply proper functioning is ensured if the 24 v load power supply has an output capacitance of at least 4700  f per 10 a of load current. other units which do not meet this condition can be adapted to this requirement by connecting a 10000  f / 40 v capacitor in parallel. 10000 m f/40v cc/eu f+ l+ 230 v ac i/o modules load power supply 24v power supply common shutdown of the cc/eu and load power supply with a 230 v ac supply analo g input/output modules
9-54 system manual c79000-g8576-c199-07 9.5.3 special features of the 465 analog input module the 465 analog input module executes integrating processing of the digital input signals; periodic system interference is thus suppressed. you can adapt the process signals, according to the application, to the input level of the analog-to-digital converter of the module with plug-in range cards (resistor dividers or shunt resistors). to monitor the sensors connected to the inputs, you can use the 6es5 498-1aa11 range card (through-connection card) to implement the abroken wire detectiono mode. you can activate broken wire detection for 8 or 16 inputs in 16-channel operation, and for 4 or 8 inputs in 8-channel operation. each time the input value is about to be encoded, a constant current is briefly (1.6 ms) switched to the input terminals and the resultant current is checked for a limit value. if a digital voltmeter is used to measure the signal at the input, these current pulses may appear to indicate fluctuation of the signal. the encoded value, however, is not affected. if these apparent fluctuations of the signal are disturbing, for example, during startup, you can switch the tripping current to the inactive state on the 465 analog input modules: apply + 24 v to pin 24 of the front connector, and 0 v to l-. you must additionally set the mode switch to awithout broken wire detection.o in the event of open-circuit of the sensor or its line, the voltage exceeds the limit and a broken wire is indicated (bit 1 in data byte 1). the analog-to-digital converter encodes the value 0. a broken wire signal is only useful when the 6es5 498-1aa11 through-connection card is used. with all other measurement cards, a broken wire signal will result in incorrect reactions. further details relating to the broken wire signal can be found in section 9.5.10. if the measuring range is exceeded, the overflow bit (bit 2 0 of the low byte) is set. you have a choice of the cyclic sampling and selective sampling modes. in the cyclic sampling mode, the module continuously encodes all measured values. the digitized measured values are stored under the channel-related address on the module (the high byte under this address, and the low byte under the next higher address). the measured values can then be read by the module at any time without waiting. when you operate the module in this mode, you can set a module address from 0 to 255. broken wire signal switching the tripping current to the inactive state measuring range exceeded cyclic sampling/ selective sampling analo g input/output modules
9-55 system manual c79000-g8576-c199-07 in the selective sampling mode, a measured value is encoded on the central initiative of the cpu. at the start of conversion, the module must be addressed once with a write operation (t pw) by the user program. an active bit (t = 1) is set during encoding. with the transition to t = 0, the measured value becomes valid. with non-constant cycle times, there may be non-periodic measured value aquisition. if you operate the module in this mode, you must set a module address from 128 to 255. you can also use the address range from 0 to 127 for selective sampling after appropriate programming in db 1 of the user program. another method is that of time-controlled program processing. with this method, certain program segments (e.g. fb 13) are automatically inserted into program processing at the 100 ms rate by a time-controlled block (ob 13). a constant timebase is thus achieved. fb 13 sprm-b len=22 abs sheet 1 segment 1 name: selsampl example of selective sampling 0005 : 0006 : 0007 :l pw128 read analog value 0008 :t fw128 in to aux: flag 128 0009 :s f 129.2 scan activity=1? 000a :jc = end if = 1, jump to end 000b :t fw10 if = 0, measured value in fw 10 000c :t pb128 initiate sampling 000d end : (1st value invalid after start) 000e 000f : 0010 :be you can read analog values of analog input modules with a function block from the abasic functionso package. the basp signal is not interpreted by the 460 analog input module. time-controlled program processing function block basp (output inhibit) analo g input/output modules
9-56 system manual c79000-g8576-c199-07 9.5.4 setting the module address you set the module address on the addressing switch. this also establishes the necessary assignments between user program and process connection. the module address is the sum of the decimal significances of the switch rockers in the on setting ( ). one data word = two data bytes is required to process an input. a module with 8 inputs therefore reserves 16 byte addresses, and a module with 16 inputs or outputs reserves 32 byte addresses. you can affix the adhesive label with the desired module address on a free labeling field under the addressing switch. the switch rockers to be set for the module address specified as a decimal number (address bit adb) are marked by dots on the label. note press the individual rockers of the addressing switch downwards with a ballpoint pen or similar object, but not a pencil. ensure that all the switches are operated properly (meaning pressed past the latching point). on setting (switch pressed) addressing switch address bit decimal signification of the address bit free field for label with module address and marked switch settngs address (decimal) 128 64 32 16 8 4 2 1 adb7 adb6 adb5 adb4 adb3 adb2 adb2 is not connected adb1 adb0 adb0 and adb1 are not assigned figure 9-20 labeling of the addressing switch the address under which the module is referenced by the step 5 program is independent of the slot. for analog input and analog output modules (8 or 16 inputs) only the lowest address (start address) is set. other addresses (subaddresses) are decoded on the module. labeling field start address, subaddress analo g input/output modules
9-57 system manual c79000-g8576-c199-07 note the start address of the analog module must be a multiple of the double channel number. 8 channels : 0, 16, 32, 48, ... 240 16 channels : 0, 32, 64, 96, ... 224 if one of the inputs or outputs (channel 0 to 7 or 0 to 15) of a module is to be addressed, the relevant subaddress must be specified in the program. the subaddress of the input or output, based on the start address of the module, is given by: start address + 2 x channel no. = subaddress example: analog input module with 8 or 16 inputs the address is the sum of the significances set with the individual coding switches. 160 = 128 + 32 = 2 7 + 2 5 on setting (switch pressed) ib 160 128 64 32 16 8 4 2 1 adb7 adb6 adb5 adb4 adb3 adb2 adb1 adb0 a module with 8 or 16 inputs (channel 0 to 7 or 0 to 15) and start address 160 reserves the address range from 160 to address 160 + 7 x 2 = 174 160 to address 160 + 15 x 2 = 190 in this example, the next free address for another module is 176 or 192. with the 465 analog input module, the size of the address range depends on the number of channels set (8 or 16). addresses already assigned must not be set again. analo g input/output modules
9-58 system manual c79000-g8576-c199-07 however, analog input modules and analog output modules may be given the same address with cyclic sampling because they are distinguished by the user program. this is not possible with selective sampling. for cyclic sampling, you can address the module in the address range from 0 to 255, and for selective sampling from 128 to 255. for selective sampling, you can also use the address range from 0 to 127 after appropriate programming in db 1 of the user program. example: on an analog input module with start address 160 (ib 160 = input byte 160), input channel 3 is to be scanned by the program. step action 1 affix the self-adhesive label with address 160 on the free field under the addressing switch on the module. adb 5 and adb 7 are marked on the label. 2 press the appropriate rockers of the addressing switch down on the side marked by a dot on the module cover. set the other rockers to the opposite setting. this way the start address of the module is set. adb 5 and adb 7 results in 2 5 + 2 7 = 32 + 128 = 160 3 enter the address 160 + 3 x 2 = 166 in the program for input channel 3. addressing for cyclic/selective sampling analo g input/output modules
9-59 system manual c79000-g8576-c199-07 9.5.5 removing and inserting modules ! warning when removing and inserting the front connector during operation, hazardous voltages of more than 25 v ac or 60 v dc may be present at the module pins. when this is the case at the front connector, live modules may only be replaced by electrical specialists or trained personnel in such a way that the module pins are not touched. during operation, the front connector and module must not be removed or inserted without the enable jumper or active enable circuit. install an analog input/output module as follows: step action 1 release the upper locking bar on the subrack and swivel it upwards and out. 2 insert the module at the desired slot in the subrack and push it back in the guides. 3 latch the module by rotating the locking pin by 90 o at the lower end of the module. it must no longer be possible to pull the module forwards. 4 engage the front connector on the support pin of the module. the width of the support pin also provides keying to prevent front connectors from being fitted to the wrong modules (for example, front connectors with 115/230 v ac wiring cannot be plugged into analog modules). 5 tighten the screw in the upper part of the front connector. analo g input/output modules
9-60 system manual c79000-g8576-c199-07 remove an analog input/output module as follows: step action 1 release the upper locking bar on the subrack and swivel it upwards and out. 2 slacken the screw in the upper part of the front connector. this causes the front connector to be pressed out of the female connector of the module. contacts f+ and f- of the enable input at the upper end of the front connector are thus opened first. if the enable input is active, power is re- moved from the outputs and the module is isolated from the s5 bus. 3 swing the front connector out and lift it away from the support pin of the module. 4 release the module by rotating the locking pin by 90 o at the lower end of the module. you can pull the module out of the subrack with a grip with swivels outwards. 1 2 3 5 6 4 module front connector support mount support pin figure 9-21 module with front connector 1 screw 2 locking pin 3 support mount 4 support pin 5 grip 6 backplane connector comply with vde specifications 0110 and 0160 to carry out the wiring of supply and signal lines which are to be connected to the programmable controllers and front connectors of the modules. detailed information on cabinet assembly, cabinet ventilation and protective measures can be found in chapter 3. analo g input/output modules
9-61 system manual c79000-g8576-c199-07 9.5.6 marking of modules and front connectors for the marking of modules and front connectors, labels are supplied with the module and central controller; they are affixed as shown in figure 9-22. 1 1 2 3 45 figure 9-22 marking and labeling of modules 1 label with the module address under which the module is referenced by the step 5 program 2 labeling strip with the product designation for the module; space to mark the module version and label the channels 3 label with module address and marking of the required settings for the addressing switch 4 labeling strip for terminal designations or connection diagrams (strip in the cover of the front connector) 5 name plate analo g input/output modules
9-62 system manual c79000-g8576-c199-07 9.5.7 connecting the signal lines for connection of the signal lines, front connectors for 20 and 40 mm mounting width with crimp connection and 40 mm mounting width with screw connection are available (screwdriver blade width: 3.5 mm, maximum torque: 0.8 nm). use stranded conductor to facilitate handling of the front connector. ferrules are not required for screw connections, because the screw terminals are provided with wire protection. when the crimp contact is inserted in the plastic body of the front connector, a click can clearly be heard. this indicates that the contact is engaged. for jumpering or to correct the wiring, you can remove the contacts with a releasing tool (see ordering information) without having to pull out the front connector. ferrules are not required for screw connections, because the screw terminals are provided with wire protection. you can use ferrules of 7 mm in length to din 46228. the maximum terminal area is 2 x 2.5 mm 2 . terminal t connector t max. nf cross-section connector for rtdvlt mounting width of mdl type type 6es 497- no. of contacts signal or supply conductor aux. jumper in connector 1) rated voltage module crimp connection -4ua12 2) 42 0.5 mm 2 0.5 mm 2 5 to 60 v dc 20 mm operation with fan -4ua22 2) 42 0.5 mm 2 0.5 mm 2 5 to 60 v dc 40 mm oti screw ti -4ub12 42 0.5 to 2.5 mm 2 0.5 to 1.0 mm 2 5 to 60 v dc 40 mm operation without fan connection -4ub31 42 0.5 to 1.5 mm 2 0.5 to 1.0 mm 2 5 to 60 v dc 20 mm without fan 1) to multiply the supply and 0 v ground terminals, and to connect the enable input 2) the crimp contacts must be ordered separately for these types of connector. ! caution only extra-low voltage 60 v dc with safety separation from system voltage may be used for the 24 v dc supply and for the 24 v dc input signals. safety separation can be implemented to the requirements of, amongst other sources, vde 0100 part 410/hd 384-4-41/iec 60364-4-41 (as functional extra-low voltage with safety separation) or vde 0805/en 60950/iec 60950 (as safety extra-low voltage selv) or vde 0106 part 101. analo g input/output modules
9-63 system manual c79000-g8576-c199-07 9.5.8 connecting a compensating box for thermal e.m.f. measurement if the room temperature fluctuations at the reference point (for example, in the terminal box) affect the measurement result and you do not wish to use a thermostat, you can compensate for the effect of temperature on the reference point with a compensating box. between - 10 and + 70 o c, it compensates for the change in thermal e.m.f. caused by temperature deviation (compensating box, see catalog mp 19). ensure that the compensating box has thermal contact with the terminals. if the compensating box is aligned at 20 o c, this must be taken into account in temperature evaluation (20 o c measuring point temperature = 0 mv). pins 22 and 23 are extended on analog input modules as an input for the compensating voltage. you must select a common input loop for all inputs on mode switch 2. the compensating box must be connected in a floating circuit. the power supply unit of the compensating box must have a grounded shield winding to avoid ac system interference being picked up. a separate compensating box with its special power supply unit is required for each analog input module. 22- a d analog input module 465 mux m- 23+ 0 v bus m+ - + power supply for compensatin g box thermocouple terminal box ~ = # range card for 4 inputs 6es5 498- -1aa11 compensating box figure 9-23 connecting a compensating box analo g input/output modules
9-64 system manual c79000-g8576-c199-07 9.5.9 connecting resistance thermometers to the 465 analog input module the relevant resistance thermometer is fed with a current of 2.5 ma (i c+ /i c- ) by a constant current generator via a 6es5 498-1aa11 card. the voltage at the pt 100 is picked off at measurement inputs m+ and m-. if only inputs 0 to 3 are assigned to resistance thermometers, you can connect other current and voltage sensors to inputs 4 to 7 by means of a coding key. if you use the pt 100 for measurement, you cannot utilize channels 12 to 15. channels 8 to 11 supply the resistance thermometers which are connected at inputs 0 to 3. note that the mode of the module is set to the 500 mv voltage range. analo g input/output modules
9-65 system manual c79000-g8576-c199-07 465 analog input module + mux a d - card 1 u cm u cm pt100 0...500mv i c+ i c- ch0 ch3 ch4 card 2 u/i i const. ch7 6es5498- range card for 4 inputs 6es5-498- -1aa11 -1aa11 -1aa21 -1aa31 -1aa41 -1aa51 -1aa61 -1aa71 1) 1) card 3 2.5ma i const. +5v current source for pt 100 operation card 4 2) 2) 2) 2) 2) 2) 2) 2) 2) 2) 2) 2) 2) m+ m- m+ m- # range card for 4 inputs 6es5-498- -1aa11 range card for 4 inputs 6es5-498- -1aa11 -1aa41 -1aa71 figure 9-24 connecting a pt 100 1) when cards 6es5 498-1aa21, 6es5 498-1aa31 or 6es5 498-1aa61 are used, no broken wire signal may be activated for this group of channels (ch4 to ch7). 2) if cards 6es5 498-1aa41 or 6es5 498-1aa71 are used, a short-circuit jumper is not required. analo g input/output modules
9-66 system manual c79000-g8576-c199-07 9.5.10 broken wire signal for resistance thermometers an open-circuit in the lines to a resistance thermometer is indicated as follows: broken wire at module reaction, encoded value error bit e m+ m- pt 100 i c+ i c- 0 0 0 0 0 1 1 1 1 1 if the mode awithout broken wire signalo is selected on the module, an open-circuit of the resistance thermometer is indicated with an overflow. unassigned channels can be used for voltage or current measurement if the current flow outputs relating to the particular measuring channel are shorted with a wire jumper. without this jumper, the error bit would be set for this channel and the value 0 would be encoded. when set to aresistance thermometer,o switch 7 of mode switch i of the 465 analog input module allows broken wire monitoring of the i c+ lines to the resistance thermometer (pt 100 constant current supply). in the event of open-circuit of this line, the error bit is set as for the other lines. at the avoltage/currento (mv/ma) setting, the i c+ lines are not monitored for broken wire. (the error bit is not set for an open-circuit of this line.) you should choose this switch setting if you exclusively measure voltages or currents. broken wire monitoring analo g input/output modules
9-67 system manual c79000-g8576-c199-07 9.5.11 connecting transducers two-wire transducer (short-circuit protected supply voltage via the range card of the analog input module) a d analog input module mux m- 0 v bus m+ + - 4...20 ma l+ l- # range card for 4 inputs 6es5-498- -1aa51 four-wire transducer (with separate supply voltage) a d analog input module mux m- 0 v bus m+ + - +4...20 ma 230 v ac do not exceed max. permissible potential difference! # 6es5-498- -1aa71 range card for 4 inputs four-wire transducer with a two-wire transducer card a d analog input module mux m- 0 v bus m+ + - 0...20 ma 230 v ac l+ l- l- (0 v ext ) # 6es5-498- -1aa71 range card for 4 inputs analo g input/output modules
9-68 system manual c79000-g8576-c199-07 9.5.12 measured-value representation (rated input range  50 mv) units input vlt byte 0 byte 1 voltage in mv 7 2 12 6 2 11 5 2 10 4 2 9 3 2 8 2 2 7 1 2 6 0 2 5 7 2 4 6 2 3 5 2 2 4 2 1 3 2 0 2 a 1 e 0 ov  4096 100.0 0 1 1 1 1 1 1 1 1 1 1 1 1 0/1 0/1 1 overflow 4095 2049 99.976 50.024 0 0 1 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 0/1 0/1 0/1 0/1 0 0 overrange 2048 2047 50.0 49.976 0 0 1 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0/1 0/1 0/1 0/1 0 0 1024 1023 25.0 23.976 0 0 0 0 1 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0/1 0/1 0/1 0/1 0 0 1 0 -1 0.024 0.0 -0.024 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 1 0 1 0/1 0/1 0/1 0/1 0/1 0/1 0 0 0 rated range -1023 -1024 - 24.976 - 25.0 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0/1 0/1 0/1 0/1 0 0 -2047 -2048 - 49.976 - 50.0 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0/1 0/1 0/1 0/1 0 0 -2049 -4095 - 50.024 - 99.976 1 1 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 0/1 0/1 0/1 0/1 0 0 overrange -4096 -100.0 1 0 0 0 0 0 0 0 0 0 0 0 1 0/1 0/1 1 overflow a = active bit e = error bit ov = overflow bit digital measured-value representation as two's complement analo g input/output modules
9-69 system manual c79000-g8576-c199-07 (rated input range  50 mv) units input vlt byte 0 byte 1 voltage in mv 7 s 6 2 11 5 2 10 4 2 9 3 2 8 2 2 7 1 2 6 0 2 5 7 2 4 6 2 3 5 2 2 4 2 1 3 2 0 2 a 1 e 0 ov  4096 100.0 0 1 1 1 1 1 1 1 1 1 1 1 1 0/1 0/1 1 overflow 4095 2049 99.976 50.024 0 0 1 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 0/1 0/1 0/1 0/1 0 0 overrange 2048 2047 50.0 49.976 0 0 1 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0/1 0/1 0/1 0/1 0 0 1024 1023 25.0 23.976 0 0 0 0 1 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0/1 0/1 0/1 0/1 0 0 1 0 -0 -1 0.024 0.0 0.0 -0.024 0 0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0 0 0 0 rated range -1023 -1024 - 24.976 - 25.0 1 1 0 0 0 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 0/1 0/1 0/1 0/1 0 0 -2047 -2048 - 49.976 - 50.0 1 1 0 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 0/1 0/1 0/1 0/1 0 0 -2049 -4095 - 50.024 - 99.976 1 1 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 1 0/1 0/1 0/1 0/1 0 0 overrange -4096 -100.0 1 1 1 1 1 1 1 1 1 1 1 1 1 0/1 0/1 1 overflow a = active bit e = error bit ov = overflow bit bit 2 12 is interpreted as the sign. digital measured-value representation as value and sign analo g input/output modules
9-70 system manual c79000-g8576-c199-07 the resolution with pt 100 resistance thermometers is approximately 0.25 o c. 1 ohm  10 units units resistance in ohm 1) temp. in o c byte 0 byte 1 ohm 1) in o c 7 s 6 2 11 5 2 10 4 2 9 3 2 8 2 2 7 1 2 6 0 2 5 7 2 4 6 2 3 5 2 2 4 2 1 3 2 0 2 a 1 e 0 ov 4096 400.0 - 0 1 1 1 1 1 1 1 1 1 1 1 1 0/1 0/1 1 overflow 4095 2049 399.90 200.98 - 269.1 0 0 1 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 0/1 0/1 0/1 0/1 0 0 overrange 2048 2047 200.0 199.90 266.5 266.0 0 0 1 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0/1 0/1 0/1 0/1 0 0 1024 1023 100.00 99.90 0 -0.2 0 0 0 0 1 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0/1 0/1 0/1 0/1 0 0 rated range 1 0 0.098 0.0 - - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0/1 0/1 0/1 0/1 0 0 1) resistance value pt 100 a = active bit e = error bit ov = overflow bit s = sign when pt 100 resistance thermometers are connected, the maximum temperature in the rated range is 266 o c. if it can be ensured that the temperature does not exceed 850 o c, the input value may extend into the overrange. the resolution is then 4095 units. unused inputs can be utilized for voltage measurements in the 500 mv range (see front connector assignments). measured-value representation for pt 100 resistance thermometers analo g input/output modules
9-71 system manual c79000-g8576-c199-07 measuring range 500 mv; card with 31.25 ohm shunt (6es5 498-1aa51/aa71) the 4 to 20 ma range is resolved to 2048 units at an interval of 512 to 2560. if you require a representation from 0 to 2048, you must subtract 512 units by software. please note the following:  a broken wire signal cannot be emitted.  detection of the overrange can be achieved by scanning bits 2 9 and 2 11 .  a broken wire can be detected with currents < 3 ma.  if you short-circuit the positive and negative terminals of the transducer when using the 6es5 498-1aa51 range card (for a two-wire transducer), the current is limited to about 28 ma. until the thermal current limiting circuit responds in the range card (about 3 s), a short-circuit current of approximately 250 ma flows. units input ct byte 0 byte 1 current in ma 7 s 6 2 11 5 2 10 4 2 9 3 2 8 2 2 7 1 2 6 0 2 5 7 2 4 6 2 3 5 2 2 4 2 1 3 2 0 2 a 1 e 0 ov  4096  32.000 0 1 1 1 1 1 1 1 1 1 1 1 1 0/1 0 1 overflow 4095 3072 3071 2561 31.992 24.0 23.992 20.008 0 0 0 0 1 1 1 1 1 1 0 0 1 0 1 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 0/1 0/1 0/1 0/1 0 0 0 0 0 0 0 0 overrange short-circuit with two- wire transducer 2560 2048 512 20.0 16.0 4.0 0 0 0 1 1 0 0 0 0 1 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0/1 0/1 0/1 0 0 0 0 0 0 rated range 511 384 383 3.992 3.0 2.992 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 0 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 0/1 0/1 0/1 0 0 0 0 0 0 range underflow 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0/1 0 0 broken wire a = active bit e = error bit ov = overflow bit s = sign measured-value representation for current measuring ranges from 4 to 20 ma current limiting analo g input/output modules
9-72 system manual c79000-g8576-c199-07 9.5.13 technical specifications 6es5 465-4ua12 analog input module rated input ranges with cards for every 4 channels - 6es5 498-1aa11 - 6es5 498-1aa21 - 6es5 498-1aa31 - 6es5 498-1aa41 - 6es5 498-1aa51 - 6es5 498-1aa61 - 6es5 498-1aa71  50 mv/  500 mv/pt 100  1 v  10 v  20 ma 4 to 20 ma for two-wire transducer  5 v 4 to 20 ma for four-wire transducer number of inputs 16 voltage/current inputs or 8 resistance inputs (pt 100) measured-value representation 13 bits (two's complement) or 12 bits + sign;  2048 units in rated range; 512 to 2560 units for 4 to 20 ma measuring principle integrating isolation no permissible potential difference between reference potentials of sensors and the module (u cm ) and between sensors (channels)  1 v max. power supply - digital section from system bus - analog section from load voltage - enabling for module f+/f- - tripping current l+ 5 v  5 %; 150 ma typical 24 v 24 v; approx. 5 ma 24 v; approx. 5 ma constant current source for pt 100 connection i c+ /i c- 2.5 ma; tc =  5 x 10 -5 /k integration time 20 ms at 50 hz; 16 2 / 3 ms at 60 hz encoding time per measured value 60 ms at 50 hz; 50 ms at 60 hz cycle time for 8 measured values with 2048 units (max. delay time for measured-value acquisition) approx. 0.48 s at 50 hz approx. 0.48 s at 50 hz input resistance (with card) for input ranges:  50 mv/  500 mv/pt 100  1 v  5 v/  10 v  20 ma 4 to 20 ma  10 m  90 k  50 k  25  31.25  analo g input/output modules
9-73 system manual c79000-g8576-c199-07 measuring point-related error signal - for overflow - for broken wire ye s yes, configurable (at  50 mv,  500 mv and pt 100) max. permissible input voltage without destruction  18 v; 75 v for 1 ms max. and duty ratio 1:20 interference suppression for f = n x (50/60 hz  1 %) - with common-mode interference - with differential-mode interference  86 db, but  1 v max.  40 db, noise voltage amplitude but 100 % max. of measuring range referred to peak value error referred to rated value - linearity - tolerance - polarity reversal error - temperature error  1 unit  1 unit  1 unit 1 x 10 -4 /k error caused by cards with input range  1 v/  5 v /  10 v  20 ma/4 to 20 ma 2 x 10 -3 ; tc =  10 x 10 -5 /k 10 -3 ; tc =  5 x 10 -5 /k you select the desired mode of the analog input module by setting mode switches i and ii according to the following table. note that all the rockers of both mode switches marked with a dot must be set, and some functions are defined by several rockers (for example, 8- to 16-channel operation, broken wire signal for 8 or 16 channels). to activate the desired modes, press the rockers down on the side marked with a dot. setting the mode analo g input/output modules
9-74 system manual c79000-g8576-c199-07 mode mode switch i (digital section) mode switch ii (digital section) without reference point compensation with reference point compensation measuring range 50 mv 500 mv; pt 100 current or voltage measurement, 16 channels current or voltage measurement, 8 channels pt 100 in 4-wire circuit 8 channels sampling selective cyclic line frequency 50 hz 60 hz 8 channels 16 channels two's complement value and sign broken-wire signal for:channels 0 ... 7 2) channels 0 ... 7 2) channels 8 ... 15 2) channels 0 ... 3 1) channels 4 ... 7 1) no broken-wire signal for: channels 0 ... 7 2) channels 8 ... 15 2) hannels 0 ... 3 1) channels 4 ... 7 1 ) mv/ma pt 100 x = switch is not assigned, any switch setting 1) for 8-channel mode = switch setting 2) for 16-mode mode analo g input/output modules
9-75 system manual c79000-g8576-c199-07 labeling of switches on the module cover: ii. 1) resistance thermometer 16 channels ...mv/ ...ma 50 mv without compensation voltage/current 8 channels ...mv/ ...ma/ resist. therm. 500 mv/ ...ma/ resistance thermometer with compensation channel 4-7 i. 1) * * 8 channels 16 channels channel 8-15 8channels 16channels channel0-3 channel0-7 with broken wire detection two's complement 8 channels/resistance thermom.; mv/ma line frequency 50 cps single scanning channel 4-7 8 channels 16 channels channel 8-15 8 channels 16 channels channel 0-3 channel 0-7 with out broken wire detection result and sign 16 channels mv; ma line frequency 60 cps cyclics canning resistance thermometer consider instruction manual voltage/current 1) it is advisable to mark the selected switch setting in these fields. on one 465 analog input module, you can insert four cards for the connection of four inputs each, and secure them with a screw. there are voltage divider, shunt and through-connection cards for the various ranges. circuit of the cards 4x mode 50 mv mode 500 mv/ ma pt 100 -1aa11 -1aa21 -1aa31 -1aa41 -1aa51 -1aa61 -1aa71 m+ m- m+ m- m+ m- m+ m- m+ m- m+ m- m- l+ l- range card type 6es5 498- m+  500 mv pt 100  1 v  10 v - (  100 mv)  50 mv  5 v 4...20ma 2-wire trans.  20 ma 4...20ma 4-wire trans. (  1 v) (  2 ma) (  500 mv) - for a defined mode (50 mv or 500 mv), you can insert cards with different ranges for every four inputs, for example, for the 500 mv mode:  4 inputs, range  500 mv; 1 card 6es5 498-1aa11  8 inputs, range  20 mv; 2 cards 6es5 498-1aa41 unused inputs must be short-circuited (with pt 100 operation, this also applies to the unused current outputs). note that the bus interface of the module is activated with 24 v via enable lines f+ and f- at the front connector. inserting range cards analo g input/output modules
9-76 system manual c79000-g8576-c199-07 voltage or current input or connection of two-wire transducer resistance thermometer block diagram of the module front strip pin connection of process signal lines 1 2 3 4 6 8 10 13 15 17 19 20 22 23 25 27 29 31 34 36 38 40 41 f+ l+ f- comp.- comp.+ mu + - 2) datenspeicher und s5-busansteuerung adu t range card 1 5 range card 2 range card 3 range card 4 6es5 498-1aa51 7 9 11 14 16 18 26 28 30 32 35 37 39 ch.15 mu + - 2) mu + - 2) mu + - 2) l- l+ + - 1) + - 1) + - 1) + - 1) + - + - + - + - ch.0 + - 1) 1) 1) 1) 1) 1) + - 1) - + 1) - + i trip 24 3)l+ 1 2 3 4 6 8 10 13 15 17 19 20 22 23 25 27 29 31 34 36 38 40 41 42 42 f+ l+ l- l- f- comp.- comp.+ data memory and s5 bus control adu t 5 7 9 11 14 16 18 26 28 30 32 35 37 39 ch.7 ch.0 ch.6 ch.5 ch.4 ch.3 ch.2 ch.1 ch.0 ch.1 ch.2 ch.3 ch.4 ch.5 ch.6 ch.7 measuring voltage inputs constant power supply i 24 3) l+ 0 vgnd (l-) connection of process signal lines front strip pin block diagram of the module range card 1 range card 2 range card 3 range card 4 trip 0 vgnd (l-) figure 9-25 front connector assignments two-wire transducers can only be connected in the 500 mv mode. connect l- to the central ground point (reference potential). 1) observe permissible potential difference between sensor and reference potential of modules or between sensors. 2) two-wire transducer 3) only required to switch off the tripping current without broken wire detection; (0 v at common ground point with l-). front connector assignments analo g input/output modules
9-77 system manual c79000-g8576-c199-07 9.6 the 466 analog input module 9.6.1 design the module is designed as a plug-in pcb for central controllers and expansion units with a backplane connector and with a blade connector to accept a plug-in front connector. you can directly connect the process signal lines to the front connector, which is available separately, with screw or crimp terminals. 9.6.2 special features of the 466 analog input module the 466 analog input module processes the digital input signals by encoding the instantaneous value; periodic system interference is therefore not suppressed. you select the measuring ranges with a switch setting for every four channels. 9.6.3 startup for analog input 466-3la11 the mode of the 466 analog input module must be set exclusively via switches on the board. figure 9-26 shows the designations and locations of switches on the board. front backplane connector for s5 i/o bus s9 s6 s5 s7 s8 s2 s1 figure 9-26 locations of mode switches on the 466 analog input module note the following 43-pin k-type front connectors are required:  6xx3 068 for crimp connection  6xx3 081 for srew connection ensure that all the switches are operated properly (meaning pressed past the latching point). measuring range introduction analo g input/output modules
9-78 system manual c79000-g8576-c199-07 measurement with respect to ground/differential measurement the type of measurement (with respect to ground or differential measurement) is set with switch s9. the switch settings relate to the locations on the module shown in figure 9-26: type of measurement switch setting s9 measurement with respect to ground on off 19 differential measurement 1 9 on off if you have preset differential measurement on switch s9, two channel groups of four channels each are available. you can configure each channel group separately for current or voltage measurement. you set this with switches s5, s6, s7 and s8. switches s5 and s7 allow three settings (left, midpoint and right); switches s6 and s8 allow two settings (left and right). the switch settings relate to the locations on the module shown in figure 9-26: setting the current/voltage measurement for channel group i channel group i (channels 0 to 3) switch s5 switch s6 current voltage setting the current/voltage measurement for channel group ii channel group ii (channels 4 to 7) switch s7 switch s8 current voltage setting the type of measurement current/voltage measurement for individual channel groups analo g input/output modules
9-79 system manual c79000-g8576-c199-07 if you have preset measurement with respect to ground on switch s9, four channel groups of four channels each are available. you can configure each channel group separately for current or voltage measurement. this is set with switches s5, s6, s7 and s8. switches s5 and s7 allow three settings (left, midpoint and right); switches s6 and s8 allow two settings (left and right). the switch settings relate to the locations on the module shown in figure 9-26: setting the current/voltage measurement for channel group i channel group i (channels 0 to 3) switch s5 current voltage setting the current/voltage measurement for channel group ii channel group ii (channels 4 to 7) switch s7 current voltage setting the current/voltage measurement for channel group iii channel group iii (channels 8 to 11) switch s6 current voltage setting the current/voltage measurement for channel group iv channel group iv (channels 12 to 15) switch s8 current voltage analo g input/output modules
9-80 system manual c79000-g8576-c199-07 the 466 analog input module has 12 measuring ranges. for each channel group (i.e. for every four inputs), you can select a range which is independent of the other channel groups. you set the ranges with switches s1 and s2. channel group i (channel 0...3) channel group ii (channel 4...7) channel group iii (channel 8...11) channel group iv (channel 12...15) on off 1 234 5678 s1 1 234 5678 s2 figure 9-27 assignment of channel groups to switches s1 / s2 the same measuring range coding is valid for each channel group. given in the following table, therefore, is the setting of the measuring range for only one channel group. the switch settings relate to the locations on the module shown in figure 9-27. note that you must additionally set the type of measurement (current/voltage) with switches s5 to s8! setting the measuring range for a channel group (4 channels each) range switch setting 0 - 20 ma on off 0 - 1.25 v 0 - 2.5 v 0 - 5 v 0 - 10 v  20 ma  1.25 v  2.5 v  5 v  10 v 4 - 20 ma 1 - 5 v setting the measuring range analo g input/output modules
9-81 system manual c79000-g8576-c199-07 set the data format by means of switch s9:  two's complement 12-bit two's complement representation (range: 0 ... 4095 units (unipolar) or - 2048 ... + 2047 units (bipolar))  value and sign 11-bit value and 1 sign bit (range: 0 ... 4095 units (unipolar) or - 2048 ... + 2047 units (bipolar))  binary 12-bit binary number (range: 0 ... 4095 units for both unipolar and bipolar measured variables) data format s9 switch setting two's complement 1 9 on off value and sign 1 9 on off binary 1 9 on off setting the data format analo g input/output modules
9-82 system manual c79000-g8576-c199-07 before starting up, first indicate via switch s9 whether you intend to use the 466 analog input module with a central controller (cc) or with an expansion unit (eu). refer to the following table: setting the module start address (1) 466-3la11 module s9 switch setting operation in cc 1 on off 9 operation in eu with im 300/312 1 on off 9 operation in eu with im 301/310 1 on off 9 operation in eu with im 304/314 1 on off 9 operation in eu with im 307/317 1 on off 9 operation in eu with im 308/318 1 on off 9 setting the module start address analo g input/output modules
9-83 system manual c79000-g8576-c199-07 set the exact start address of the module as shown in the following table. setting the module start address (2) module address s9 switch setting 000 1 9 on off 016* 1 9 on off 032 1 9 on off 048* 1 9 on off 064 1 9 on off 080* 1 9 on off 096 1 9 on off 112* 1 9 on off 128 1 9 on off 144* 1 9 on off 160 1 9 on off 176* 1 9 on off 192 1 9 on off 208* 1 9 on off 224 1 9 on off 240* 1 9 on off * can only be set for differential measurement analo g input/output modules
9-84 system manual c79000-g8576-c199-07 9.6.4 startup for analog input 466-4ua11 the mode of the 466 analog input module must be set exclusively via switches on the board. the following figure shows the designation and the position of the switches on the board switches s9 and s3 have been changed or are new. front backplane connector for s5 i/o bus s9 s6 s5 s7 s8 s2 s1 s3 figure 9-28position of the mode switch note an adaption capsule is required in order to use the analog input module 466 in the plc (for example, 6es5 491-olb12). the following 42-pin k-type front connectors are required:  6es5 497-4ua12 for crimp connection  6es5 497-4ub31 for srew connection ensure that all the switches are operated properly (meaning pressed past the latching point). introduction analo g input/output modules
9-85 system manual c79000-g8576-c199-07 measurement with respect to ground/differential measurement the type of measurement (with respect to ground or differential measurement) is set with switch s9. the switch settings relate to the locations on the module shown in figure 9-28: type of measurement switch position s9 measurement with regard to ground on off 1 8 differential measurement 1 8 on off if you have preset differential measurement on switch s9 , two channel groups of four channels each are available. you can configure each channel group separately for current or voltage measurement. you set this with switches s5 , s6 , s7 and s8 . switches s5 and s7 allow three settings (left, midpoint and right); switches s6 and s8 allow two settings (left and right). the switch settings relate to the locations on the module shown in figure 9-26: setting the current/voltage measurement for channel group i channel group i (channel 0...3) switch s5 switch s6 current voltage setting the current/voltage measurement for channel group ii channel group ii (channel 4...7) switch s7 switch s8 current voltage setting the type of measurement current/voltage measurement for individual channel groups analo g input/output modules
9-86 system manual c79000-g8576-c199-07 if you have preset measurement with respect to ground on switch s9 , four channel groups of four channels each are available. you can configure each channel group separately for current or voltage measurement. this is set with switches s5 , s6 , s7 and s8 . switches s5 and s7 allow three settings (left, midpoint and right); switches s6 and s8 allow two settings (left and right). the switch settings relate to the locations on the module shown in figure 9-28: setting the current/voltage measurement for channel group i channel group i (channel 0...3) switch s5 current voltage setting the current/voltage measurement for channel group ii channel group ii (channel 4...7) switch s7 current voltage setting the current/voltage measurement for channel group iii channel group iii (channel 8...11) switch s6 current voltage setting the current/voltage measurement for channel group iv channel group iv (channel 12...15) switch s8 current voltage analo g input/output modules
9-87 system manual c79000-g8576-c199-07 the 466 analog input module has 12 measuring ranges. for each channel group (i.e. for every four inputs), you can select a range which is independent of the other channel groups. you set the ranges with switches s1 and s2. the assignment of the switches to the channel group is shown in figure 9-28. channel group i (channel 0...3) channel group ii (channel 4...7) channel group iii (channel 8...11) channel group iv (channel 12...15) on off 1 234 5678 s1 1 234 5678 s2 figure 9-29assignment of the switches s1 / s2 and the channel group the same measuring range coding is valid for each channel group. given in the following table, therefore, is the setting of the measuring range for only one channel group. the switch settings relate to the locations on the module shown in the figure. note that you must additionally set the type of measurement (current/voltage) with switches s5 to s8! setting the measuring range for a channel group (4 channels each) setting the measu- ring range analo g input/output modules
9-88 system manual c79000-g8576-c199-07 measuring range switch position 0 - 20 ma on off 0 - 1,25 v 0 - 2,5 v 0 - 5 v 0 - 10 v  20 ma  1,25 v  2,5 v  5 v  10 v 4 - 20 ma 1 - 5 v the data format is set by using switch s9:  two's complement 12-bit two's complement representation (range: 0 ... 4095 units (unipolar) or - 2048 ... + 2047 units (bipolar))  value and sign 11-bit value and 1 sign bit (range: 0 ... 4095 units (unipolar) or - 2048 ... + 2047 units (bipolar))  binary 12-bit binary number (range: 0 ... 4095 units for both unipolar and bipolar measured variables) setting the data format analo g input/output modules
9-89 system manual c79000-g8576-c199-07 data format switch position s9 two's complement 1 8 on off value and sign 1 8 on off binary on off 1 8 table setting the type of coupling module 466-ua11 switch position s9 during operation in the cc or in the eu via decentralized couplings 1 on off 8 p area pg with im 304/314, 307/317, 308/318-3, 300/312 1 on off 8 o area 1 on off 8 im 3 area 1 on off 8 im 4 area during operation in the decentralized eu 701-2/3 with as 301/310 eu 185 with as 301/310 1 on off 8 setting the initial module address analo g input/output modules
9-90 system manual c79000-g8576-c199-07 setting the initial module address for s5-135/155 module address switch setting s9 000 (f000 h ) on off 4 3 2 1 016* (f010 h ) 1 on off 234 032 (f020 h ) 1 4 on off 23 048* (f030 h ) 14 on off 23 064 (f040 h ) 1 4 on off 23 080* (f050 h ) 1 4 on off 23 096 (f060 h ) 14 on off 3 2 112* (f070 h ) 1 on off 234 128 (f080 h ) 4 on off 123 144* (f090 h ) 14 on off 23 160 (f0a0 h ) 14 on off 2 3 176* (f0b0 h ) 14 on off 2 3 192 (f0c0 h ) 14 on off 3 2 208* (f0d0 h ) 14 on off 3 2 224 (f0e0 h ) 1 4 on off 3 2 240* (f0f0 h ) 14 on off 3 2 * can only be set for differential measurement analo g input/output modules
9-91 system manual c79000-g8576-c199-07 9.6.5 removing and inserting modules ! warning when removing and inserting the front connector during operation, hazardous voltages of more than 25 v ac or 60 v dc may be present at the module pins. when this is the case at the front connector, live modules may only be replaced by electrical specialists or trained personnel in such a way that the module pins are not touched. during operation, the front connector and module must not be removed or inserted without the enable jumper or active enable circuit. install an analog input/output module as follows: step action 1 release the upper locking bar on the subrack and swivel it upwards and out. 2 insert the module at the desired slot in the subrack and push it back in the guides. 3 latch the module by rotating the locking pin by 90 o at the lower end of the module. it must no longer be possible to pull the module forwards. 4 engage the front connector on the support pin of the module. the width of the support pin also provides keying to prevent front connectors from being fitted to the wrong modules (e.g. front connectors with 115/230 v ac wiring cannot be plugged into analog modules). 5 tighten the screw in the upper part of the front connector. analo g input/output modules
9-92 system manual c79000-g8576-c199-07 remove an analog input/output module as follows: step action 1 release the upper locking bar on the subrack and swivel it upwards and out. 2 slacken the screw in the upper part of the front connector. this causes the front connector to be pressed out of the female connector of the module. contacts f+ and f- of the enable input at the upper end of the front connector are thus opened first. if the enable input is active, power is removed from the outputs and the module is isolated from the s5 bus. 3 swing the front connector out and lift it away from the support pin of the module. 4 release the module by rotating the locking pin by 90 o at the lower end of the module. you can pull the module out of the subrack with a grip with swivels outwards. 1 2 3 5 6 4 module front connector support mount support pin figure 9-30 module with front connector 1 screw 2 locking pin 3 support mount 4 support pin 5 grip 6 backplane connector comply with vde specifications 0110 and 0160 to carry out the wiring of supply and signal lines which are to be connected to the programmable controllers and front connectors of the modules. detailed information on cabinet assembly, cabinet ventilation and protective measures can be found in chapter 3. analo g input/output modules
9-93 system manual c79000-g8576-c199-07 9.6.6 marking of modules and front connectors for the marking of modules and front connectors, labels are supplied with the module and central controller; they are affixed as shown in figure 9-31. 5 1 13 4 2 figure 9-31 marking and labeling of modules 1 label with the module address under which the module is referenced by the step 5 program 2 labeling strip with the product designation for the module; space to mark the module version and label the channels 3 label with module address and marking of the required settings for the addressing switch 4 labeling strip for terminal designations or connection diagrams (strip in the cover of the front connector) 5 name plate analo g input/output modules
9-94 system manual c79000-g8576-c199-07 9.6.7 connecting the signal lines for connection of the signal lines, front connectors for 20 and 40 mm mounting width with crimp connection and 40 mm mounting width with screw connection are available (screwdriver blade width: 3.5 mm, maximum torque: 0.8 nm). use stranded conductor to facilitate handling of the front connector. ferrules are not required for screw connections, because the screw terminals are provided with wire protection. when the crimp contact is inserted in the plastic body of the front connector, a click can clearly be heard. this indicates that the contact is engaged. for jumpering or to correct the wiring, you can remove the contacts with a releasing tool (see ordering information) without having to pull out the front connector. ferrules are not required for screw connections, because the screw terminals are provided with wire protection. you can use ferrules of 7 mm in length to din 46228. the maximum terminal area is 2 x 2.5 mm 2 . ! caution only extra-low voltage 60 v dc with safety separation from system voltage may be used for the 24 v dc supply and for the 24 v dc input signals. safety separation can be implemented to the requirements of, amongst other sources, vde 0100 part 410/hd 384-4-41/iec 60364-4-41 (as functional extra-low voltage with safety separation) or vde 0805/en 60950/iec 60950 (as safety extra-low voltage selv) or vde 0106 part 101. analo g input/output modules
9-95 system manual c79000-g8576-c199-07 9.6.8 connecting sensors to the 466 analog input module the connections for the 466 analog input module depend on the type of measurement (with respect to ground or differential measurement). for measurement with respect to ground, all signal lines have a common reference point. this is achieved by connecting all the m inputs in use to one point. since this type of measurement is susceptible to interference, the signal sources should be arranged in the vicinity of the 466 analog input module. 16 channels are available; unused channels must be shorted (jumper between m+ and m-). the channels have the following designations on the module: channel 0: m0 + m0 - channel 1: m1 + m1 - : : channel 15 m15 + m15 - channels are arranged in groups of four, for which you can set separate measuring ranges: channel group i: channels 0 to 3 channel group ii: channels 4 to 7 channel group iii: channels 8 to 11 channel group iv: channels 12 to 15 measurement with respect to ground analo g input/output modules
9-96 system manual c79000-g8576-c199-07 the following figure shows the connection of sensors to the module. for measurement with respect to ground, all the m- connection points are interconnected internally on the module. u e2 u e1 analog input module m+ m- + - + - m+ u iso mux 0 v bus u e1/2: input v oltage u iso: potential difference : equipotential; this potential is established by the sensor reference potential (external reference potential) figure 9-32 connecting sensors to the 466 analog input module (measurement with respect to ground) the differential measurement is a method of compensating for interference on the line. each signal source is assigned its own signal reference line. the differential measurement between signal line and signal reference line thus compensates for the interference acting on both lines. you must also short-circuit the unused channels with this measuring method (jumper between m+ and m-). differential measurement is required:  if the sensors are at different potentials;  if various signal sources are not close to each other;  if there is a need to measure signals with high precision;  and when a high level of interference is expected. differential measurement analo g input/output modules
9-97 system manual c79000-g8576-c199-07 the channels have the following designations on the module: channel 0: m0 + m0 - channel 1: m1 + m1 - : : channel 7: m7 + m7 - channels are arranged in groups of four, for which you can set separate measuring ranges: channel group i: channels 0 to 3 channel group ii: channels 4 to 7 the following figure shows the connection of sensors to the module. you must observe the following condition: u e + u cm < 12 v (i.e. the sum of the set voltage range and common-mode voltage must be less than 12 v; current measuring ranges correspond to a voltage of 2.5 v). m+ m- m+ u iso mux 0 v bus + - + - u e2 u cm2 + - + - u cm1 m- 0 v ext u e1 analog input module u e1/2: input v oltage u iso: potential difference : equipotential; this potential is established by the sensor reference potential (external reference potential) u cm1/2: common-mode v oltage figure 9-33 connecting sensors to the 466 analog input module (differential measurement) analo g input/output modules
9-98 system manual c79000-g8576-c199-07 9.6.9 measured-value representation after conversion, the digital result is stored in the module's ram. the bits in both bytes have the following significance: byte 0 7 65 4 3 21 0 7 65 4 3 21 0 2 12 222 2 222 22 222 11 10 9 5 7 3 1 8 4 6 2 0 aeov byte 1 binary value is not assigned is set in case of internal error; in this case, the measured value is not valid (is set if the range limit is reached) active bit; error bit; overflow bit; figure 9-34 digital result representation bits 0 to 2 in byte 1 have no influence on the measured value, they only give information on measured-value representation. the following table describes their significance in more detail. bit significance signal status meaning of the signal status ov overflow bit 1 range exceeded * e error bit 1 broken wire a active bit 0 not used * a measuring-point overflow does not affect the overflow bits of the other channels; i.e. the measured values of unaffected channels are correct and can be evaluated. please note the following special features:  bit 7 in the high byte (2 12 ) indicates the sign for bipolar measured-value representation (two's complement and value with sign).  bit 6 in the high byte (2 11 ) is not used in the case of bipolar measured-value representation (no overrange).  the 466 module has no overrange.  selective sampling is not possible with the 466 module (active bit is not set). measured-value representation with various ranges analo g input/output modules
9-99 system manual c79000-g8576-c199-07 shown in the following tables is the representation of the measured value as a function of the selected measuring range. units measured value in v measured value in v measured value in v byte 0 * byte 1 * value in v (0 - 5 v) value in v (0 - 10 v) value in v (0 - 20 ma) 7 2 12 6 2 11 5 2 10 4 2 9 3 2 8 2 2 7 1 2 6 0 2 5 7 2 4 6 2 3 5 2 2 4 2 1 3 2 0 2 a 1 e 0 o 4095 4094 : 0001 0000 4.9988 4.9976 : 0.0012 0.0000 9.9976 9.9951 : 0.0024 0.0000 19.9951 19.9902 : 0.00488 0.00000 0 0 0 0 1 1 0 0 1 1 0 0 1 1 : 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 0 : 1 0 0 0 0 0 0 0 0 0 1 0 0 1 * same representation for the data formats: two's complement, value and sign, binary representation. a = active bit e = error bit o = overflow bit units measured value in v measured value in v measured value in v byte 0 * byte 1 * value in v (  5 v) value in v (  10 v) value in v (  20 ma) 7 2 12 6 2 11 5 2 10 4 2 9 3 2 8 2 2 7 1 2 6 0 2 5 7 2 4 6 2 3 5 2 2 4 2 1 3 2 0 2 a 1 e 0 o 2047 2046 : 0001 0000 -0001 : -2047 -2048 4.9976 4.9951 : 0.0024 0.0000 -0.0024 : -4.9976 -5.0000 9.9951 9.9902 : 0.0049 0.0000 -0.0049 : -9.9951 -10.000 19.9902 19.9804 : 0.00976 0.00000 -0.00976 : -19.9902 -20.0000 0 0 0 0 1 1 1 0 0 0 0 1 1 1 1 1 0 0 1 0 0 1 1 : 0 0 1 : 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 0 : 1 0 1 : 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 1 a = active bit e = error bit o = overflow bit measuring range 0-20 ma, 0-5 v and 0-10 v; unipolar two's complement; measuring range  5 v,  20 ma and  10 v; bipolar analo g input/output modules
9-100 system manual c79000-g8576-c199-07 value and sign; measuring range  5 v,  20 ma and  10 v; bipolar units measured value in v measured value in v measured value in v byte 0 * byte 1 * value in v (  5 v) value in v (  10 v) value in v (  20 ma) 7 2 12 6 2 11 5 2 10 4 2 9 3 2 8 2 2 7 1 2 6 0 2 5 7 2 4 6 2 3 5 2 2 4 2 1 3 2 0 2 a 1 e 0 o 2047 2046 : 0001 0000 -0001 : -2047 -2048 4.9976 4.9951 : 0.0024 0.0000 -0.0024 : -4.9976 -5.0000 9.9951 9.9902 : 0.0049 0.0000 -0.0049 : -9.9951 -10.000 19.9902 19.9804 : 0.00976 0.00000 -0.00976 : -19.9902 -20.0000 0 0 0 0 1 1 1 0 0 0 0 0 0 1 1 1 0 0 0 1 0 1 1 : 0 0 0 : 1 0 1 1 0 0 0 1 0 1 1 0 0 0 1 0 1 1 0 0 0 1 0 1 1 0 0 0 1 0 1 1 0 0 0 1 0 1 1 0 0 0 1 0 1 1 0 0 0 1 0 1 1 0 0 0 1 0 1 0 : 1 0 1 : 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 1 a = active bit e = error bit o = overflow bit binary; measuring range  5 v,  20 ma and  10 v; bipolar units measured value in v measured value in v measured value in v byte 0 * byte 1 * value in v (  5 v) value in v (  10 v) value in v (  20 ma) 7 2 12 6 2 11 5 2 10 4 2 9 3 2 8 2 2 7 1 2 6 0 2 5 7 2 4 6 2 3 5 2 2 4 2 1 3 2 0 2 a 1 e 0 o 4095 4094 : 2049 2048 2047 : 0001 0000 4.9976 4.9951 : 0.0024 0.0000 -0.0024 : -4.9976 -5.0000 9.9951 9.9902 : 0.0049 0.0000 -0.0049 : -9.9951 -10.000 19.9902 19.9804 : 0.00976 0.00000 -0.00976 : -19.9902 -20.0000 0 0 0 0 0 0 0 1 1 1 1 0 0 0 1 1 0 0 1 0 0 1 1 : 0 0 1 : 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 0 : 1 0 1 : 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 1 a = active bit e = error bit o = overflow bit measuring range 0-1.25 v and 0-2.5 v; unipolar units measured value in v measured value in v byte 0 byte 1 value in v (0 - 1.25 v) value in v (0 - 2.5 v) 7 2 12 6 2 11 5 2 10 4 2 9 3 2 8 2 2 7 1 2 6 0 2 5 7 2 4 6 2 3 5 2 2 4 2 1 3 2 0 2 a 1 e 0 o 4095 4094 : 0001 0000 1.2497 1.2494 : 0.0003 0.0000 2.4994 2.4988 : 0.0006 0.0000 0 0 0 0 1 1 0 0 1 1 0 0 1 1 : 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 0 : 1 0 0 0 0 0 0 0 0 0 1 0 0 1 * same representation for the data formats: two's complement, value and sign, binary representation. a = active bit e = error bit o = overflow bit analo g input/output modules
9-101 system manual c79000-g8576-c199-07 two's complement; measuring range  1.25 v and  2.5 v; bipolar units measured value in v measured value in v byte 0 byte 1 value in v (  1.25 v) value in v (  2.5 v) 7 2 12 6 2 11 5 2 10 4 2 9 3 2 8 2 2 7 1 2 6 0 2 5 7 2 4 6 2 3 5 2 2 4 2 1 3 2 0 2 a 1 e 0 o 2047 2046 : 0001 0000 -0001 : -2047 -2048 1.2494 1.2488 : 0.0006 0.0000 -0.0006 : -1.2494 -1.2500 2.4988 2.4975 : 0.0012 0.0000 -0.0012 : -2.4988 -2.5000 0 0 0 0 1 1 1 0 0 0 0 1 1 1 1 1 0 0 1 0 0 1 1 : 0 0 1 : 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 0 : 1 0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 : 0 0 1 0 0 0 0 0 1 a = active bit e = error bit o = overflow bit value and sign; measuring range  1.25 v and  2.5 v; bipolar units measured value in v measured value in v byte 0 byte 1 value in v (  1.25 v) value in v (  2.5 v) 7 2 12 6 2 11 5 2 10 4 2 9 3 2 8 2 2 7 1 2 6 0 2 5 7 2 4 6 2 3 5 2 2 4 2 1 3 2 0 2 a 1 e 0 o 2047 2046 : 0001 0000 -0001 : -2047 -2048 1.2494 1.2488 : 0.0006 0.0000 -0.0006 : -1.2494 -1.2500 2.4988 2.4975 : 0.0012 0.0000 -0.0012 : -2.4988 -2.5000 0 0 0 0 1 1 1 0 0 0 0 0 0 1 1 1 0 0 0 1 0 1 1 : 0 0 0 : 1 0 1 1 0 0 0 1 0 1 1 0 0 0 1 0 1 1 0 0 0 1 0 1 1 0 0 0 1 0 1 1 0 0 0 1 0 1 1 0 0 0 1 0 1 1 0 0 0 1 0 1 1 0 0 0 1 0 1 0 : 1 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 : 0 0 1 0 0 0 0 0 1 a = active bit e = error bit o = overflow bit binary; measuring range  1.25 v and  2.5 v; bipolar units measured measured byte 0 byte 1 value in v (  1.25 v) value in v (  2.5 v) 7 2 12 6 2 11 5 2 10 4 2 9 3 2 8 2 2 7 1 2 6 0 2 5 7 2 4 6 2 3 5 2 2 4 2 1 3 2 0 2 a 1 e 0 ov 4095 4094 : 2049 2048 2047 : 0001 0000 1.2494 1.2488 : 0.0006 0.0000 -0.0006 : -1.2494 -1.2500 2.4988 2.4975 : 0.0012 0.0000 -0.0012 : -2.4988 -2.5000 0 0 0 0 0 0 0 1 1 1 1 0 0 0 1 1 0 0 1 0 0 1 1 : 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 1 0 0 1 0 0 1 0 : 1 0 1 : 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 1 * same representation for the data formats: two's complement, value and sign, binary representation. a = active bit e = error bit o = overflow bit analo g input/output modules
9-102 system manual c79000-g8576-c199-07 9.6.10 technical specifications 6es5 466-3la11/ 466-4ua11 analog input modules input ranges 0-20 ma; 4-20 ma;  20 ma; 0-1.25 v; 0-2.5 v; 0-5 v; 1-5 v; 0-10 v;  1.25 v;  2.5 v;  5 v;  10 v number of inputs 16 single or 8 differential inputs in groups of 4 or 2 channels (selectable) voltage or current measurement measuring principle instantaneous value encoding conversion time 25  s typical (per channel) isolation ye s permissible isolation between sensor ref. potential and central ground point 25 v ac/60 v dc max. supply voltage internal external + 5 v +/- 5 % none current consumption, internal 466-3la11 466-4ua11 0.7 a typical 0.6 a typical encoding time per measured value 250  s duration of cyclic sampling (cycle time) for 8 measured values for 16 measured values 2 ms max. 4 ms max. input resistance voltage measuring range current measuring range  10 m  125  type of circuit for sensors two-wire circuit digital representation of the input signal selectable, following types of representation: - 12-bit two's complement - 11-bit value with sign - 12-bit binary max. permissible input voltage without destruction  30 v max. (static) or  75 v (pulse for 1 ms max. and duty ratio 1:20) interference voltage suppression common-mode interference (vpp = 1 v) 70 db min. basic error limits - voltage ranges except for 0-1.25 v;  1.25 v - current ranges and 0-1.25 v ;  1.25 v 0.1 % 0.2 % analo g input/output modules
9-103 system manual c79000-g8576-c199-07 operational error limit (0 o c ... 60 o c) - voltage ranges except for 0-1.25 v,  1.25 v - current ranges and 0-1.25 v,  1.25 v 0.2 % 0.24 % error signal for overflow for internal error yes (overflow bit set) yes (error bit (= e bit) set) single error linearity tolerance polarity reversal error 0.02 % 0.05 % 0.05 % temperature error 0.005 %/k insulation rating to vde 0160 line length - shielded 200 m max. front connector 466-3la11 466-4ua11 43-pole 42-pole power dissipation of module 466-3la11 466-4la11 3.5 w typical 3 w typical weight approx. 0.4 kg rated insulation voltage (between channels and ground point) tested at 500 v analo g input/output modules
9-104 system manual c79000-g8576-c199-07 front connector assignments for 466-3la11 voltage-to-ground measurement differential measurement front strip pin 1 2 3 4 6 8 10 13 15 17 19 20 22 23 25 27 29 31 34 36 38 40 41 5 7 9 11 14 16 18 26 28 30 32 35 37 39 m8- mext mext mext mext mext mext mext mext m9- m13- m10- m14- m11- m15- m12- m0+ m0+ m4+ m2+ m6+ m1+ m5+ m3+ m7+ m1+ m5+ m2+ m6+ m3+ m7+ m4+ m0- mext mext mext mext mext mext mext mext m1- m5- m2- m6- m3- m7- m4- 24 42 33 21 12 m8+ m0- m4- m2- m6- m1- m5- m3- m7- m9+ m13+ m10+ m14+ m11+ m15+ m12+ 1 2 3 4 6 8 10 13 15 17 19 20 22 23 25 27 29 31 34 36 38 40 41 5 7 9 11 14 16 18 26 28 30 32 35 37 39 24 42 33 21 12 front strip pin figure 9-35 front connector assignments analo g input/output modules
9-105 system manual c79000-g8576-c199-07 front connector assignments for 466-4ua11 voltage-to-ground measurement differential measurement front strip pin 1 2 3 4 6 8 10 13 15 17 19 20 22 23 25 27 29 31 34 36 38 40 41 5 7 9 11 14 16 18 26 28 30 32 35 37 39 m0+ m0+ mext mext mext mext mext mext mext m1- m13- m2- m14- m11- m15+ m4- m6+ m0- m5+ m3+ m8+ m5+ m6+ m3+ m7- m4+ m2+ mext m1+ mext mext mext m1+ m5- m2+ m6- m3- m15- m4+ 24 42 33 21 12 m0- mext mext mext m6- mext m5- m3- m7- m9- m13+ m10- m14+ m11+ m12- front strip pin 1 2 3 4 6 8 10 13 15 17 19 20 22 23 25 27 29 31 34 36 38 40 41 5 7 9 11 14 16 18 26 28 30 32 35 37 39 24 42 33 21 12 m8- m9+ m10+ m12+ m7+ mext m1- m2- m4- m7+ figure 9-36 front connector assignments note take the differing pin assignment in comparison to the 466-3la11 into consideration! analo g input/output modules
9-106 system manual c79000-g8576-c199-07 9.7 the 470 analog output module 9.7.1 design the module is designed as a plug-in pcb for central controllers and expansion units with a backplane connector and with a blade connector to accept a plug-in front connector. you can directly connect the process signal lines to the front connector, which is available separately, with screw or crimp terminals. situated on each module is an addressing switch with six rockers to set the module address. the modules are protected by covers on both sides. blade connector addressing switch front connector figure 9-37 analog output module 9.7.2 function of the enable input the 470 module has an enable circuit. you can use the enable inputs to switch off individual modules whilst the plc is in operation. this means that:  the module can no longer be addressed by the user program.  on analog output modules, the last analog value to be output is retained. modules which are switched off can be removed or inserted during operation. if this is not necessary, operate the module with the enable input switched off. addressing switch, mode switches analo g input/output modules
9-107 system manual c79000-g8576-c199-07 the enable circuit requires an external 24 v voltage at enable inputs f+/f- in the front connector. if there is no voltage at f+/f-, the modules will not acknowledge. when the front connector is swivelled away from the front strip of the module, the supply of power to the enable input is interrupted, i.e. the module is switched off and can no longer be addressed by the user program: a timeout (qvz) occurs in the cc. the -4ux12/13-type modules additionally offer the facility for changing the enable mode. the modules have a jumper accessible from above in the vicinity of the addressing switch. enable jumper figure 9-38 enable input and enable jumper jumper inserted: enable input (f+/f-) active (factory setting) jumper open: enable input (f+/f-) switched off examples of functioning of the enable inputs:  to switch off individual subprocesses, i.e. outputs of various modules can be operated from a common load supply and yet activated separately.  the load voltage of individual modules can be monitored without additional circuitry. any reactions to failure of the load voltage can be programmed in the qvz (timeout) organization block. enable input switching off the enable input analo g input/output modules
9-108 system manual c79000-g8576-c199-07 you must observe the following when configuring systems: switching on at the latest 100 ms after power-up of the plc, the voltage must be present at the enable inputs of the i/o modules. switching off when the plc has been switched off, the voltage at the enable inputs of the i/o modules must still be present as long as the internal 5 v voltage is present. however, you must ensure that the 24 v load supply for analog output modules is switched off together with the plc. if the supply voltage is still present at the modules and the plc is switched off, the output values can drift. (the analog holding elements for the outputs will no lon- ger be refreshed with the current value, because there is no 5 v supply to the modules from the bus.) you should observe the following instructions for switching off ccs and equipment for supplying power to the enable inputs. when there is a need to switch off the load power supply separately without affecting the enabling of modules, there are the following possibilities for producing the enable voltage. these exist even when the load power supply is used without an additional capacitor and common shutdown.  230 v ac supply for cc/eu and load power supply f+ l+ i/o modules 230 v ac cc/eu -951 a) c) b) battery l+ power supply load power supply 24v supply for the enable inputs from: a) 6es5 951-4lb11 load power supply b) battery c) terminals for 24 v on the front plate of the power supply configuring switching off the cc separate or common shutdown of the cc/eu and load power supply analo g input/output modules
9-109 system manual c79000-g8576-c199-07  24 v supply for cc/eu and i/os f+ l+ i/o modules 24 v dc b) a) cc/eu l+ battery power supply 24v supply for the enable inputs from: a) battery b) terminals for 24 v on the front plate of the power supply proper functioning is ensured if the 24 v load power supply has an output capacitance of at least 4700  f per 10 a of load current. other units which do not meet this condition can be adapted to this requirement by connecting a 10000  f / 40 v capacitor in parallel. 10000 m f/ 40v cc/eu f+ l+ 230 v ac i/o modules load power supply 24v power supply common shutdown of the cc/eu and load power supply with a 230 v ac supply analo g input/output modules
9-110 system manual c79000-g8576-c199-07 9.7.3 special features of the 470 analog output module the basp signal is not interpreted by the 470 analog output module. once output, a value is retained. you can output analog values to the process via analog output modules with a function block from the abasic functionso package. 9.7.4 setting the module address you set the module address on the addressing switch. this also establishes the necessary assignments between user program and process connection. the module address is the sum of the decimal significances of the switch rockers in the on setting ( ). one data word = two data bytes is required to process an input or an output. a module with 8 inputs or outputs reserves 16 byte addresses. you can affix the adhesive label with the desired module address on a free labeling field under the addressing switch. the switch rockers to be set for the module address specified as a decimal number (address bit adb) are marked by dots on the label. press the individual rockers of the addressing switch downwards with a ballpoint pen or similar object, but not a pencil. on setting (switch pressed) addressing switch address bit decimal signification of the address bit free field for label with module address and marked switch settngs address (decimal) 128 64 32 16 8 4 2 1 adb7 adb6 adb5 adb4 adb3 adb2 adb2 is not connected adb1 adb0 adb0 and adb1 are not assigned figure 9-39 labeling of the addressing switch the address under which the module is referenced by the step 5 program is independent of the slot. basp (output inhibit) function block labeling field analo g input/output modules
9-111 system manual c79000-g8576-c199-07 for analog output modules ( 8 outputs) only the lowest address (start address) is set. other addresses (subaddresses) are decoded on the module. note the start address of an analog module must be a multiple of the double channel number. 8 channels : 0, 16, 32, 48, ... 240 ensure that all the switches are operated properly (meaning pressed past the latching point). do not use a pencil to set the addressing switch. if one of the outputs (channel 0 to 7) of a module is to be addressed, the relevant subaddress must be specified in the program. the subaddress of the output, based on the start address of the module, is given by: start address + 2 x channel no. = subaddress example: analog output module with 8 outputs the address is the sum of the significances set with the individual coding switches. 160 = 128 + 32 = 2 7 + 2 5 on setting (switch pressed) ib 160 128 64 32 16 8 4 2 1 adb7 adb6 adb5 adb4 adb3 adb2 adb1 adb0 a module with 8 outputs (channel 0 to 7) and start address 160 reserves the address range from 160 to address 160 + 7 x 2 = 174 in this example, the next free address for another module is 176. addresses already assigned must not be set again. start address, subaddress analo g input/output modules
9-112 system manual c79000-g8576-c199-07 however, analog input modules and analog output modules may be given the same address with cyclic sampling because they are distinguished by the user program. this is not possible with selective sampling. for cyclic sampling, you can address the module in the address range from 0 to 255, and for selective sampling from 128 to 255. for selective sampling, you can also use the address range from 0 to 127 after appropriate programming in db 1 of the user program. example: on an analog output module with 8 outputs with start address 144 (ib 144 = output byte 144), output channel 7 is to be scanned by the program. step action 1 affix the self-adhesive label with address 160 on the free field under the addressing switch on the module. adb 4 and adb 7 are marked on the label. 2 press the appropriate rockers of the addressing switch down on the side marked by a dot on the module cover. set the other rockers to the opposite setting. this sets the start address of the module. adb 4 and adb 7 results in 2 4 + 2 7 = 16 + 128 = 144 3 enter the address 144 + 7 x 2 = 158 in the program for input channel 7. addressing for cyclic/selective sampling analo g input/output modules
9-113 system manual c79000-g8576-c199-07 9.7.5 removing and inserting modules ! warning when removing and inserting the front connector during operation, hazardous voltages of more than 25 v ac or 60 v dc may be present at the module pins. when this is the case at the front connector, live modules may only be replaced by electrical specialists or trained personnel in such a way that the module pins are not touched. during operation, the front connector and module must not be removed or inserted without the enable jumper or active enable circuit. install an analog output module as follows: step action 1 release the upper locking bar on the subrack and swivel it upwards and out. 2 insert the module at the desired slot in the subrack and push it back in the guides. 3 latch the module by rotating the locking pin by 90 o at the lower end of the module. it must no longer be possible to pull the module forwards. 4 engage the front connector on the support pin of the module. the width of the support pin also provides keying to prevent front connectors from being fitted to the wrong modules (for example, front connectors with 115/230 v ac wiring cannot be plugged into analog modules). 5 tighten the screw in the upper part of the front connector. analo g input/output modules
9-114 system manual c79000-g8576-c199-07 remove an analog output module as follows: step action 1 release the upper locking bar on the subrack and swivel it upwards and out. 2 slacken the screw in the upper part of the front connector. this causes the front connector to be pressed out of the female connector of the module. contacts f+ and f- of the enable input at the upper end of the front connector are thus opened first. if the enable input is active, power is removed from the outputs and the module is isolated from the s5 bus. 3 swing the front connector out and lift it away from the support pin of the module. 4 release the module by rotating the locking pin by 90 o at the lower end of the module. you can pull the module out of the subrack with a grip with swivels outwards. 1 2 3 5 6 4 module front connector support mount support pin figure 9-40 module with front connector 1 screw 2 locking pin 3 support mount 4 support pin 5 grip 6 backplane connector comply with vde specifications 0110 and 0160 to carry out the wiring of supply and signal lines which are to be connected to the programmable controllers and front connectors of the modules. detailed information on cabinet assembly, cabinet ventilation and protective measures can be found in chapter 3. analo g input/output modules
9-115 system manual c79000-g8576-c199-07 9.7.6 marking of modules and front connectors for the marking of modules and front connectors, labels are supplied with the module and central controller; they are affixed as shown in figure 9-41. 5 1 1 3 4 2 figure 9-41 marking and labeling of modules 1 label with the module address under which the module is referenced by the step 5 program 2 labeling strip with the product designation for the module; space to mark the module version and label the channels 3 label with module address and marking of the required settings for the addressing switch 4 labeling strip for terminal designations or connection diagrams (strip in the cover of the front connector) 5 name plate analo g input/output modules
9-116 system manual c79000-g8576-c199-07 9.7.7 connecting the signal lines for connection of the signal lines, front connectors for 20 and 40 mm mounting width with crimp connection and 40 mm mounting width with screw connection are available (screwdriver blade width: 3.5 mm, maximum torque: 0.8 nm). use stranded conductor to facilitate handling of the front connector. ferrules are not required for screw connections, because the screw terminals are provided with wire protection. when the crimp contact is inserted in the plastic body of the front connector, a click can clearly be heard. this indicates that the contact is engaged. for jumpering or to correct the wiring, you can remove the contacts with a releasing tool (see ordering information) without having to pull out the front connector. ferrules are not required for screw connections, because the screw terminals are provided with wire protection. you can use ferrules of 7 mm in length to din 46228. the maximum terminal area is 2 x 2.5 mm 2 . terminal t connector t max. nf cross-section connector for rtdvlt mounting width of mdl type type 6es 497- no. of contacts signal or supply conductor aux. jumper in connector 1) rated voltage module crimp connection -4ua12 2) 42 0.5 mm 2 0.5 mm 2 5 to 60 v dc 20 mm operation with fan -4ua22 2) 42 0.5 mm 2 0.5 mm 2 5 to 60 v dc 40 mm oti screw ti -4ub12 42 0.5 to 2.5 mm 2 0.5 to 1.0 mm 2 5 to 60 v dc 40 mm operation without fan connection -4ub31 42 0.5 to 1.5 mm 2 0.5 to 1.0 mm 2 5 to 60 v dc 20 mm without fan 1) to multiply the supply and 0 v ground terminals, and to connect the enable input 2) the crimp contacts must be ordered separately for these types of connector. ! caution only extra-low voltage 60 v dc with safety separation from system voltage may be used for the 24 v dc supply and for the 24 v dc input signals. safety separation can be implemented to the requirements of, amongst other sources, vde 0100 part 410/hd 384-4-41/iec 60364-4-41 (as functional extra-low voltage with safety separation) or vde 0805/en 60950/iec 60950 (as safety extra-low voltage selv) or vde 0106 part 101. analo g input/output modules
9-117 system manual c79000-g8576-c199-07 9.7.8 connecting loads to the 470 analog output module the voltage at the load is measured at a high resistance via the sensor lines (s+/s-) of voltage output qv, so that voltage drops on the load lines do not falsify the load voltages. lines s+(x) and s-(x) should therefore be directly connected to the load (four-wire circuit). the voltage drops on the lines from qv(x) to the load and from the load to m ana must not exceed 3 v. + - load (voltage) + - load (current) qv(x) s+(x) s - (x) qi (x) i m ana figure 9-42 connecting loads qv(x) voltage output, voltage on channels 0 to 7 qi(x) current output, current on channels 0 to 7 s+(x) sensor line (+) for channels 0 to 7 s- (x) sensor line (-) for channels 0 to 7 m ana ground terminal for the analog section when current and voltage outputs are used on the 470-4ua/-4uc... analog output modules, connect the loads as follows: + - + - qv0 m ana s+0 s-0 qi0 + - + - + - + - + - m ana m ana current output only jumper jumper qv1 s+1 s-1 qi1 qv2 s+2 s-2 qi2 qv3 s+3 s-3 qi3 qv4 s+4 s-4 qi4 _ jumper jumper not current and not voltage output figure 9-43 connecting loads connecting loads to current and voltage outputs analo g input/output modules
9-118 system manual c79000-g8576-c199-07 if, with voltage outputs, an excessively great voltage drop must be expected on the lines to the load, you must route the sensor lines s+(x) and s-(x) to the load. when voltage outputs are not used, the s+(x) sensor lines in the front connector must be connected to the corresponding voltage output terminals (qv(x)) with wire jumpers. the s-(x) sensor lines must be connected to m ana with wire jumpers. you must also insert the same jumpers if only current outputs are used. unused current outputs may remain open. the maximum load for the current outputs including line resistance, must not exceed 300 ohms. the voltage outputs of the 470 analog output module are wired as follows: + - qv0 s+0 s-0 + - + - m ana no load at qv3 jumper jumper qv1 s+1 s-1 qv2 s+2 s-2 qv3 s+3 s-3 m ana figure 9-44 connecting loads the s+(x) and s-(x) sensor lines must be routed to the load (four-wire circuit) if the voltage drop on the lines to the load is not negligible. the common connection for the voltage outputs is m ana . if the voltage drop on lines to the load is negligible, you can connect s+(x) to qv(x) and s-(x) to m ana in the front connector. when voltage outputs are unused, you must insert jumpers in the front connector, e.g. qv(3) to s+(3) and s-(3) to m ana for unused voltage output 3 (see previous section). connecting loads to voltage outputs four-wire circuit analo g input/output modules
9-119 system manual c79000-g8576-c199-07 9.7.9 measured-value representation units output voltage or current of the 470 analog output module byte 0 byte 1 -4ua/b12/13 -4ua12/13 -4uc12/13 7 2 11 6 2 10 5 2 9 4 2 8 3 2 7 2 2 6 1 2 5 0 2 4 7 2 3 6 2 2 5 2 1 4 2 0 3 x 2 x 1 x 0 x 1280 1025 12.5 v 10.0098 v 25.0 ma 20.0195ma 6.0 v 24.0 ma 5.004 v 20.016 ma 0 0 1 1 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 overrange 1024 1023 512 256 128 64 1 0 - 1 - 64 - 128 - 256 - 512 -1024 10.0 v 9.99 v 5.0 v 2.5 v 1.25 v 0.625 v 9.8 mv 0 v - 9.8 mv - 0.625 v - 1.25 v - 2.5 v - 5.0 v - 10.0 v 20.0 ma 19.98 ma 10.0 ma 5.0 ma 2.5 ma 1.25 ma 19.5 ma 0 ma 0 ma 0 ma 0 ma 0 ma 0 ma 0 ma 5.0 v 20.0 ma 4.995 v 19.98 ma 3.0 v 12.0 ma 2.0 v 8.0 ma 1.5 v 6.0 ma 1.25 v 5.0 ma 1.004 v 4.016 ma 1.0 v 4.0 ma 0.996 v 3.984 ma 0.75 v 3.0 ma 0.5 v 2.0 ma 0 v 0 ma - 1 v 0 ma - 3.0 v 0 ma 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 0 0 0 0 0 0 0 1 1 1 1 1 1 0 1 1 0 0 0 0 0 1 1 1 1 1 0 0 1 0 1 0 0 0 0 1 1 1 1 0 0 0 1 0 0 1 0 0 0 1 1 1 0 0 0 0 1 0 0 0 1 0 0 1 1 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 1 0 1 0 0 0 0 0 rated range -1025 -1280 -10.0098v -12.5 v 0 ma 0 ma - 3.004v 0 ma - 5.0 v 0 ma 1 1 0 0 1 1 1 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 overrange digital measured-value representation as two's complement analo g input/output modules
9-120 system manual c79000-g8576-c199-07 9.7.10 technical specifications 6es5 470-4ua12, 6es5 470-4ub12 and 6es5 470-4uc12 analog output modules rated output ranges - 6es5 470-4ua12 (-4ua13) - 6es5 470-4ub12 (-4ub13) - 6es5 470-4uc12 (-4uc13) 0 to  10 v and 0 to 20 ma parallel for  1024 units  10 v for  1024 units 1 to 5 v and 4 to 20 ma parallel for 0 to 1024 units number of outputs 8 voltage and current outputs each, no-load and short-circuit-proof isolation yes 8 outputs with respect to m ext , m and l+/l- measured value representation 12-bit (two's complement) linearity in the range of  1024 units  2 lsb =  0.2 % operational error limits (0 to 60 o c)  0.6 % temperature coefficient for voltage and current outputs 1 x 10 -4 /k permissible overrange approx. 25 % (  1024 to  1272 units) fault current at voltage output approx. 25 ma no-load voltage at current output approx. 18 v load impedance - at voltage output - at current output  3.3 k   300  delay between data transfer and analog value output to > 99%  5ms capacitive load including line capacity for -4ua12 from version 03 and for -4ub12 and -4uc12 from version 04: 100 nf max. 1  f max. permissible voltage drop on voltage output lines  0.3 v at maximum output voltage power supply - digital section from system bus - analog section from load voltage - enabling for module, f+/f- 5 v  5 %; approx. 250 ma 24 v; 200 to 400 ma 24 v; approx. 7 ma permissible potential difference between reference poten- tial of the load and housing (u cm ) 25 v ac / 60 v dc max. voltage test to vde 0160 between outputs and housing tested at 500 v ac analo g input/output modules
9-121 system manual c79000-g8576-c199-07 470-4ub 470-4ua 470-4uc connection of process signal lines 1 2 3 4 6 8 10 13 15 17 19 20 22 23 25 27 29 31 34 36 38 40 41 f+ l+ f- data mamory and s5 bus control dau t 5 7 9 11 14 16 18 26 28 30 32 35 37 39 ch.7 qv0 24 u 42 33 v 21 12 l- ch.6 v v ch.5 ch.4 v v ch.3 v ch.2 v v ch.1 ch.0 s+0 s-0 qv1 s+1 s-1 u u u u u u u m ana qv2 s+2 s-2 qv3 s+3 s-3 qv4 s+4 s-4 qv5 s+5 s-5 qv6 s+6 s-6 qv7 s+7 s-7 # front strip pin 1 2 3 4 6 8 10 13 15 17 19 20 22 23 25 27 29 31 34 36 38 40 41 f+ l+ f- dau t 5 7 9 11 14 16 18 26 28 30 32 35 37 39 ch.7 qv0 24 u 42 33 v 21 12 l- ch.6 v v ch.5 ch.4 v v ch.3 v ch.2 v v ch.1 ch.0 s+0 s-0 qv1 s+1 s-1 u m ana qv2 s+2 s-2 qv3 s+3 s-3 qv4 s+4 s-4 qv5 s+5 s-5 qv6 s+6 s-6 qv7 s+7 s-7 i i i i i i i i qi0 qi1 qi2 qi3 qi4 qi5 qi6 qi7 i i u u i i u u i i u u i i # front strip pin connection of process signal lines block diagram of the module block diagram of the module data mamory and s5 bus control figure 9-45 front connector assignments front connector assignments analo g input/output modules
9-122 system manual c79000-g8576-c199-07 analo g input/output modules
10-1 system manual c79000-g8576-c199-07 monitoring module this chapter describes the installation, the wiring and the operation of the monitoring module 6es5 313-3aa12. section description page 10.1 application 10-2 10.2 installation 10-6 10.3 operation 10-8 10.4 technical specifications 10-14 10.5 address table 10-16 chapter overview 10
10-2 system manual c79000-g8576-c199-07 10.1 application the monitoring module can be used in the expansion units of the programmable controllers s5-115u, s5-135u and S5-155U. the module monitors the data bus, the address bus and the control signals memw/, memr/ and rdy/. faults are displayed via four red leds on the front panel. a group signal is output at the same time via a floating contact. following a fault, the module can be reset by means of the reset key on the front panel or the reset input (see section 10.2.3). 10.1.1 design the monitoring module is designed as a plug-in pcb in double euroformat with a 32-pin backplane connector for the s5 bus. a connector for the relay contact and reset input as well as one green led, four red leds and a reset key are located on the front panel. operation (green led) command output inhibit (red led) control signal fault (red led) address bus fault (red led) data bus fault (red led) reset input relay contact reset key run basp r/w adb db 1 2 3 4 5 6 7 8 s1 s2 s3 s4 s5 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 x4 1 6 bus pesp qvz 125ms 250ms 500ms 1s 1 2 4 8 16 32 64 128 on off on off on off on off on off figure 10-1 location of the coding switches note ensure that all the switches are operated properly (meaning pressed past the latching point). monitorin g module
10-3 system manual c79000-g8576-c199-07 10.1.2 mode of operation 10.1.3 block diagram control signal monitoring memr memw rdy edge basp r/w db adb cpkl s r run preselection of time address comparison read and compare data bit inversion ouput data s5 bus address bus data bus address comparison s1 s2 s3 s4 x4/5 x4/6 x4/4 reset input l+ (24v) l internal +5v internal 0v x4/3 x4/2 x4/1 relay contact  1 time monitoring time monitoring time monitoring address comparison address comparison  1  1 figure 10-2 block diagram monitorin g module
10-4 system manual c79000-g8576-c199-07 10.1.4 fault detection from an address which has been set at switch s1, the data (55h or aah) is read by the cpu from the monitoring module. this data is to be written back by the cpu to the address set at switch s2. the module inverts the accurate incoming data bit by bit (from 55h to aah or vice versa) which is read again in the next cycle from the address set at s1. if the data which has been set on the monitoring module is not returned within the set monitoring time, the module signals a data bus fault. detectable faults interruptions of the data lines, short circuits to ground and + 5v, short circuits between adjacent data lines, e.g. db0-db1, db1-db2 etc. non-detectable faults short circuits between even data lines db0-db2-db4-db6 and between odd data lines db1-db3-db5-db7. the addresses which have been set at switches s3 and s4 are only alistened too by the monitoring module, i.e. they do not output an acknowledgement signal (rdy/) and are not active on the data bus. if one or both addresses are not accessed again within the monitoring time, the monitoring module signals an address bus fault. detectable / non-detectable faults the same as for the data bus, if the inverse addresses 85 (55h) and 170 (aah) have been set at the addressing switches s3 and s4 of all monitoring modules. data bus faults address bus faults monitorin g module
10-5 system manual c79000-g8576-c199-07 a control line fault (r/w) occurs if the write signal (memw/) and the read signal (memr/) are active simultaneously, the acknowledgement signal (rdy/) is active without a (memw/) or (memr/) signal and the address line 'peripheral memory' (pesp') has not changed from status a1o to a0.o evaluation of the control signal (pesp') can be turned off with the s5/7 switch. if the module is used in a programmable controller into which only i/o modules may be inserted (i.e. no memory modules or cps), this switch must always be turned off. in this configuration, only i/o accesses to the bus are performed and the pesp` signal always has the status a1.o it should also be turned off when using the im 301, im 302 1) , im 304 and im 308 interface modules for expansion units since a permanent pesp` signal can be applied to them. if a command output inhibit (basp) is active, the abaspo led is lit. if one or more faults occur, the corresponding leds are lit, the relay contact commutes and the module no longer acknowledges with the rdy/ signal. this timeout can be suppressed by opening the s5/8 switch. 10.1.5 resetting there are several ways of resetting the module: cpkl/ signal = a1o (when the plc is switched on); trailing edge of the basp signal (during startup of the plc or following return of the load voltage); applying 24 v to the front connector x4 between connections 4 (reset input) and 6 (l-); linking connections 4 (reset input) and 5 (l+) with connector x4. 1) in the s5-115u, the monitoring module cannot be used together with the im 302 / 311 link. control line faults basp messages monitorin g module
10-6 system manual c79000-g8576-c199-07 10.2 installation 10.2.1 possible configurations recommended slots possible slots er 2 ps0 12345 67im er 3 eu 187 eu 186 eu 185 eu 183 eu 184 eu 182 67 311192735435159 75 83 91 107115 123 139 147 155163 99 131 10.2.2 removing and inserting the module is pulled out by holding the handles and gently lifting and lowering while pulling towards you. the monitoring module may only be removed or inserted if the expansion unit is switched off. monitorin g module
10-7 system manual c79000-g8576-c199-07 10.2.3 connecting the reset input 4 5 6 3 2 1 relay contact reset input l+ (24v) l l+ l 4 5 6 3 2 1 relay contact reset input l+ (24v) l reset input (floating) with external 24-v supply reset input (floating) with internal 24-v suppy 10.2.4 switch positions of the relay contact 4 5 6 3 2 1 4 5 6 3 2 1 contact not actuated (idle) or fault contact 1-3 closed contact 1-2 closed contact actuated (operational) 10.2.5 installation guidelines the module is to be wired according to the vde regulations 0100, 0110 and 0160. detailed information on power supply, cabinet design, cabinet ventilation, cabinet wiring and protective measures can be found in chapter 3. monitorin g module
10-8 system manual c79000-g8576-c199-07 10.3 operation the addresses set at these switches are acknowledged by the monitoring module with rdy/ and are therefore not to be used again for inputs and outputs in this programmable controller (double addressing is not allowed). no acknowledgement signal (rdy/) is returned by the monitoring module to the addresses set the switches s3 and s4. these addresses must be accessed by the programmable controller as input or output addresses. this means that they must be occupied by i/o modules or by one monitoring module at switches s1 and s2. these modules must have been inserted into the last expansion unit. to achieve optimum address bus monitoring, inverse addresses should be used [e.g. 85 (55h) 2) and 170 (aah)]. it is advisable to make sure that the setting of switches s3 and s4 is the same on all monitoring modules used. the setting of switches s1and s2 as well s3 and s4 should be the same on the monitoring module in the last expansion unit. switch i nput address can be accessed using memr/ (read) output address can be ac- cessed using memw/ (write) acknowl- edged by module with rdy/ s1 * * s2 * * s3 * * s4 * * 1) select addresses 213 (d5h) and 170 (aah) when using the module in the s5-115u. for exceptions refer to page 10 - 13. switch s1 (read) and s2 (write) switch s3 (listen) and s4 (listen) monitorin g module
1 0 - 9 s y s t e m m a n u a l c 7 9 0 0 0 - g 8 5 7 6 - c 1 9 9 - 0 7 i m 3 0 0 c c 1 1 5 u c c 1 3 5 u c c 1 5 5 u i m 3 1 2 i m 3 1 2 i m 3 1 2 i m 3 1 2 i m 3 1 2 i m 3 1 2 i m 3 1 0 i m 3 1 4 i m 3 1 8 i m 3 1 0 i m 3 1 4 i m 3 1 8 i m 3 0 1 i m 3 0 4 i m 3 0 8 i m 3 0 0 m m 3 1 3 m m 3 1 3 m m 3 1 3 2 n d m m 3 1 3 1 s t m m 3 1 3 e u 1 8 3 u e u 1 8 5 u e u 1 8 3 u e u 1 8 4 u e u 1 8 7 u 3 r d m o n i t o r i n g m o d u l e 3 1 3 i n t h e l a s t e x p a n s i o n u n i t i m 3 1 2 i m 3 1 2 i m 3 1 2 i m 3 1 2 i m 3 1 2 i m 3 1 2 e x p a n s i o n u n i t s c e n t r a l c o n t r o l l e r s e x a m p l e : m o n i t o r i n g m o d u l e
10-10 system manual c79000-g8576-c199-07 10.3.1 addressing s5-130k, s5-135u or S5-155U 1st mm 2nd mm 3rd mm in the last eu s1 e.g. 127 (7fh) 3) e.g. 126 (7eh) 3) 85 (55h) 4) s2 e.g. 127 (7fh) 3) e.g. 126 (7eh) 3) 170 (aah) 4) s3 85 (55h) 5) 85 (55h) 5) 85 (55h) 5) s4 170 (aah) 5) 170 (aah) 5) 170 (aah) 5) user program in ob 1 or fb 0 without s5-dos with s5-dos l eb 127 l py 127 t ab 127 t py 127 l eb 126 l py 126 t ab 126 t py 126 l eb 85 l py 85 t pb 170 t py 170 be be 3) possible addresses 0 (00h) to 255 (ffh) 4) to achieve optimum fault detection, set the inverse addresses 85 (55h) and 170 (aah) at s1 and s2. 5) since the addresses of the monitoring module switches s3 and s4 are not acknowledged, this must be done by the monitoring module contained in the last expansion unit (the most remote from the central controller). the addresses 85 (55h) or 170 (aah) of this monitoring module must be coded at switches s1 or s2, respectively. these addresses may no longer be occupied for i/o tasks. example 1 monitorin g module
10-11 system manual c79000-g8576-c199-07 s5-115u s1 e.g. 128 (80h) 6) e.g. 129 (81h) 6) 213 (d5h) 6) s2 e.g. 128 (80h) 6) e.g. 129 (81h) 6) 170 (aah) 6) s3 213 (d5h) 7) 8) 213 (d5h) 7)8) 213 (d5h) 7)8) s4 170 (aah) 7) 170 (aah) 7) 170 (aah) 7) user program in ob 1 or fb 0 without s5-dos with s5-dos l pb 128 l py 128 t pb 128 t py 128 l pb 129 l py 129 t pb 129 t py 129 l pb 213 8) l py 213 8) t pb 170 t py 170 be be 6) when using the monitoring module in the s5-115u, always select addresses > 127 since that is the only way to address byte to byte. 7) to achieve maximum fault detection, select inverse addresses > 127, e.g. 213 (d5h) and 170 (aah). in this combination, the address bit adb 7 is not monitored . 8) if adb 7 is also to be monitored, the address 84/85 (54h/55h) in the last expansion unit must be occupied by an input or output module and cyclically accessed by the user program. set address 85 (55h) in place of 213 (d5h) at switch s3 of all monitoring modules. select any address between 128 (80h) and 255 (ffh) for switch s1 of the monitoring module in the last expansion unit. as an alternative, you may access the address at s1 of the monitoring module in the last expansion unit vi a direct access (without process image) using l pb 85 or l py 85. then, the addresses 84 and 85 (54h) and (55h) in the process image may no longer be used by other inputs. the address at s3 of all monitoring modules is then also to be set to 85 (55h). example 2 monitorin g module
10-12 system manual c79000-g8576-c199-07 10.3.2 setting the address switches s1, s2, s3, s4 the addresses are set as one-byte addresses as in the case of i/o modules. adb 7 significance 128 adb 0 significance 1 adb 5 significance 32 adb 6 significance 64 adb 4 significance 16 adb 1 significance 2 adb 2 significance 4 adb 3 significance 8 1 2 3 4 5 6 7 8 on off the significance of the rockers pressed down to on at the switches must be added. address 85 is to be set. rockers to be pressed down to on significance 1 (adb 0) 1 3 (adb 2) 4 5 (adb 4) 16 7 (adb 6) 64 85 1 2 3 4 5 6 7 8 on off example monitorin g module
10-13 system manual c79000-g8576-c199-07 10.3.3 setting the switch s5 on: pesp` monitoring on monitoring time rdy/ is suppressed in case of fault rdy/ is also output in case of fault on: off: when basp is active (a1o signal) rdy/ is always output 125ms 500ms 250ms 1s 1 2 3 4 5 6 7 8 on off select the monitoring time (between 125 ms and 1 s) by switching one of the switches s5/1 to s5/4 to on. if none of the four switches s5/1 to s5/4 is in the on position, for safety reasons the monitoring time has been set to 1 s. if serial interface modules and the link between im 304 and im 314 are used, the pesp` monitoring is to be switched off (see section 10.1.4: control line faults). should the acknowledgement signal (rdy/) not be suppressed in the event of a fault, the switch s5/8 must be in the off position. when a basp signal is active, the rdy/ signal will always be output. monitorin g module
10-14 system manual c79000-g8576-c199-07 10.4 technical specifications power supply supply voltage of the system bus power consumption + 5 v 5 % 450 ma max. reset input rated input voltage electrical isolation input voltage for signal 0 for signal 1 input current permissible cable length 24 v dc yes 33 to + 5 v dc or input open +13 to + 33 v dc 8.5 ma 100 m max. unscreened sensor supply for reset input rated output voltage electrical isolation output voltage output current 24 v dc yes 20 to 30 v dc short-circuit proof to l 20 ma max. relay contact loading of contact with resistive load or inductive load 30 v dc/ 1 a max. safety test voltage test acc. to vde 0160 relay contacts referred to internal reset input referred to internal reset input referred to relay contacts 500 r.m.s. 500 r.m.s. 500 r.m.s. mechanical data dimensions (w x h x d) weight 20 mm x 243 mm x 193 mm 270g ambient conditions operating temperature storage and transportation temperature relative humidity operating altitude vibration acc. to iec 68-2-6 shock acc. to iec 68-2-27 0 to + 60 o c 25 to + 70 o c max. 95 % at 25 o c; no condensation max. 3500 m above sea level 10 to 57 hz, 0.15 mm; 57 to 500 hz, 2  12 shocks, half-sine; 15  / 11 ms monitorin g module
10-15 system manual c79000-g8576-c199-07 pin assignment of bus connector x1 b z 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 0 v pesp' adb 0 adb 1 adb 2 adb 3 adb 4 adb 5 adb 6 adb 7 basp 0 v 5 v cpkl/ memr/ memw/ rdy/ db 0 db 1 db 2 db 3 db 4 db 5 db 6 db 7 0 v monitorin g module
10-16 system manual c79000-g8576-c199-07 10.5 address table 16 32 64 128 12 28 44 60 76 92 108 124 140 156 172 188 204 220 236 252 13 29 45 61 77 93 109 125 141 157 173 189 205 221 237 253 14 30 46 62 78 94 110 126 142 158 174 190 206 222 238 254 15 31 47 63 79 95 111 127 143 159 175 191 207 223 239 255 0 16 32 48 64 80 96 112 128 144 160 176 192 208 224 240 2 18 34 50 66 82 98 114 130 146 162 178 194 210 226 242 4 20 36 52 68 84 100 116 132 148 164 180 196 212 228 244 5 21 37 53 69 85 101 117 133 149 165 181 197 213 229 245 6 22 38 54 70 86 102 118 134 150 166 182 198 214 230 246 7 23 39 55 71 87 103 119 135 151 167 183 199 215 231 247 8 24 40 56 72 88 104 120 136 152 168 184 200 216 232 248 9 25 41 57 73 89 105 121 137 153 169 185 201 217 233 249 10 26 42 58 74 90 106 122 138 154 170 186 202 218 234 250 11 27 43 59 75 91 107 123 139 155 171 187 203 219 235 251 1 17 33 49 65 81 97 113 129 145 161 177 193 209 225 241 3 19 35 51 67 83 99 115 131 147 163 179 195 211 227 243 128 64 32 16 8 4 2 1 switch position on 1 2 4 8 significance byte address monitorin g module
11-1 system manual c79000-g8576-c199-07 connector assignments in this chapter are the connector assignments of the  backplane for the central controllers and expansion units  power supplies  backplane connectors and front connectors of the cpus, coordinators and ims. 11
11-2 system manual c79000-g8576-c199-07 connector assignments of the backplane of the s5-135u/155u cc slot 3, cor, i/o slot 11, 27, 43, 59 cpu, cp, i/o, ip backplane 1 pin n rin row pin n rin row conn. 1 no. z b d no. z b d 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 p5 v pl reset memr memw rdy db 0 db 1 db 2 db 3 db 4 db 5 db 6 db 7 pl m5 v pesp adb 0 adb 1 adb 2 adb 3 adb 4 adb 5 adb 6 adb 7 adb 8 adb 9 adb 10 adb 11 basp m5 v ubat adb 12 adb 13 adb 14 adb 15 pl pl pl pl pl pl pl dsi pl baspa 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 p5 v pl reset memr memw rdy db 0 db 1 db 2 db 3 db 4 db 5 db 6 db 7 pl pl m5 v pesp adb 0 adb 1 adb 2 adb 3 adb 4 adb 5 adb 6 adb 7 adb 8 adb 9 adb 10 adb 11 basp m5 v ubat adb 12 adb 13 adb 14 adb 15 irx 1) ire irf irg dsi pl baspa backplane conn. 2 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 p5 v db 12 db 13 db 14 db 15 nau bau reseta peu gep pl m24 v 2) p24 v m5 v db 8 db 9 db 10 db 11 pl pl pl pl pl pl pl pl pl m24 v 2) m5 v pl pl pl pl pl pl pl pl pl pl pl pl pl pl m24 v 2) p15 v 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 p5 v db 12 db 13 db 14 db 15 m5 v nau bau peu gep pl m24 v 2) p24 v m5 v db 8 db 9 db 10 db 11 pl pl m5 v pl pl m5 v pl pl m24 v 2) m5 v m5 v pl pl pl m24 v 2) p15 v abbreviations: im-v - im slot with additional power supply output irq - interrupt source (module which generates the interrupt) pl - private line 1) see pin designations for the interrupt signals 2) m24 v also serves as the return line for p15 v. connector assi g nments
11-3 system manual c79000-g8576-c199-07 slot 19, 35, 51, 67, 75, 83, 91, 99 cp, ip, i/o, irq slot 107, 115, 123, 131 cp, ip, i/o, im307 (irq) backplane 1 pin- n pin row pin- n pin row conn. 1 no. z b d no. z b d 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 p5 v pl reset memr memw rdy db 0 db 1 db 2 db 3 db 4 db 5 db 6 db 7 pl m5 v pesp adb 0 adb 1 adb 2 adb 3 adb 4 adb 5 adb 6 adb 7 adb 8 adb 9 adb 10 adb 11 basp m5 v ubat adb 12 adb 13 adb 14 adb 15 ira irb irc ird ire irf irg dsi baspa 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 p5 v pl reset memr memw rdy db 0 db 1 db 2 db 3 db 4 db 5 db 6 db 7 pl m5 v pesp adb 0 adb 1 adb 2 adb 3 adb 4 adb 5 adb 6 adb 7 adb 8 adb 9 adb 10 adb 11 basp m5 v ubat adb 12 adb 13 adb 14 adb 15 ira irb irc ird ire irf irg dsi baspa backplane conn. 2 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 p5 v db 12 db 13 db 14 db 15 nau bau gep pl m24 v 1) p24 v m5 v db 8 db 9 db 10 db 11 pl pl pl pl pl * pl m24 v 1) m5 v pl * pl pl m24 v 1) p15 v 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 p5 v db 12 db 13 db 14 db 15 nau bau reseta gep pl m24 v 1) p24 v m5 v db 8 db 9 db 10 db 11 pl pl peu pl pl pl m24 v 1) m5 v pl pl m24 v 1) p15 v pl * = only at slots 75, 83, 91 and 99 1) m24 v also serves as the return line for p15 v. connector assi g nments
11-4 system manual c79000-g8576-c199-07 slot 139, 147 i/o, im, ip without page addressing slot 155, 163 i/o, im backplane 1 pin- n pin row pin- n pin row conn. 1 no. z b d no. z b d 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 p5 v pl reset memr memw rdy db 0 db 1 db 2 db 3 db 4 db 5 db 6 db 7 m5 v pesp adb 0 adb 1 adb 2 adb 3 adb 4 adb 5 adb 6 adb 7 adb 8 adb 9 adb 10 adb 11 basp m5 v adb 12 adb 13 adb 14 adb 15 m5 v m5 v m5 v m5 v m5 v m5 v m5 v baspa 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 p5 v pl reset memr memw rdy db 0 db 1 db 2 db 3 db 4 db 5 db 6 db 7 m5 v pesp adb 0 adb 1 adb 2 adb 3 adb 4 adb 5 adb 6 adb 7 adb 8 adb 9 adb 10 adb 11 basp m5 v p5 v adb 12 adb 13 adb 14 adb 15 p5 v p5 v m5 v m5 v m5 v m5 v m5 v m5 v m5 v baspa backplane conn. 2 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 p5 v db 12 db 13 db 14 db 15 reseta m5 v m5 v m5 v m5 v m5 v m5 v m5 v db 8 db 9 db 10 db 11 peu m5 v m5 v m5 v m5 v m5 v m5 v 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 p5 v db 12 db 13 db 14 db 15 p5 v p5 v p5 v reseta m5 v m5 v m5 v m5 v m5 v m5 v m5 v db 8 db 9 db 10 db 11 p5 v p5 v p5 v peu m5 v m5 v m5 v m5 v m5 v m5 v pin designation of the interrupt signals on the backplane interrupt sink interrupt source module cpu 1 cpu 2 cpu 3 cpu 4 i/os/cp/ip slot no. 11 27 43 59 19, 35, 51, 67-131 signal ira irb irc ird ire (cpu 948 only) irf (cpu 948 only) irg (cpu 948 only) 1d 14 1d 22 1d 24 1d 26 1d 14 1d 22 1d 24 1d 26 1d 14 1d 22 1d 24 1d 26 1d 14 1d 22 1d 24 1d 26 1d 14 1d 16 1d 18 1d 20 1d 22 1d 24 1d 26 connector assi g nments
11-5 system manual c79000-g8576-c199-07 connector assignments of the backplane for the eu 183u, 184u, 187 u i/o modules im 312-5 eu slot eu slot 183u 184u 187u 11 to 155 3 to 155 3 to 147 184u 187u 163 backplane 1 pin n pin row pin n pin row p conn. 1 no. z b no. z b d 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5v - cpkl memr memw rdy db0 db1 db2 db3 db4 db5 db6 db7 - - 0v pesp adb0 adb1 adb2 adb3 adb4 adb5 adb6 adb7 0v 0v 0v 0v basp 0v 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5v - cpkl memr memw rdy db0 db1 db2 db3 db4 db5 db6 db7 - 0v 0v pesp adb0 adb1 adb2 adb3 adb4 adb5 adb6 adb7 0v 0v 0v 0v basp 0v shield +5v +5v +5v +5v +5v +5v +5v 0v 0v 0v 0v 0v 0v 0v 0v im 300-3 and -5 / 312-3 im 310, im 314, im 317, im 318 eu slot eu slot 183u 163 183u 3 backplane 1 pin- n pin row pin- n pin row p conn. 1 no. z b d no. z b d 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5v - cpkl memr memw rdy db0 db1 db2 db3 db4 db5 db6 db7 eank - 0v pesp adb0 adb1 adb2 adb3 adb4 adb5 adb6 adb7 0v 0v 0v 0v basp 0v shield +5v - - - - +5v +5v 0v 0v 0v 0v 0v 0v 0v baspa 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5v takt cpkl memr memw rdy db0 db1 db2 db3 db4 db5 db6 db7 - - 0v pesp adb0 adb1 adb2 adb3 adb4 adb5 adb6 adb7 0v 0v 0v 0v basp 0v shield +5v - - - - +5v +5v 0v 0v 0v 0v 0v 0v 0v baspa backplane conn. 2 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5v - - - - +5v +5v +5v cpkla - 0v 0v 0v 0v 0v 0v 0v - - - - +5v +5v +5v nau - 0v 0v 0v 0v 0v 0v - 0v - - - +5v +5v +5v - - - - - - - - 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5v - - - - +5v +5v +5v cpkla - 0v 0v 0v 0v 0v 0v 0v - - - - +5v +5v +5v nau - 0v 0v 0v 0v 0v 0v - 0v - - - +5v +5v +5v - - - - - - - - connector assi g nments
11-6 system manual c79000-g8576-c199-07 connector assignments of the backplane for the eu 185u im 310 and im 314 i/o module slot 3 923c coordinator i/o module slot 11 pin- pin row pin- pin row no. z b d no. z b d backplane conn. 1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v reset memr memw rdy db0 db1 db2 db3 db4 db5 db6 db7 dsi 0 v pesp adb0 adb1 adb2 adb3 adb4 adb5 adb6 adb7 adb8 adb9 adb10 adb11 basp 0 v adb12 adb13 adb14 adb15 0 v 0 v 0 v 0 v 0 v 0 v 0 v baspa 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v reset memr memw rdy db0 db1 db2 db3 db4 db5 db6 db7 0 v pesp adb0 adb1 adb2 adb3 adb4 adb5 adb6 adb7 adb8 adb9 adb10 adb11 basp 0 v ubat adb12 adb13 adb14 adb15 dsi baspa backplane conn. 2 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v db12 db13 db14 db15 reseta 0 v 0 v 0 v 0 v 0 v 0 v 0 v db8 db9 db10 db11 + 5v + 5v + 5v nau 0 v 0 v 0 v 0 v 0 v 0 v 0 v reset 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v db12 db13 db14 db15 nau bau reseta peu gep m2 + 24v 0 v db8 db9 db10 db11 rxds6 txds6 rxds4 txds4 rxds2 txds2 m2 0 v rxds8 txds8 rxds7 txds7 rxds5 txds5 rxds3 txds3 rxds1 txds1 sprxd m2 + 15 v connector assi g nments
11-7 system manual c79000-g8576-c199-07 communication processor intelligent i/os i/o module slots 19 to 75 communication processor intelligent i/os i/o module slots 83 to 139 pin- pin row pin- pin row no. z b d no. z b d backplane conn. 1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v reset memr memw rdy db0 db1 db2 db3 db4 db5 db6 db7 0 v pesp adb0 adb1 adb2 adb3 adb4 adb5 adb6 adb7 adb8 adb9 adb10 adb11 basp 0 v ubat adb12 adb13 adb14 adb15 dsi baspa 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v reset memr memw rdy db0 db1 db2 db3 db4 db5 db6 db7 0 v pesp adb0 adb1 adb2 adb3 adb4 adb5 adb6 adb7 adb8 adb9 adb10 adb11 basp 0 v ubat adb12 adb13 adb14 adb15 dsi baspa backplane conn. 2 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v db12 db13 db14 db15 nau bau peu gep m2 + 24 v 0 v db8 db9 db10 db11 rxdsn m2 0 v txdsn sprxd m2 +15 v 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v db12 db13 db14 db15 nau bau peu gep m2 + 24 v 0 v db8 db9 db10 db11 m2 0 v m2 + 15 v connector assi g nments
11-8 system manual c79000-g8576-c199-07 im 314 r i/o module slot 147, 155 im 300 i/o module slot 163 pin- pin row pin- pin row no. z b d no. z b d backplane conn. 1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v reset memr memw rdy db0 db1 db2 db3 db4 db5 db6 db7 0 v 0 v pesp adb0 adb1 adb2 adb3 adb4 adb5 adb6 adb7 adb8 adb9 adb10 adb11 basp 0 v shield adb12 adb13 adb14 adb15 0 v baspa 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v reset memr memw rdy db0 db1 db2 db3 db4 db5 db6 db7 0 v pesp adb0 adb1 adb2 adb3 adb4 adb5 adb6 adb7 adb8 adb9 adb10 adb11 basp 0 v + 5 v adb12 adb13 adb14 adb15 + 5 v + 5 v 0 v 0 v 0 v 0 v 0 v 0 v 0 v baspa backplane conn. 2 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v na0 na1 na2 na3 reseta 0 v 0 v 0 v 0 v 0 v 0 v 0 v sa0 sa1 sa2 sa3 nau 0 v 0 v 0 v 0 v 0 v 0 v 0 v reset 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v + 5 v + 5 v + 5 v reseta 0 v 0 v 0 v 0 v 0 v 0 v 0 v + 5 v + 5 v + 5 v nau 0 v 0 v 0 v 0 v 0 v 0 v connector assi g nments
11-9 system manual c79000-g8576-c199-07 connector assignments of the power supply units the terminals for the supply lines between the power supply unit and the backplane are in an 8-way connector (connector x1) at the rear of the unit. the following figures show the connector assignments. 5v/18a power supply units pins 4 to 6 are not fitted. 12345678 m2 (0v) 5v/18a 5v/40a power supply units 12345678 m2 (0v) 5v/40a the signal terminals of the power supply unit are in a 37-way connector (connector x2) at the rear of the unit. the following figure shows the connector assignments. pins 8 and 9 are reserved. m2 (0v) 12345678 910111213 14 15 16 17 18 19 reseta dsi gep nau 24v baspa u-batt reset 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 +15v bau reserved connector x1 connector x2 connector assi g nments
11-10 system manual c79000-g8576-c199-07 connector assignments of the 6es5 955-3na12 power supply unit the terminals of the supply lines between the power supply unit and the backplane are in an 8-way connector (subminiature, fitted with 8 high-current contacts, series d to mil-c24308). 12345678 m2 (0v) 5v/10a the signal terminals of the power supply unit are in a 37-way connector (plug connector, 37-way, series d to mil-c24308). basp m2 (0v) 12345678 910111213 14 15 16 17 18 19 dsi gep +15 v 24v/0.8a basp a u batt cpkl bau 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 -15v rlsa reset reset a ds nau hold unas- signed resin ir connector x1 connector x2 connector assi g nments
11-11 system manual c79000-g8576-c199-07 assignments of the backplane connector cpu 948 pin n pin row no. z b d backplane conn. 1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v reset memr memw rdy db0 db1 db2 db3 db4 db5 db6 db7 halt m 5 v pesp adb 0 adb 1 adb 2 adb 3 adb 4 adb 5 adb 6 adb 7 adb 8 adb 9 adb 10 adb 11 basp m 5 v ubat adb 12 adb 13 adb14 adb 15 ir ire irf irg dsi busen baspa backplane conn. 2 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v db 12 db 13 db 14 db 15 m 5 v nau bau +5v peu gep m 24 v + 24 v m 5 v db8 db9 db 10 db 11 pgbusx pgbusy m 5 v steu stoppa m 5 v r x d pero m 24 v m 5 v m 5 v t x d test m 24v connector assi g nments
11-12 system manual c79000-g8576-c199-07 assignments of the backplane connector cpu 928b pin n pin row no. z b d backplane conn. 1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v cpkl memr memw rdy db0 db1 db2 db3 db4 db5 db6 db7 halt m 5 v pesp adb 0 adb 1 adb 2 adb 3 adb 4 adb 5 adb 6 adb 7 adb 8 adb 9 adb 10 adb 11 basp m 5 v ubat adb 12 adb 13 adb14 adb 15 ir dsi busen baspa backplane conn. 2 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v db 12 db 13 db 14 db 15 m 5 v nau bau +5v peu gep m 24 v + 24 v m 5 v db8 db9 db 10 db 11 m 5 v steu stoppa m 5 v r x d pero m 24 v m 5 v m 5 v t x d test connector assi g nments
11-13 system manual c79000-g8576-c199-07 assignments of the backplane connectorcpu 928 pin n pin row no. z b d backplane conn. 1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v cpkl memr memw rdy db0 db1 db2 db3 db4 db5 db6 db7 halt m 5 v pesp adb 0 adb 1 adb 2 adb 3 adb 4 adb 5 adb 6 adb 7 adb 8 adb 9 adb 10 adb 11 basp m 5 v ubat adb 12 adb 13 adb14 adb 15 ir dsi busen baspa backplane conn. 2 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v db 12 db 13 db 14 db 15 m 5 v nau bau +5v peu gep m 24 v + 24 v m 5 v db8 db9 db 10 db 11 m 5 v steu stoppa m 5 v r x d pero m 24 v m 5 v m 5 v t x d test connector assi g nments
11-14 system manual c79000-g8576-c199-07 assignments of the backplane connector cpu 922 pin n pin row no. z b d backplane conn. 1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v cpkl memr memw rdy db0 db1 db2 db3 db4 db5 db6 db7 quitt halt m 5 v pesp adb 0 adb 1 adb 2 adb 3 adb 4 adb 5 adb 6 adb 7 adb 8 adb 9 adb 10 adb 11 basp m 5 v ubat adb 12 adb 13 adb14 adb 15 ir dsi busen baspa backplane conn. 2 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v m 5 v nau bau peu gep m 24 v + 24 v m 5 v m 5 v steu stoppa m 5 v r x d pero m 24 v m 5 v m 5 v t x d test connector assi g nments
11-15 system manual c79000-g8576-c199-07 assignments of the cpu front connector (pg interface) pin no. designation 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 housing/0 v/0v ext r x d vpg + 5 v dc + 24 v from bus 0 v/0 v int txd txd housing/0 v/0v ext r x d 24 v ground 20 ma/transmitter 0 v/0 v int 20 ma/receiver vpg + 5 v dc 0 v/0 v int connector assi g nments
11-16 system manual c79000-g8576-c199-07 assignments of the backplane connector: 923a coordinator pin n pin row no. z b d backplane conn. 1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v reset memr memw rdy db 0 db 1 db 2 db 3 db 4 db 5 db 6 db 7 halt m 5 v adb 0 adb 1 adb 2 adb 3 adb 4 adb 5 adb 6 adb 7 adb 8 adb 9 adb 10 adb 11 m 5 v ubat busen 1 busen 2 busen 3 busen 4 dsi backplane conn. 2 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v nau m 5 v steu stoppa pero m 5 v test connector assi g nments
11-17 system manual c79000-g8576-c199-07 assignments of the backplane connector: 923c coordinator pin n pin row no. z b d backplane conn. 1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v reset memr memw rdy db 0 db 1 db 2 db 3 db 4 db 5 db 6 db 7 halt m 5 v adb 0 adb 1 adb 2 adb 3 adb 4 adb 5 adb 6 adb 7 adb 8 adb 9 adb 10 adb 11 m 5 v ubat adb 12 adb 13 adb 14 adb 15 busen 1 busen 2 busen 3 busen 4 dsi backplane conn. 2 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 + 5 v nau m 24 v m 5 v m 5 v rxd 6 txd 6 rxd 4 txd 4 steu stoppa pero m 5 v rxd 8 txd 8 rxd 7 txd 7 rxd 5 txd 5 rxd 3 txd 3 rxd 1 txd 1 test connector assi g nments
11-18 system manual c79000-g8576-c199-07 assignments of the front connector for the coordinators pin no. designation 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 housing/0 v/0v ext receiver tty(-) private line +24 v private line transmitter tty (+) transmitter tty (-) housing/0 v/0v ext receiver tty (+) 24 v ground (20 ma (-) current sources) 20 ma (+) current source private line 20 ma (+) current source private line private line connector assi g nments
11-19 system manual c79000-g8576-c199-07 assignments of the backplane connectors of the ims im 300-3 im 300-5c im 300-5l im 301-3 pin pin row zb d pin row zb d pin row zb d pin row zb d b a c k p l a n e c o n n 1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 +5v 0v shield - pesp - cpkl adb0 - memr adb1 - memw adb2 - rdy adb3 - db0 adb4 - db1 adb5 - db2 adb6 0v db3 adb7 0v db4 adb8 0v db5 adb9 0v db6 adb10 0v db7 adb11 0v - basp 0v -0v- +5v 0v shield - pesp +5v cpkl adb0 - memr adb1 - memw adb2 - rdy adb3 - db0 adb4 +5v db1 adb5 +5v db2 adb6 0v db3 adb7 0v db4 adb 8 0v db5 adb 9 0v db6 adb 10 0v db7 adb 11 0v - basp 0v 0v 0v - +5v m - - pesp - reset adb1 - mrd adb2 - mwr adb3 - rdy adb4 - db0 adb5 - db1 adb6 - db2 adb7 - db3 adb8 - db4 adb9 - db5 adb10 - db6 adb11 - db7 basp - -m- -- - +5v 0v shield - pesp - cpkl adb0 - memr adb1 - memw adb2 - rdy adb3 - db0 adb4 - db1 adb5 - db2 adb6 0v db3 adb7 0v db4 adb 8 0v db5 adb 9 0v db6 adb 10 0v db7 adb 11 0v - basp 0v -0v- b a c k p l a n e c o n n 2 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 +5v - - -- - -- - -- - -- - -- - -- - -- - - nau - -- - 0v 0v - 0v 0v - 0v 0v - 0v 0v - 0v 0v - 0v 0v - +5v - - -- - -- - -- - -- - +5v +5v - +5v +5v - +5v +5v - -- - -- - 0v 0v - 0v 0v - 0v 0v - 0v 0v - 0v 0v - 0v 0v - +5v m - -- - -- - -- - -- - -- - -- - -- - - peu - -- - -- - -- - -- - -- - -- - -m- +5v - - -- - -- - -- - -- - +5v +5v - +5v +5v - +5v +5v - - nau - -- - 0v 0v - 0v 0v - 0v 0v - 0v 0v - 0v 0v - 0v 0v - connector assi g nments
11-20 system manual c79000-g8576-c199-07 im 301-5 im 304 pin row pin row pin z b d z b d b a c k p l a n e c o n n 1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 +5v 0v shield - pesp +5v cpkl adb0 - memr adb1 - memw adb2 - rdy adb3 - db0 adb4 +5v db1 adb5 +5v db2 adb6 0v db3 adb7 0v db4 adb 8 0v db5 adb 9 0v db6 adb 10 0v db7 adb 11 0v - basp 0v 0v 0v - +5v m - --- cpkl adb0 adb 12 memr adb1 adb 13 memw adb2 adb14 rdy adb3 adb15 db0 adb4 - db1 adb5 - db2 adb6 - db3 adb7 - db4 adb8 - db5 adb9 - db6 adb10 - db7 adb11 - - basp - -m- b a c k p l a n e c o n n 2 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 +5v - - --- --- --- --- +5v +5v - +5v +5v - +5v +5v - - nau - --- 0v 0v - 0v 0v - 0v 0v - 0v 0v - 0v 0v - 0v 0v - +5v m - db12 db8 - db13 db9 - db14 db10 - db15 db11 - - - - peu * -- - - - - peu *- --- --- --- --- --- --- -m- connector assi g nments
11-21 system manual c79000-g8576-c199-07 im 310-3 im 312-3 im 312-5 im 314 pin pin row zbd pin row zbd pin row zbd pin row zbd b a c k p l a n e c o n n 1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 +5v 0v shield+ - pesp +5v cpkl adb0 - memra db1 - memw adb2 - rdy adb3 - db0 adb4 +5v db1 adb5 +5v db2 adb6 0v db3 adb7 0v db4 - 0v db5 - 0v db6 - 0v db7 - 0v - basp 0v -0v- +5v 0v - - pesp +5v cpkl adb0 +5v memr adb1 +5v memw adb2 +5v rdy adb3 +5v db0 adb4 +5v db1 adb5 +5v db2 adb6 0v db3 adb7 0v db4 - 0v db5 - 0v db6 - 0v db7 - 0v nau basp 0v - 0v baspa +5v 0v -+ - pesp +5v cpkl adb0 +5v memr adb1 +5v memw adb2 +5v rdy adb3 +5v db0 adb4 +5v db1 adb5 +5v db2 adb6 0v db3 adb7 0v db4 - 0v db5 - 0v db6 - 0v db7 - 0v - basp 0v -0v- +5v m - - pesp +5v cpkla adb0 adb12 memr adb1 adb13 memw adb2 adb14 rdy adb3 adb15 db0 adb4 - db1 adb5 - db2 adb6 - db3 adb7 - db4 adb8 - db5 adb9 - db6 adb10- db7 adb11- dsi basp - -m- b a c k p l a n e c o n n 2 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 +5v 0v - --us --- --- --- - - +5v - - +5v - - +5v cpkla nau - --- 0v 0v - 0v 0v - 0v 0v - 0v 0v - 0v 0v - 0v 0v - +5v m - db12 db8 - db13 db9 cpkle db14 db10 - db15 db11 - - +5v - - +5v - - +5v - cpkla nau - --- mm- mm- mm- mm- mm- mm- connector assi g nments
11-22 system manual c79000-g8576-c199-07 assignments of the front blade connectors im 300-3 im 300-5c im 300-5l im 301 im 304 pin no. blade conn. 3 blade conn. 3 blade conn. 4 blade conn. 3, 4 blade conn. 3 blade conn. 4 blade conn. 3 blade conn. 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 shield - - - +peu - peu adb1 adb4 adb7 db1 db4 0v 0v 0v 0v 0v shield - - - + zgu - zgu adb0 adb3 adb6 0v db3 db6 0v 0v 0v 0v 0v - - cpkl memr memw pesp adb2 adb5 db0 db2 db5 db7 rdy basp - 0v 0v 0v ext + 5v + 5v + 5v - - adb 1 adb 4 adb 7 db 1 db 4 0v 0v 0v 0v 0v 0v ext + 5v + 5v + 5v - - adb 0 adb 3 adb 6 0v db 3 db 6 0v 0v 0v 0v 0v +5v - cpkl memr memw pesp adb 2 adb 5 db 0 db 2 db 5 db 7 rdy basp - 0v 0v 0v ext + 5v + 5v + 5v + 5v + 5v adb 1 adb 4 adb 7 db 1 db 4 0v 0v 0v 0v 0v 0v ext + 5v + 5v + 5v + 5v + 5v adb 0 adb 3 adb 6 0v db 3 db 6 0v 0v 0v 0v 0v +5v - cpkl memr memw pesp adb 2 adb 5 db 0 db 2 db 5 db 7 rdy basp - 0v 0v shield + 5 v + 5 v + 5 v peu1 peu2 adb1 adb4 adb7 db1 db4 m m m m m shield + 5 v + 5 v + 5 v + 5 v + 5 v adb0 adb3 adb6 m db3 db6 m m m m m + 5 v reset mrd mwr pesp adb2 adb5 db0 db2 db5 db7 rdy basp m m shield - - - +peu - peu adb1 adb4 adb7 db1 db4 0v 0v 0v 0v 0v shield - - - - zgu + zgu adb0 adb3 adb6 0v db3 db6 0v 0v 0v 0v 0v - - cpkl memr memw pesp adb2 adb5 db0 db2 db5 db7 rdy basp - 0v 0v shield + adb 4 - adb 4 + adb 5 - adb 5 + adb 6 - adb 6 + adb 7 - adb 7 + db 6 - db 6 + db 7 - db 7 + peu - peu rg 0 shield + adb 0 - adb 0 + adb 1 - adb 1 + adb 2 - adb 2 + adb 3 - adb 3 + db 3 - db 3 + db 4 - db 4 + db 5 - db 5 + zgu - zgu + memr - memr + memw - memw + pesp - pesp + basp - basp + db 0 - db 0 + db 1 - db 1 + db 2 - db 2 + rdy - rdy 0v + ad 12 - ad 12 + ad 13 - ad 13 + ad 14 - ad 14 + ad 15 - ad 15 + ad 6 - ad 6 + ad 7 - ad 7 + peu - peu - - + ad 8 - ad 8 + ad 9 - ad 9 + ad 10 - ad 10 + ad 11 - ad 11 + ad 3 - ad 3 + ad 4 - ad 4 + ad 5 - ad 5 + zgu - zgu + memr - memr + memw - memw + ale - ale + basp - basp + ad0 - ad 0 + ad 1 - ad 1 + ad 2 - ad 2 + rdy - rdy - + ad 12 - ad 12 + ad 13 - ad 13 + ad 14 - ad 14 + ad 15 - ad 15 + ad 6 - ad 6 + ad 7 - ad 7 + peu ** - peu ** 0v -0v + ad 8 - ad 8 + ad 9 - ad 9 + ad 10 - ad 10 + ad 11 - ad 11 + ad 3 - ad 3 + ad 4 - ad 4 + ad 5 - ad 5 (zgu/ par) * + memr - memr + memw - memw + ale - ale (basp/ paf) * + ad0 - ad 0 + ad 1 - ad 1 + ad 2 - ad 2 + rdy - rdy - * for parallel communication with the im 324u ** no signal in parallel communication connector assi g nments
11-23 system manual c79000-g8576-c199-07 pin no. im 310-3 im 312-3 im 312-5c im 314 blade connector 3 blade connector 4 blade connector 3 blade connector 3 blade connector 4 blade connector 3 blade connector 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 0v ext + adb 4 - adb 4 + adb 5 - adb 5 + adb 6 - adb 6 + adb 7 - adb 7 + db 6 - db 6 + db 7 - db 7 + peu - peu - 0v ext + adb 0 - adb 0 + adb 1 - adb 1 + adb 2 - adb 2 + adb 3 - adb 3 + db 3 - db 3 + db 4 - db 4 + db 5 - db 5 + zgu - zgu + memr - memr + memw - memw + pesp - pesp + basp - basp + db 0 - db 0 + db 1 - db 1 + db 2 - db 2 + rdy - rdy - 0v ext + adb 4 - adb 4 + adb 5 - adb 5 + adb 6 - adb 6 + adb 7 - adb 7 + db 6 - db 6 + db 7 - db 7 + peu - peu 5v 0v ext + adb 0 - adb 0 + adb 1 - adb 1 + adb 2 - adb 2 + adb 3 - adb 3 + db 3 - db 3 + db 4 - db 4 + db 5 - db 5 + zgu - zgu + memr - memr + memw - memw + pesp - pesp + basp - basp + db 0 - db 0 + db 1 - db 1 + db 2 - db 2 + rdy - rdy 0v shield - - - + peu - peu adb1 adb4 adb7 db1 db4 0v 0v 0v 0v 0v shield - - - - zgu + zgu adb0 adb3 adb6 0v db3 db6 0v 0v 0v 0v 0v - - cpkl memr memw pesp adb2 adb5 db0 db2 db5 db7 rdy basp - 0v 0v 0v ext + 5v + 5v + 5v + 5v + 5v adb 1 adb 4 adb 7 db 1 db 4 0v 0v 0v 0v 0v 0v ext + 5v + 5v + 5v + 5v + 5v adb 0 adb 3 adb 6 0v db 3 db 6 0v 0v 0v 0v 0v +5v - cpkl memr memw pesp adb 2 adb 5 db 0 db 2 db 5 db 7 rdy basp - 0v 0v 0v ext + 5v + 5v + 5v + 5v + 5v adb 1 adb 4 adb 7 db 1 db 4 0v 0v 0v 0v 0v 0v ext + 5v + 5v + 5v + 5v + 5v adb 0 adb 3 adb 6 0v db 3 db 6 0v 0v 0v 0v 0v +5v - cpkl memr memw pesp adb 2 adb 5 db 0 db 2 db 5 db 7 rdy basp - 0v 0v + ad 12 - ad 12 + ad 13 - ad 13 + ad 14 - ad 14 + ad 15 - ad 15 + ad 6 - ad 6 + ad 7 - ad 7 peua peua - - + ad 8 - ad 8 + ad 9 - ad 9 + ad 10 - ad 10 + ad 11 - ad 11 + ad 3 - ad 3 + ad 4 - ad 4 + ad 5 - ad 5 zgue zgue + memr - memr + memw - memw + ale - ale + basp - basp + ad0 - ad 0 + ad 1 - ad 1 + ad 2 - ad 2 + rdy - rdy - + ad 12 - ad 12 + ad 13 - ad 13 + ad 14 - ad 14 + ad 15 - ad 15 + ad 6 - ad 6 + ad 7 - ad 7 peue peue 0v 0v + ad 8 - ad 8 + ad 9 - ad 9 + ad 10 - ad 10 + ad 11 - ad 11 + ad 3 - ad 3 + ad 4 - ad 4 + ad 5 - ad 5 zgua zgua + memr - memr + memw - memw + ale - ale + basp - basp + ad0 - ad 0 + ad 1 - ad 1 + ad 2 - ad 2 + rdy - rdy +5v connector assi g nments
11-24 system manual c79000-g8576-c199-07 connector assi g nments
a-1 system manual c79000-g8576-c199-07 appendix given in the appendix are the  ordering information on products mentioned in this manual a
a-2 system manual c79000-g8576-c199-07 ordering information given in this section are the order numbers for the products mentioned and/or described in the system manual. the order numbers are arranged according to the chapters in which the corresponding products are mentioned. central controllers with power supply unit 6es5 955-3lc42 6es5 955-3lf42 6es5 955-3nc42 6es5 955-3nf42 6es5 188-3ua12 6es5 188-3ua22 6es5 188-3ua32 6es5 188-3ua51 with power supply unit 6es5 955-3na12 6es5 135-3ua42 expansion units with power supply unit 6es5 955-3lc42 6es5 183-3ua13 6es5 185-3ua13 with power supply unit 6es5 955-3lf42 6es5 185-3ua33 with power supply unit 6es5 955-3nc42 6es5 183-3ua22 6es5 185-3ua23 with power supply unit 6es5 955-3nf42 6es5 185-3ua43 with fan module 230/120v ac 24v dc 6es5 184-3ua11 6es5 184-3ua21 without power supply or fan module 6es5 187-5ua11 baffle 6es5 981-0da11 dummy front plates width 1 slot width 2 slots 6xf2 008-6kb00 6xf2 016-6kb00 for chapter 4 appendix
a-3 system manual c79000-g8576-c199-07 power supply units 230/120 v ac, isolated, 5 v dc/18 a 230/120 v ac, isolated, 5 v dc/40 a 24 v dc, isolated, 5 v dc/18 a 24 v dc, isolated, 5 v dc/40 a 6es5 955-3lc42 6es5 955-3lf42 6es5 955-3nc42 6es5 955-3nf42 lithium backup battery 3.6 v 6ew1 000-7aa (with ewk lz s2) rechargeable battery with two screws 6es5 980-0nc11 (with ewk lz s2) fan subassembly with fan and terminals for rechargeable battery 6es5 988-3nb41 (with wkf rzf) filter holder, guides, 10 filter mats 6es5 981-0fa41 (with wkf rzf) filter mats (10) 6es5 981-0ea41 (with wkf rzf) battery compartment battery compartment holder c98130-a1155-b21 (with wkf rzf) c98130-a1155-b20 (with wkf rzf) battery compartment and battery compartment holder c98130-a1155-a7 (with wkf rzf) fuses for 3lc41 4 a, slow, 250 v fuses for 3lf41 8 a, fast, 250 v fuses for 3nc41 20 a, super-fast, 65 v fuses for 3nf41 30 a, super-fast, 65 v c97327-z1006-c130 c98327-s1001-c23 c98327-s1001-c19 c98327-s1001-c24 (with wkf rzf) caps for terminals (4) c98130-a1102-c49 (with wkf rzf) 951 load power supply module 230/120 v ac, isolated, 24 v/4 a 6es5 951-4lb11 fuse, 1 a slow fuse, 2 a slow front connector, 20-way for crimp connection, 40 mm spring contacts front connector, 20-way for screw connection, 40 mm w79054-l4011-t100 w79054-l4011-t200 6es5 497-4ua42 6xx3 070 6es5 497-4ub42 24v dc, not isolated, 10a 6es5 955-3na12 15 v auxiliary submodule battery module fan unit backup battery 6es5 956-0aa12 6xg3 400-2ck00 6es5 988-3na11 6ew1 000-7aa appendix
a-4 system manual c79000-g8576-c199-07 cpus cpu 948-1 (640 kbyte user memory) cpu 948-2 (1664 kbyte user memory) 6es5 948-3ua13 6es5 948-3ua23 cpu 928b 6es5 928-3ub21 cpu 928 6es5 928-3ua21 cpu 922 6es5 922-3ua11 374 memory cards 256 bbytes 512 bbytes 1028 bbytes 2048 bbytes 4112 bbytes 6es5 374-2fh21 6es5 374-2fj21 6es5 374-2fk21 6es5 374-2fl21 6es5 374-2fm21 376 memory cards 16 bbytes 32 bbytes 64 bbytes 6es5 376-0aa11 6es5 376-0aa21 6es5 376-0aa31 377 memory cards 16 bbytes 32 bbytes 64 bbytes 64 kbytes (with backup battery) backup battery 6es5 377-0aa11 6es5 377-0aa21 6es5 377-0aa32 6es5 377-0ba31 6es5 980-0da11 interface submodules pg submodule tty submodule for 20 ma current loop v.24 (rs-232c) submodule rs422-a/485 submodule sinec l1 submodule 6es5 752-0aa53 6es5 752-0aa12 6es5 752-0aa22 6es5 752-0aa42 6es5 752-0aa62 cover for submodule receptacle c79458-l957-b51 bt 777 bus terminal 6es5 777-xxx00 standard connecting cables cpu 948/928b - pg 7xx cpu 928b - cp 544/525/524 (rs422-a/485) cpu 928b - cp 544/525/524 (tty) cpu 928b - cp 544/525/524 (v.24) cpu 928b - dr 210/dr 211 dr 230/dr 231 (tty/v.24) 6es5 734-2xxx0 6es5 725-7xxx0 6es5 726-1xxx0 6es5 726-8xxx0 6es5 726-5xxx0 (xxx = simatic length code, see catalog) for chapter 5 appendix
a-5 system manual c79000-g8576-c199-07 coordinators 923a coordinator 6es5 923-3ua11 923c coordinator 6es5 923-3uc11 coding plug front cover connecting cable for cp 530, 143 and 5430 0.9 m 2.5 m c79334-a3011-b12 c79451-a3079-c251 6es5 725-0ak00 6es5 725-0bc50 interface modules im 300-3 6es5 300-3ab11 im 300-5c 6es5 300-5ca11 im 300-5l 6es5 300-5lb11 im 301-3 6es5 301-3ab13 im 301-5 6es5 301-5ca12 im 304 6es5 304-3ub11 im 310 6es5 310-3ab11 im 312-3 (0.5 m) im 312-3 (0.95 m) 6es5 312-3ab11 6es5 312-3ab31 im 312-5 (0.5 m) im 312-5 (1.5 m) 6es5 312-5ca11 6es5 312-5ca21 im 314 6es5 314-3ua11 im 314r 6es5 314-3ur11 connecting cable (xxx = simatic length code, see catalog) 6es5-721-0xxx connecting cable for im 300-5lb11 length 0.5 m length 1.5 m 6es5 705-0af00 6es5 705-0bb0 terminator for im 314 for im 312 and im 301-3 for im 301-3 6es5 760-1aa11 6es5 760-0ab11 6es5 760-0aa11 for chapter 6 for chapter 7 appendix
a-6 system manual c79000-g8576-c199-07 digital input/output modules modules adhesive label 6es5 420-4ua13 6es5 430-4ua13 6es5 431-4ua12 6es5 432-4ua12 6es5 434-4ua12 6es5 435-4ua12 6es5 436-4ua12 6es5 436-4ub12 6es5 441-4ua13 6es5 451-4ua13 6es5 453-4ua12 6es5 454-4ua13 6es5 455-4ua12 c79451-a3079-c751 c79451-a3079-c752 c79451-a3079-c732 c79451-a3079-c733 c79451-a3079-c734 c79451-a3079-c735 c79451-a3079-c736 c79451-a3079-c737 c79451-a3079-c753 c79451-a3079-c755 c79451-a3079-c740 c79451-a3079-c756 c79451-a3079-c742 6es5 456-4ua12 6es5 456-4ub12 6es5 457-4ua12 6es5 458-4ua12 6es5 458-4uc11 6es5 482-4ua11 c79451-a3079-c743 c79451-a3079-c744 c79451-a3079-c727 c79451-a3079-c745 e89100-b2749-c100 c79451-a3079-c749 front connectors crimp terminals, single-width, 42-way crimp terminals, double-width, 42-way crimp terminals, double-width, 20-way screw terminals, single-width, 42-way screw terminals, double-width, 42-way screw terminals, double-width, 25-way screw terminals, double-width, 20-way 6es5 497-4ua12 6es5 497-4ua22 6es5 497-4ua42 6es5 497-4ub31 6es5 497-4ub12 6es5 497-4ub22 6es5 497-4ub42 ip 257 6es5 257-4ua11 local bus for di/dq 482 6es5 751-2aa11 mini spring contacts (250 single contacts) 6xx3070 crimping tool 6xx3071 ferrules to din 46228 extraction (releasing) tool 6es5 497-4uc11 set of labels for addresses 6es5 497-4ud11 coding jumper (to change over the enable mode) w79070-g2602-n2 fuse for 6es5 456-4ub12 3.5 a, fast/250 v ul/csa w79054-l1021-f350 for chapter 8 appendix
a-7 system manual c79000-g8576-c199-07 fuse for 6es5 455-4ua12 and 6es5 455-4ua12 6.3 a, fast/250 v w79054-l1011-f630 fuse for 6es5 482-4ua11 6.3 a/125 v w79054-m1041-t630 light guide k for front connector with crimp terminal 6es5 497-4ul11 light guide s for front connector with screw terminal 6es5 497-4ul21 analog input/output modules modules adhesive labels 6es5 460-4ua13 6es5 463-4ua12 6es5 465-4ua12 6es5 470-4ua12 6es5 470-4ub12 6es5 470-4uc12 c79451-a3079-c723 c79451-a3079-c746 c79451-a3079-c748 c79451-a3079-c724 c79451-a3079-c725 c79451-a3079-c726 front connectors crimp terminals, single-width, 42-way crimp terminals, double-width, 42-way crimp terminals, double-width, 20-way screw terminals, single-width, 42-way screw terminals, double-width, 42-way screw terminals, double-width, 25-way screw terminals, double-width, 20-way 6es5 497-4ua12 6es5 497-4ua22 6es5 497-4ua42 6es5 497-4ub31 6es5 497-4ub12 6es5 497-4ub22 6es5 497-4ub42 mini spring contacts (250 single contacts) 6xx3070 crimping tool 6xx3071 ferrules to din 46228 extraction (releasing) tool 6es5 497-4uc11 set of labels for addresses 6es5 497-4ud11 for chapter 9 appendix
a-8 system manual c79000-g8576-c199-07 range cards modules features range card 6es5 460-4ua13 6es5 465-4ua12  12.5/50/500mv/pt 100  50/500mv/pt 100  1v  5v  10v  20ma 4 to 20ma/2-wire transducer 4 to 20ma/4-wire transducer 6es5 498-1aa11 6es5 498-1aa11 6es5 498-1aa21 6es5 498-1aa61 6es5 498-1aa31 6es5 498-1aa41 6es5 498-1aa51 6es5 498-1aa71 appendix
b-1 system manual c79000-g8576-c199-07 guidelines for handling electrostatically-sensitive devices (esd) section contents page b.1 what is esd? b-2 b.2 electrostatic charging of persons b-3 b.3 general protective measures against electrostatic discharge damage b-4 chapter overview b
b-2 system manual c79000-g8576-c199-07 b.1 what is esd? all electronic modules are equipped with large-scale integrated ics or components. due to their design, these electronic elements are very sensitive to overvoltages and thus to any electrostatic discharge. these e lectrostatically- s ensitive d evices are commonly referred to by the abbreviation esd . electrostatically-sensitive devices are labeled with the following symbol: ! caution electrostatically-sensitive devices are subject to voltages that are far below the voltage values that can still be perceived by human beings. these voltages are present if you touch a component or the electrical connections of a module without previously being electrostatically discharged. in most cases, the damage caused by an overvoltage is not immediately noticeable and results in total damage only after a prolonged period of operation. definition guidelines for handlin g electrostaticall y -sensitive devices ( esd )
b-3 system manual c79000-g8576-c199-07 b.2 electrostatic charging of persons every person with a non-conductive connection to the electrical potential of its surroundings can be charged electrostatically. figure b-1 shows you the maximum values for electrostatic voltages which can build up on a person coming into contact with the materials indicated in the figure. these values are in conformity with the specifications of iec 801-2. voltage in kv 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 (kv) 510 20 30 40 50 60 70 80 90 100 relative air humidity in % 1 3 1 synthetic material 2 wool 3 antistatic material, for example, wood, or concrete 2 figure b-1 electrostatic voltages which can build up on a person charging guidelines for handlin g electrostaticall y -sensitive devices ( esd )
b-4 system manual c79000-g8576-c199-07 b.3 general protective measures against electrostatic discharge damage make sure that the personnel, working surfaces, and packaging are sufficiently grounded when handling electrostatically-sensitive devices. you thus avoid electrostatic charging. you should touch electrostatically-sensitive devices only if it is unavoidable (for example, during maintenance work). hold modules without touching the pins of components or printed conductors. in this way, the discharged energy cannot affect the sensitive devices. if you have to carry out measurements on a module, you must discharge your body before you start the measurement by touching grounded metallic parts. use grounded measuring devices only. ensure sufficient grounding avoid direct contact guidelines for handlin g electrostaticall y -sensitive devices ( esd )
index-1 system manual c79000-g8576-c199-07 index a address label, 8-20 addressing cyclic sampling, 9-12, 9-58, 9-112 selective sampling, 9-12, 9-58, 9-112 addressing switch analog input/output modules, 9-4, 9-35, 9-50, 9-106 digital input/output modules, 8-4 air filter, 4-64 application cor 923a, 6-15 cor 923c, 6-18 cpu 922, 5-71 cpu 928, 5-62 cpu 928 -3ua21, 5-54 cpu 928b, 5-42 cpu 928b -3ub21, 5-30 cpu 948, 5-17 cpu 948 -3ua13, 5-2 cpu 948 -3ua23, 5-2 auxiliary submodule, 15 v, 4-63 b backup battery power supply units, 4-31 psu 6es5 955-3na12, 4-66 ram submodules 377, 5-87 base address, 6-25 setting, 6-22 basic functions, power supply units, 4-20 basp analog input modules, 9-9, 9-55, 9-110 digital input modules, 8-3 digital output modules, 8-3 basp signal, 6-14 battery voltage power supply units, 4-21 psu 6es5 955-3na12, 4-58, 4-70 broken wire monitoring, extended pt 100 mea- suring range, 9-22, 9-66 broken wire signal, 9-8, 9-54 bus arbitration, 6-15, 6-16, 6-18, 6-19 bus enable, 6-16, 6-19 bus enable assignment, 6-16 sequence, 6-19 bus enable signal, 6-16, 6-19 bus lock signal, 6-20 bus pcb, 4-3 c cabinet assembly, for emc, 3-9 cable clamps, 3-16 cable duct, 4-3 cables, power supply units, 4-27 cabling, fan submodule, 4-73 central controller, installing, 4-6 central grounding, 3-24 central programmer connection, 6-18 centrally grounded supply, 3-24 checklist, emc measures, 3-19 communication flag area, 6-7 communication flag areas, setting, 6-6 communication flags, 6-15, 6-16, 6-20 communication memory, 6-15, 6-16, 6-18 addressing, 6-6, 6-7 compensating box, connection, 9-19, 9-63 connecting loads, 9-117, 9-118 connector assignment 6es5 955-3na12 power supply unit, 11-10 coordinator 923 a, 11-16 coordinator 923 c, 11-17 cpu 922, 11-14 cpu 928, 11-13 cpu 928b, 11-12 cpu 948, 11-11 front connector of the cpus (pg interface), 11-15 front connectors of the coordinators, 11-18 ims, 11-19 power supply units, 11-9 psu 6es5 955-3na12, 11-10
index-2 system manual c79000-g8576-c199-07 connector assignments, power supply units, 11-9 connector assignments of the backplane eu 183u, eu 184u, eu 187u, 11-5 eu 185u, 11-6 s5-135u/155u cc, 11-2 controls and indicators cor 923c, 6-23 cpu 922, 5-74 cpu 928, 5-65 cpu 928 -3ua21, 5-57 cpu 928b, 5-35, 5-47 cpu 948, 5-20 cpu 948 -3ua13, 5-6 cpu 948 -3ua23, 5-6 im 300, 7-4 im 301, 7-11 im 304, 7-15 psu 6es5 955-3na12, 4-58 coordinator location of jumper sockets, 6-4 modes, 6-13 normal operation, 6-13 stop in the event of fault, 6-13 test mode, 6-14 cor 923a, 6-6 application, 6-15 design, 6-15 mode switch, 6-17 principle of operation, 6-16 cor 923c, 6-6, 6-12, 6-15 activating addresses, 6-25 application, 6-18 controls, 6-23 design, 6-19 indicators, 6-23 principle of operation, 6-19 setting the coordination section, 6-24 setting the dil switches, 6-24 setting the pg multiplexer, 6-25 switching off the coordination signal, 6-27 coupling capacitive coupling, 3-4 direct coupling, 3-4 inductive coupling, 3-4 mechanisms, 3-3 radiated interference, 3-4 current limiting, two-wire transducers, 9-46 current sensors, connection, 9-17 current/voltage measurement, 9-78, 9-85 cyclic program processing, 6-13, 6-14 cyclic sampling, 9-8, 9-54 d data format setting, 9-88 setting, 9-48, 9-81 design cor 923a, 6-15 cor 923c, 6-19 cpu 922, 5-71 cpu 928, 5-62 cpu 928 -3ua21, 5-54 cpu 928b, 5-42 cpu 928b -3ub21, 5-30 cpu 948, 5-17 cpu 948 -3ua13, 5-2 cpu 948 -3ua23, 5-2 differential measurement, 9-78, 9-96 distributed arrangement of monitor and plc, 3-31 double addressing, 6-6, 6-21 e electrical connection with process i/os, 3-23 electromagnetic compatibility, 3-2 emc, basic rules, 3-6 emc measures, specific, 3-17 enable, switching off, 9-5 enable circuit, digital input/output modules, 8-5 enable input, 9-5, 9-36, 9-51, 9-107 switching off, 9-107 enable inputs, functioning, 8-6 enable switching off, 9-36, 9-51 enable time, 6-16, 6-19 equipotential bonding conductor, 3-14, 9-17 example of an electrical installation, 3-23 f fan, 4-3 failure, 4-50 removing, 4-33 replacing, 4-41, 4-67 fan lock, releasing, 4-33 fan submodule connecting, 4-72 setting, 4-72 fault detection, monitoring module, 10-4 fault indications power supply units, 4-36 psu 6es5 955-3na12, 4-65 index
index-3 system manual c79000-g8576-c199-07 fault leds, fan submodule 6es5 988-3la11, 4-73 fault register, 6-27 fb 40 function block, 9-9, 9-55, 9-110 filter mat, replacing, 4-46 filter subdrawer, fitting, 4-34 floating modules, 3-27 four-wire circuit, 9-118 front connector, 4-9, 6-19 463 analog input module, 9-49 466 analog input module, 9-104 470 analog input module, 9-106 front panel, monitoring module, 10-2 front plate, 6-19 cpu 922, 5-74 cpu 928, 5-65 cpu 928 -3ua21, 5-57 cpu 928b, 5-47 cpu 928b -3ub21, 5-35 cpu 948, 5-20 fan submodule 6es5 998-3la11, 4-70 power supply units, 4-21 psu 6es5 955-3na12, 4-58 front plate width, 6-15, 6-19 full duplex operation, rs422 a/485 submodule, 5-112 fusing, 3-21, 8-24 g global memory access, 6-15 grounding distributed arrangement of monitor and plc, 3-31 inactive metal parts, 3-6, 3-8 plcs, 3-23 i i/o byte, changeover, di/dq 482, 8-13 i/o modules, 8-2 analog input/output modules, 9-2 digital input/output modules, 8-2 individual locking, 4-3 inductive loads, 8-25 inputs/outputs fan submodule 6es5 988-3la11, 4-70 power supply units, 4-21 psu 6es5 955-3na12, 4-59 installing, monitoring, 10-2 interchange of data, 6-15 interface submodules installing, 5-93 pg submodule, 5-95 removing, 5-94 rs422 a/485 submodule, 5-112 sinec l1 submodule, 5-118 tty submodule, 5-106 use, 5-92 v.24 submodule, 5-99 interfaces cpu 928b, 5-43 cpu 928b -3ub21, 5-31 cpu 948, 5-13, 5-27 cpu 948 -3ua13, 5-13 cpu 948 -3ua23, 5-13 interference, 3-2 measures for interference-free operation, 3-17 interference source, 3-4 interference-free installation centralized interface circuits, 3-28 distributed interface circuits, 3-28 j jumper settings cor 923a, 6-4 cor 923c, 6-4, 6-27 cpu 928b, 5-33, 5-45 cpu 948, 5-18 cpu 948 -3ua13, 5-3 cpu 948 -3ua23, 5-3 im 300-3, 7-5 im 300-5, 7-6, 7-8 im 301, 7-12 im 304, 7-16 im 314, 7-18 pg submodule, 5-97 power supply units, 4-25 psu 6es5 955-3na12, 4-60 rs422 a/485 submodule, 5-114 sinec l1 submodule, 5-120 tty submodule, 5-108 v.24 submodule, 5-101 l labeling field, 8-14, 9-10, 9-39, 9-56, 9-110 index
index-4 system manual c79000-g8576-c199-07 leds cor 923c, 6-23 cpu 922, 5-76 cpu 928 , 5-67 cpu 928 -3ua21, 5-58 cpu 928b, 5-37, 5-49 cpu 948, 5-23 cpu 948 -3ua13, 5-9 cpu 948 -3ua23, 5-9 digital input/output modules, 8-4 fan submodule 6es5 99-3la11, 4-70 monitoring module, 10-2 power supply units, 4-36 psu 6es5 955-3na12, 4-65 leds and controls, power supply units, 4-22 leds for fault indication and signaling cpu 922, 5-77 cpu 928, 5-68 cpu 928b, 5-49 cpu 928 -3ua21, 5-59 cpu 928b -3ub21, 5-37 cpu 948, 5-23 cpu 948 -3ua13, 5-9 cpu 948 -3ua23, 5-9 lightning protection, 3-13 lithium battery fitting in psu, 4-31 replacing, 4-41 load circuit, disconnecting, 8-26 load power supply, 3-20 load voltage, 9-46 loads, connection, 9-117 location of jumpers power supply units, 4-29 psu 6es5 955-3na12, 4-60 locking bar, 4-3 m main switch, 3-21 measured-value representation current measuring range 4 to 20 ma, 9-28, 9-71 different measuring ranges, 9-98 output current/voltage, 9-119 pt 100, 9-26, 9-70 two's complement, 9-24, 9-68 measurement with respect to ground, 9-78, 9-95 measuring range 466 analog input module, 9-77 setting, 9-80 measuring range exceeded, 9-8, 9-54 memory cards 374, 5-80 erasing, 5-80 inserting, 5-80 programming, 5-80 memory page, 6-20 memory submodules 376, 5-82 erasing, 5-82 inserting, 5-82 programming, 5-82 memory submodules 377, 5-84 backup battery, 5-87 inserting, 5-88 programming, 5-84 removing, 5-89 with battery backup, 5-85 me?bereich, einstellen, 9-87 mode, setting, 9-31, 9-73 mode switch, 6-17, 6-23, 9-4, 9-35, 9-50, 9-106 coordinator, 6-13 cor 923a, 6-17 cor 923c, 6-23 cpu 922, 5-75 cpu 928 , 5-66 cpu 928 -3ua21, 5-58 cpu 928b , 5-48 cpu 928b -3ub21, 5-36 cpu 948, 5-21 cpu 948 -3ua13, 5-7 cpu 948 -3ua23, 5-7 module, mounting width, 4-8 momentary-contact mode switch cpu 922, 5-75 cpu 928 , 5-66 cpu 928b, 5-48 cpu 928 -3ua21, 5-58 cpu 928b -3ub21, 5-36 cpu 948, 5-21 cpu 948 -3ua13, 5-7 cpu 948 -3ua23, 5-7 monitor connection, 3-30 monitoring for bus assignment, 6-20 monitoring function, power supply units, 4-20 mounting in cabinets, 3-9 mounting on racks, 3-11 index
index-5 system manual c79000-g8576-c199-07 mounting on walls, 3-11 multiplex interface, 6-21 multiprocessor operation, 1-1, 6-2, 6-15 starting, 6-3 startup phase, 6-12 n non-floating modules, 3-26 o operator functions, 6-15 outputs, 8-22 parallel connection, 8-22 overall reset cpu 922, 5-75, 5-78 cpu 928, 5-69 cpu 928 , 5-66 cpu 928b, 5-48 cpu 928b , 5-51 cpu 928 -3ua21, 5-58, 5-60 cpu 928b -3ub21, 5-36, 5-39 cpu 948, 5-21, 5-25 cpu 948 -3ua13, 5-7, 5-11 cpu 948 -3ua23, 5-7, 5-11 p page memory, 6-21 pg interfaces cpu 928b, 5-31, 5-43 cpu 948, 5-27 cpu 948 -3ua13, 5-13 cpu 948 -3ua23, 5-13 pg multiplexer, of cor 923c, 6-21 pg mux, 6-27 pg submodule, 5-95 pin assignments pg submodule, 5-96 rs422 a/485 submodule, 5-113 sinec l1 submodule, 5-119 tty submodule, 5-107 v.24 submodule, 5-100 power dissipation, in cabinets, 3-36 power supplies ac, 3-22 centrally grounded, 3-24 control circuits, 3-20 grounded, 3-23 load circuits, 3-20 ungrounded, 3-25 power supply failure, 4-49 for programmable controllers, 3-18 types, 4-19 power supply unit, 4-3 connecting, 4-23 fitting, 4-30 removing, 4-28 setting, 4-23 switching on, 4-35 process inputs, scanning, 8-9, 8-10 process interrupt processing cpu 922, 5-72 cpu 928, 5-63 cpu 928 -3ua21, 5-55 cpu 928b, 5-44 cpu 928b -3ub21, 5-32 processing levels cpu 922, 5-71 cpu 928, 5-62 cpu 928 -3ua21, 5-54 cpu 928b, 5-30, 5-42 cpu 948, 5-17 cpu 948 -3ua13, 5-2 cpu 948 -3ua23, 5-2 programmable controller power supply, 3-18, 3-24 validity check, 4-11 protection, 3-21 pt 100, connection, 9-65 pt 100 measuring range, 9-26 q quenching circuitry, 8-25 quenching devices, selection, connection, 8-26 index
index-6 system manual c79000-g8576-c199-07 r radiated interference, 3-4 rechargeable battery, connecting, 4-33 reference potential, 3-7 removing and inserting cpu 922 , 5-73 cpu 928 -3ua21, 5-56 cpu 928 , 5-64 cpu 928b, 5-45 cpu 928b -3ub21, 5-33 cpu 948, 5-19 cpu 948 -3ua13, 5-4 cpu 948 -3ua23, 5-4 modules, 8-18, 9-13, 9-42, 9-59, 9-91, 9-113 monitoring module, 10-6 replacing the battery power supply units, 4-41 psu 6es5 955-3na12, 4-66 reset automatic, 6-13 cpu 948, 5-21 reset cpu 922, 5-75, 5-78 cpu 928, 5-69 cpu 928 , 5-66 cpu 928 -3ua21, 5-58, 5-60 cpu 928b, 5-48 cpu 928b -3ub21, 5-36, 5-39, 5-51 cpu 948 -3ua13, 5-7, 5-11 cpu 948 -3ua23, 5-7, 5-11 resistance thermometers, connection, 9-20 restart, 5-51 automatic, 6-13 cpu 922, 5-75, 5-78 cpu 928, 5-69 cpu 928 , 5-66 cpu 928b, 5-48 cpu 928 -3ua21, 5-58 cpu 928b -3ub21, 5-36, 5-39 cpu 948, 5-21, 5-25 cpu 948 -3ua13, 5-7, 5-12 cpu 948 -3ua23, 5-7, 5-12 routing of lines, 3-6 rs422 a/485 submodule, 5-112 rules for ensuring emc, 3-6 s s5 bus, 6-16 selective sampling, 9-9, 9-54 semaphores, 6-16, 6-20 sensors, connection, 9-48, 9-96 serial interface, 6-21 selection method, 6-22 shielding, 3-15 distributed arrangement of monitor and plc, 3-31 shielding of cables/lines, 3-15 short-circuit protection, 8-24 signal lines, connection, 8-21, 9-16, 9-45, 9-62, 9-94, 9-116 signal output, 8-3 signaling circuits fan submodule, 4-72 of the power supply units, 4-26 signaling function, power supply units, 4-20 sinec h1 lan, routing of cables, 3-12 sinec l1 lan, routing of cables, 3-12 sinec l1 submodule, 5-118 sinec l2 lan, routing of cables, 3-12 slot, 6-22 setting the number of cpu slots, 6-6 slots, slots required by cpu, 1-1, 6-2 standard connecting cables pg submodule, 5-98 rs422 a/485 submodule, 5-117 tty submodule, 5-109 v.24 submodule, 5-102 start, 6-13 manual, 6-13 start address, 8-15 start address, subaddress, analog input/output modules, 9-11, 9-40, 9-56, 9-111 startup cpu 922, 5-78 cpu 928 , 5-69 cpu 928 -3ua21, 5-60 cpu 928b, 5-39, 5-51 cpu 948, 5-25 cpu 948 -3ua13, 5-11 cpu 948 -3ua23, 5-11 startup of cc, brief instructions, 4-10 startup of the programmable controller, 4-10 station number, 6-22 status indicators cpu 922, 5-76 cpu 928 , 5-67 cpu 928b, 5-49 cpu 928 -3ua21, 5-58 cpu 928b -3ub21, 5-37 cpu 948, 5-22 cpu 948 -3ua13, 5-8 cpu 948 -3ua23, 5-8 index
index-7 system manual c79000-g8576-c199-07 stop state, 6-13 supply line l+ and l, disconnecting, 8-26 systems, installation to emc requirements, 3-2 t technical specifications 374 memory cards, 5-81 376 memory submodules, 5-83 377 memory submodules, 5-90 420 digital input module, 8-30 430 digital input module, 8-32 431 digital input module, 8-34 432 digital input module, 8-36 434 digital input module, 8-39 435 digital input module, 8-42 436-4ua12 digital input module, 8-44 436-4ub12 digital input module, 8-46 441 digital output module, 8-48 451 digital output module, 8-50 453 digital output module, 8-52 454 digital output module, 8-54 455 digital output module, 8-56 456-4ua12 digital output module, 8-58 456-4ub12 digital output module, 8-60 457 digital output module, 8-62 458-4ua12 digital output module, 8-64 458-4uc11 digital output module, 8-67, 8-69 coordinators, 6-28 cpu 922, 5-79 cpu 928, 5-70 cpu 928 -3ua21, 5-61 cpu 928b, 5-40, 5-52 cpu 948, 5-28 cpu 948 -3ua13, 5-15 cpu 948 -3ua23, 5-15 expansion units, 4-18 fan submodule 6es5 998-3la11, 4-74 interface modules, 7-21 interface submodules, 5-122 monitoring module, 10-14 power supply units, 4-51 psu 6es5 955-3na12, 4-68 time-controlled program processing, 9-9, 9-55 time-division multiplex operation, 6-16, 6-19 transducers, connection, 9-23, 9-67 tripping current, 9-8, 9-54 tty submodule, 5-106 two-wire switches, 8-27 v v.24 interface, 5-99 v.24 submodule, 5-99 vector register, 6-21 voltage selector switch, setting, 4-34 voltage sensors, connection, 9-17 w wall mounting, 3-11 wiring, 8-19 index
index-8 system manual c79000-g8576-c199-07 index
system manual 6es5998-0sh21-07 1  siemens ag a&d as e 81 oestliche rheinbrueckenstr. 50 d-76181 karlsruhe federal republic of germany please check any industry that applies to you:  automotive  chemical  electrical machinery  food  instrument and control  nonelectrical machinery  petrochemical  pharmaceutical  plastic  pulp and paper  textiles  transportation  other ___________ from: your name: _____________________________ your title: _____________________________ company name: __________________________ street: __________________________ city, zip code __________________________ country: __________________________ phone: __________________________
2 system manual 6es5998-0sh21-07 additional comments: ___________________________________ ___________________________________ ___________________________________ ___________________________________ ___________________________________ ___________________________________ ___________________________________ ___________________________________ ___________________________________ ___________________________________ ___________________________________ ___________________________________ remarks form your comments and recommendations will help us to improve the quality and usefulness of our publications. please take the first available opportunity to fill out this questionnaire and return it to siemens. please give each of the following questions your own personal mark within the range from 1 (very good) to 5 (poor). 1. do the contents meet your requirements? 2. is the information you need easy to find? 3. is the text easy to understand? 4. does the level of technical detail meet your requirements? 5. please rate the quality of the graphics/tables:


▲Up To Search▲   

 
Price & Availability of S5-155U

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X